[SHTM 03-01 Part A – PDF page 173]
Appendix 5: Recommended airflow rates in m3/s through a doorway between rooms of different cleanliness to control cross- contamination
Table A4 Flows through dooorways
Room
Dirty Transitional Clean Sterile
class
Sterile Hatch Single door
0 or 0.28a
Double door
0 or 0.57a
Clean Single door
0 or 0.28a
Double door
0 or 0.57a
Single door
0 or 0.28a
Transition al
Double door
0 or 0.57a
Dirty Single door
0
Double door
0
Open single door = 0.80 m x 2.01 m high Open double door = 1.80 m x 2.01 m high
Open single door = 0.80 m x 2.01 m high Open double door = 1.80 m x 2.01 m high
Open single door = 0.80 m x 2.01 m high Open double door = 1.80 m x 2.01 m high
Designers’ notes:
The degree of protection required at an open doorway between rooms is dependent on the degree of difference in cleanliness between them.
Flow-rate required between rooms within the same class tends to zero as class reduces.
If two rooms are of equal cleanliness, no flow is required (in practice there will be an interchange in either direction) and the design of the air movement will assume zero airflow. In certain cases, however, interchange is not permitted, and a protection airflow of 0.28 is assumed in the design – for example, in the case of a preparation room used as a “lay up”.
[SHTM 03-01 Part A – PDF page 174]
Appendix 6: Typical approximate pressures in an operating suite when a given door is open
Typical approximate effect on other rooms
Table A5 Pressure in room with open door
Room Pressure (Pa) pressure
Door open between Typical approximate
in these rooms (Pa)
resultant
0
Operating theatre and corridor
Anaesthetic Preparation – lay-up Utility
12
or
–6
Preparation – sterile pack store
Scrub bay and corridor
0
5
26
Preparation – lay-up Utility
–9
Operating theatre and anaesthetic room (or other series room with double doors)
17
22
Preparation – sterile pack store
No change
Operating theatre and Utility room
or
25
Operating theatre and preparation room
30
Anaesthetic room and corridor
Preparation – lay-up Utility
–6
Operating theatre
20
(or other series room with double doors)
0
25
Preparation – sterile pack store
No change
Preparation room and corridor
or
0
Utility room and corridor
0 No change
Utility room and outer corridor
Notes:
The room differential pressure protects against reverse flows when the door is closed.
The flow of air through a doorway protects against reverse airflow when the door is open.
Pressure stabilisers control flow and ensure a known airflow path between rooms when doors are closed and also reduce backflow between rooms when doors to other rooms are open.