SHTM 03-01 Part A: Appendix 5: Recommended airflow rates in m3/s through a doorway between rooms of different cleanliness to control cross-contamination / Appendix 6: Typical approximate pressures in an operating suite when a given door is open

Ventilation for Healthcare - Design and validation (SHTM 03-01 Part A) · PDF pages 173–174 of 227 · Source file: shtm-03-01-part-a-v30-feb-2022.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 03-01 Part A – PDF page 173]

Appendix 5: Recommended airflow rates in m3/s through a doorway between rooms of different cleanliness to control cross- contamination

Table A4 Flows through dooorways

Room

Dirty Transitional Clean Sterile

class

Sterile Hatch Single door

0 or 0.28a

Double door

0 or 0.57a

Clean Single door

0 or 0.28a

Double door

0 or 0.57a

Single door

0 or 0.28a

Transition al

Double door

0 or 0.57a

Dirty Single door

0

Double door

0

Open single door = 0.80 m x 2.01 m high Open double door = 1.80 m x 2.01 m high

Open single door = 0.80 m x 2.01 m high Open double door = 1.80 m x 2.01 m high

Open single door = 0.80 m x 2.01 m high Open double door = 1.80 m x 2.01 m high

Designers’ notes:

The degree of protection required at an open doorway between rooms is dependent on the degree of difference in cleanliness between them.

Flow-rate required between rooms within the same class tends to zero as class reduces.

If two rooms are of equal cleanliness, no flow is required (in practice there will be an interchange in either direction) and the design of the air movement will assume zero airflow. In certain cases, however, interchange is not permitted, and a protection airflow of 0.28 is assumed in the design – for example, in the case of a preparation room used as a “lay up”.

[SHTM 03-01 Part A – PDF page 174]

Appendix 6: Typical approximate pressures in an operating suite when a given door is open

Typical approximate effect on other rooms

Table A5 Pressure in room with open door

Room Pressure (Pa) pressure

Door open between Typical approximate

in these rooms (Pa)

resultant

0

Operating theatre and corridor

Anaesthetic Preparation – lay-up Utility

12

or

–6

Preparation – sterile pack store

Scrub bay and corridor

0

5

26

Preparation – lay-up Utility

–9

Operating theatre and anaesthetic room (or other series room with double doors)

17

22

Preparation – sterile pack store

No change

Operating theatre and Utility room

or

25

Operating theatre and preparation room

30

Anaesthetic room and corridor

Preparation – lay-up Utility

–6

Operating theatre

20

(or other series room with double doors)

0

25

Preparation – sterile pack store

No change

Preparation room and corridor

or

0

Utility room and corridor

0 No change

Utility room and outer corridor

Notes:

The room differential pressure protects against reverse flows when the door is closed.

The flow of air through a doorway protects against reverse airflow when the door is open.

Pressure stabilisers control flow and ensure a known airflow path between rooms when doors are closed and also reduce backflow between rooms when doors to other rooms are open.