Test and measuring equipment

Any test or measuring equipment used should have a certificate to prove that it has been calibrated within the previous 12 months at a facility using traceable national standards.

In the case of a noise meter, its “matched sound source” should have a certificate to prove that it has been calibrated within the previous 12 months at a facility using traceable national standards. The noise meter should be calibrated to the sound source on each occasion that it is used.

Test grid – vertical flow canopies

A test grid should be constructed on the floor within the UCV canopy footprint as projected by the inside dimensions of the side walls or boundary air curtain. A suitably marked test sheet will provide a consistent standard of test grid.

Note: The entire clean zone footprint of the UCV canopy will be designated by a contrasting coloured inlay in the floor covering. A line marked on or cut into the floor covering is not sufficient and will not be accepted.

The test grid should comprise test squares of 280 mm × 280 mm dimension.

The test grid should be aligned along the centre lines of the canopy footprint with its centre under the centre point of the canopy.

Any test square with 80% of its area within the UCV footprint should be used as a test position.

An inner zone will be designated that is not less than 36% of the total footprint. It will be made up of a number of test squares distributed symmetrically about the canopy footprint centre line. Regardless of the size or shape of the canopy footprint, the inner zone will comprise a minimum grid of 6 × 6 test squares.

Unless specified otherwise, a test position should be in the geometric centre of a test square.

Test position 1 will be the left-most test square in the row nearest to the operating theatre wall that houses the theatre control panel. (For an example of a grid for a 2.8 m × 2.8 m canopy, see Figure 11.)

UCV canopy leakage tests

The diffuser screen fitted below the face of the canopy terminal filters should be lowered or removed while the leakage tests are being carried out.

The installed terminal EPA filters are to be checked to ensure that their grade accords with the design specification and that their performance has been certified by their manufacturer.

Test equipment

An LSAPC connected to an isokinetic fishtail scanning probe will be used to detect the size and number of particles present.

[SHTM 03-01 Part A – PDF page 148]

Spot readings are taken at several filter faces to establish the smallest non- penetrating particle size. If particles at or above this size are detected when subsequent scans are made, there is deemed to be a significant leak at, or near, the test position.

UCV canopy clean zone leak test

The test will confirm that there is no unfiltered air leakage in the canopy.

The construction joints and service penetration points under the UCV canopy within its side walls or boundary air curtain should be scanned to prove that there are no leaks.

Figure 11: Example of a test grid for a 2.8 m × 2.8 m UCV terminal

Note: For larger UCV terminals, add extra (280 mm x 280 mm) test squares symmetrically around the periphery of the grid and increase the inner zone in accordance with the guidance in paragraphs 12.50–12.56 of Scottish Health Technical Memorandum 03-01 Part A.

A leak is defined as a significant and repeatable rise above the background level.

Terminal EPA filter seal leak test

The test will confirm that there is no unfiltered air bypassing the EPA filter seal.

Each EPA filter seal should be scanned to prove that there are no leaks.

A leak is defined as a significant and repeatable rise above the background level.

EPA filter media leak test

The test will confirm that the EPA filters have not sustained damage while being installed.

The face of each EPA filter should be scanned to prove that there are no leaks.

A leak is defined as a significant and repeatable rise above the background level.