SHTM 03-01 Part A: 9. Equipment Selection Factors – Local exhaust ventilation (LEV)
[SHTM 03-01 Part A – PDF page 121]
Local exhaust ventilation (LEV)
Devices that use an inflow of air to control exposure of staff to hazardous substances are classified as LEV systems under the COSHH Regulations.
An LEV system will typically comprise a unit where the airborne hazard is captured, ductwork to convey the extract air to the fan and a discharge stack. The extract air may be filtered or centrifugally separated to remove any particulate material prior to discharge. HSG 258 produced by the Health & Safety Executive gives detailed guidance.
It is important to recognise at the design stage whether an extract is being provided for comfort, to remove odours or to remove hazards, in which case it will be an LEV system. Chapter 8 lists typical devices used in healthcare applications.
The quantity and location of the terminals supplying the make-up air is an important factor in the design of LEV systems.
LEV systems are statutory items that will be subject to an independent examination and test at least every 14 months by a competent person.
Extract ductwork and fan
Extract ductwork for an LEV system should, where possible, be installed outside of a building. Where it has to be inside, it should take the most direct route through, with as few bends or changes of direction as possible.
All ductwork joints should be sealed and ideally there should be no access hatches. Where access hatches have to be provided, they should be of a type that has a hermetic seal.
Some substances are particularly corrosive, so the choice of material for the ductwork, and type of extract fan fitted, should reflect the nature of the substance being conveyed.
The ductwork should either be fire rated or fitted with intumescent collars where it passes through fire compartments within the building. This will ensure that the extract system is unobstructed and always open to atmosphere up to the discharge point.
Some LEV systems (for example, microbiological safety cabinets) HEPA-filter the extract air within the cabinet unit, but it should not be assumed that the exhaust air will be totally free from microbiological or other hazardous material.
The extract ductwork should as far as practicable be kept under negative pressure while inside the building. The extract fan should be located outside of the building or if this is not practicable, as close as possible to the outside so that any ductwork on the discharge side inside the building is kept to an absolute minimum.
The extract fan drive motor should be out of the airstream and it should be possible to change the motor without disturbing the fan or its casing.
Duplex fans are only required when several LEV systems share a common extract system (for example, multiple fume cupboards in a large pathology department where it can be anticipated that at least one cupboard will always be in use or need to be
[SHTM 03-01 Part A – PDF page 122]
available for use). In such a situation each cupboard should be fitted with a non- return damper at the point that it joins the common system and be capable of being isolated from the common extract system. The common extract duct should be large enough to handle the combined extract volume from all the systems that feed into it.
If extract filters are fitted in the ductwork the system design should allow them to be changed safely.
Current standards permit the installation of microbiological safety cabinets with integral fans, provided that the extract ductwork can be kept short (that is, less than 2 m); such an installation, however, is likely to be noisy and is not recommended for use in new buildings.
LEV discharge stack arrangements
Roof-level discharge, wherever practicable, is preferred since it removes much of the uncertainty over air re- entering the building through ventilation inlets or windows. In such an installation, the extract fan should be situated separate from the LEV captor unit and close to the discharge stack to maintain the duct within the building under negative pressure.
The discharge point on a flat roof should be through a terminal at least 3 m above roof level but as high as necessary to limit re-entry into supply air inlets or other plant openings. This will protect those who may need to access the roof. Terminals at other roof types need to be high enough to prevent the wind blowing across the roof from causing downdrafts.
Where there are adjacent buildings with opening windows, or where downdraughts are likely to occur, it may be necessary to increase the height of the discharge stack in order to achieve adequate dispersal. In complex locations, airflow modelling or wind tunnel tests may be required to determine the optimum height.
The discharge stack should have an open end. It may be fitted with a collar to reduce its area and so increase the air efflux velocity at the point of discharge (known as the venturi effect). To ensure that air leaving the terminal is not deflected down but allowed to disperse freely, the terminal cannot be fitted with any sort of cover or hat. A drain may be required at the base of the discharge stack to remove any rain that enters (see photograph).
Figure 9 Typical LEV discharge stacks
[SHTM 03-01 Part A – PDF page 123]
LEV system information and identification
Once installed, all elements of each LEV system should be uniquely identified with a permanent label as described in Chapter 13. There is a statutory requirement to have information on the design and required operational performance of an LEV system available to those who are responsible for its operation and
maintenance. The designer should ensure that this information is available at handover.