[SHTM 03-01 Part A – PDF page 109]

The thermal insulation of intake and discharge ductwork will be dependent on its location in heated or unheated plant spaces and risk of surface condensation.

In normal circumstances, the insulation thickness for heat resistance is sufficient to prevent surface condensation, but in extreme conditions the insulation thickness for vapour resistance may be greater than that for heat resistance. When cold ducts pass through areas of high dew- point, carefully selected vapour barriers should be applied externally to the insulation.

Noise generation within the ductwork

Noise is generated in ductwork at sharp edges, by tie rods, damper blades, duct obstructions, sharp bends, etc. This airflow-generated noise becomes an important factor if it is about the same or greater level than the upstream noise level. Airflow- generated noise is often referred to as regenerated noise.

The noise level generated by airflow in ductwork is very sensitive to the velocity. The sound power of this noise is approximately proportional to the sixth power of the velocity; that is, a doubling of the duct velocity will increase the sound power by a factor of 64 (or about 18 dB). The duct velocities should therefore be kept as low as possible. In general, duct fittings which have lower pressure loss factors in similar flow conditions will generate less noise.

Ductwork serving quiet areas should not be routed through noisy areas, where noise break-in can occur and increase the noise level in the ductwork.

Grille register and louvre noise should be kept to the minimum by selecting types having low noise-producing characteristics, without high tonal noise; and should be fitted with acoustically treated external inlet and outlet louvres.

Cross-talk attenuators may be necessary where noise intrusion between adjacent spaces can arise and where individual room confidentiality is required. They will normally be of the “through-the- ceiling, up-and-over” type and may include a fire and smoke damper.

Volume control damper locations

In order to be able to carry out a full proportional balance, manually operated dampers are typically needed:

in branches of zone ducts;

in sub-branch ducts serving four or more terminals;

in dedicated sub-branch ducts serving a room;

at terminals not covered by any of the above.

Dampers integral with terminals are to be avoided for final trimming of air volumes, as they often create noise and air distribution problems.

Dampers in rectangular ducts should be opposed-blade multi-leaf type. In circular ducts, iris-type dampers are recommended. Dampers should be accessible, incorporate a position indicator and means of locking in the commissioned position. They should be installed with the adjusting handle or knob at the lower vertical edge

[SHTM 03-01 Part A – PDF page 110]

so that they are accessible for the commissioning team once the ceilings are in place. Dampers should be located as far away as possible from adjacent branches or plant items.

Duct cleaning and access door locations

Cleaning and access doors are required to facilitate access to plant items and ductwork components for inspection, maintenance, cleaning and replacement, and should be of sufficient size to permit safe access for the required functions.

Recommended locations for access doors are given in the current BESA TR/19 specification and are generally provided to give access to:

every regulating damper;

every fire-and-smoke, and motorised damper;

filters (to facilitate filter withdrawal);

both sides of trimmer cooling/heating coils;

zone humidifiers;

auxiliary fans;

ducts, where required for cleaning.

Care should be taken when siting access doors to ensure that no other services to be installed will prevent reasonable access.

Flexible ducting

Flexible ductwork can only be used to make the final connection between rigid ductwork and a terminal in exceptional circumstances where a solid connection is not possible. Where used it will cause a significant frictional loss and may be difficult to clean, so it should take the most direct route and be as short as possible, never exceeding 0.5 m in length. It can never be used in lieu of a bend and will possess the same fire rating as the ductwork it is connected to.

Terminal fittings selection and sizing

The effectiveness of all ventilation and air-conditioning systems depends on the methods by which air is introduced to, and vitiated air is removed from, the space. The usual results of poor air-terminal selection and/or positioning are:

draughts;

stagnation;

poor air quality;

large temperature gradients;

excessive noise.

Air can be supplied to a space in a number of ways, although any device can be broadly placed into one of two categories:

that producing a diffused supply;

[SHTM 03-01 Part A – PDF page 111]

that producing a perpendicular jet.

Diffusers may be radial or linear, and normally utilise the coanda effect (that is, adhesion of the air stream to an adjacent surface) to reduce the risk of excessive room air movement. A perpendicular jet is formed by discharging air through grilles, louvres or nozzles, which are generally adjustable.

Supply air terminals can be incorporated into any room surface, for example, floors, walls (high or low level), desktop.

As they operate on the jet principle, the use of sidewall and linear grilles is restricted to areas where air-change rates are low, that is, less than 10 per hour.

Perforated rectangular diffusers can provide acceptable conditions within the occupied zone at up to 15 ac/h. In areas where a higher air-change rate is required, square or circular ceiling-mounted diffusers should be used.

The performance of supply air terminal devices is based on three criteria – throw, spread and drop:

throw is defined as perpendicular or parallel distance from the terminal to the point at which the air velocity is;

0.5 m/s isovel;

Spread is defined as the width of the;

0.5 m/s isovel;

Drop is defined as the vertical distance from the centre line of the terminal to the bottom edge of the 0.25 m/s isovel.

It is necessary to consider each of these parameters in both summer and winter conditions to ensure satisfactory operation of the air terminal device, as warm jets behave very differently from cold jets.

A warm jet tends to rise until it attaches itself to a horizontal surface, while a cold jet falls. Care should be taken to ensure that this does not lead to unacceptable temperature gradients in winter, or excessive air velocities in the occupied zone in summer.

In order to ensure satisfactory air movement within a space, it is necessary to consider interaction between air movement from adjacent terminals, and ceiling- mounted fixtures (light fittings, etc), as well as interaction between air movement and room surfaces.

If the supply and extract terminals are too close, short-circuiting may occur, while if they are too far apart, stagnant zones may be formed. Where two opposing air streams meet, the individual velocities should not be greater than 0.25 m/s. Further guidance on the selection of grilles and diffusers is given in the CIBSE Guide B

In operating theatres, the supply terminals should be able to produce a movement of air in the operating zone 1 m above floor level of between 0.2 and 0.3m/s:

[SHTM 03-01 Part A – PDF page 112]

ceiling-mounted diffusers with fixed directional vanes that provide a downward turbulent airflow are the preferred option: 600 × 600 four-way blow or circular “air- master” style;

plenum boxes fitted with perforated screens to produce a laminar downflow are also acceptable;

linear ceiling-mounted diffusers that provide a downward-flowing air curtain around the operating theatre may also be used (additional supply terminals may be located within the area bounded by the linear diffusers to provide ventilation within the;

air-curtained zone).

The following terminal types are not suitable for use in operating theatres because they do not produce an appropriate pattern of air distribution:

swirl diffusers;

single- or multi-outlet adjustable directional nozzles or jets of any type;

sidewall-mounted linear diffusers that utilise the coanda effect to send air across the ceiling and “droop” it into the operating zone.

Extract terminals should be of an easy-to-clean design and, in order to assist identification when commissioning and subsequently measuring, be of a different design style to the supply terminals. Extract terminals mounted at low level should be of the spring clip retained, pull off face type to enable ease of cleaning. The terminal should be mounted on an angled face to prevent it becoming occluded by movable equipment or stores (see Appendix 9 for examples). Perforated plates are not to be fitted in extract terminals or extract plenums as they quickly become blocked with lint. Extract terminals do not need any directional adjustment so fixed-vane or “egg-crate” styles are preferred.

UCV terminal canopy

UCV canopies should be fitted with one or more non-electronic, mechanical, direct reading pressure gauge(s) to indicate the pressure drop across either a representative terminal EPA filter or the pressure in each zone of the canopy.

If a UCV canopy incorporates a method of adjusting the air discharge direction so that the canopy can be “tuned” to the room in which it is installed, the directional adjustment device(s) are to be capable of being locked in position once commissioning is complete to prevent future casual alteration.

Ceiling-mounted canopy diffusion screen(s) can become contaminated with blood spatter when in use. If the UCV canopy is fitted with perforated diffusion screens the blood spatter can penetrate, so the screens should be capable of being hinged down for cleaning between theatre cases. The screen retaining mechanism will have a double action to release the screen. Mono-filament diffusion screens should be retained by clip-in profiles or an alternative system that allows them to be easily removed when necessary.

For the validation of UCV terminal canopies, see Chapter 12.

[SHTM 03-01 Part A – PDF page 113]

Transfer grille: size and location

Air transfer grilles in walls, partitions or doors form an integral part of the building’s air distribution system. Modern door sets have very low leakage rates so cannot be relied upon to permit even quite small airflows. Failure to make adequate provision for air to move from room to room will result in excessive pressure differentials and “door whistle”.

Transfer grilles are required in locations where there is a significant imbalance between the supply and extract rates in a room. They will relieve any pressure differentials which may affect the operation of the spaces and/or the ventilation system and permit airflow in a known direction.

Care needs to be taken to ensure that the positioning of transfer grilles does not interfere with the fire or smoke integrity of the building. In general, the air transfer grilles should not be installed within fire- resisting boundaries, although if this is unavoidable, they should be fitted with fire or smoke dampers.

Where installed, transfer grilles should be of the non-vision type, sized for a maximum face velocity of 1.5 m/s.

Note: Cross-talk attenuators may be necessary where noise intrusion between adjacent spaces can arise and where individual room confidentiality is required.

Pressure stabilisers: size and location

Pressure stabilisers are required in areas where it is necessary to maintain a pressure differential between adjacent rooms and to prevent reversal of airflows for example, in operating suites, isolation facilities and cleanrooms (see paragraph 8.24).

Fire precautions for pressure stabilisers are the same as for transfer grilles. If the pressure stabiliser is fitted with a fire and smoke damper, the damper test switch should be easily accessible from, in airflow terms, the least clean side of the damper.

Pressure stabilisers should be of the balanced blade type, with the facility to make fine adjustment of the pressure setting. They should be silent in operation and give a seal as tight as practicable when closed. The materials of construction and method of assembly should allow for cleaning and disinfection.

Pressure stabilisers should be wall- mounted in a visible location so that their operation can be readily observed. For sizing criteria, refer to the manufacturer’s information. When fitted at low level, they may require a stand-off cage to prevent occlusion (see photograph).