8. Specific Healthcare Department Requirements

General considerations

The foregoing chapters of this document contain general information on healthcare aspects of ventilation system design and specification. This chapter gives information relating to the specific design requirements for a range of healthcare applications.

The following departments will require a degree of ventilation appropriate to their function.

the operating department;

treatment rooms, endoscopy and minimally invasive suites;

critical care area – levels 2 and 3;

diagnostic and interventional imaging and cardiology suites;

obstetrics/maternity;

infectious diseases unit and isolation facilities;

bone marrow and other transplant units;

chemotherapy and oncology units;

the pharmacy department;

the pathology department, mortuary and post-mortem suite;

central decontamination units;

burns unit;

cystic fibrosis unit;

tissue bank, gene therapy and emerging treatment specialties;

physiotherapy and hydrotherapy;

estates infrastructure.

Design information for many of these applications is given below, in Appendix 2 or the relevant SHPN/HBN.

It is not possible to give definitive guidance for every healthcare ventilation application; however, the section on operating theatres contains much information that is common to other applications. Where no specific guidance is given, the principles set out below should be followed:

the CIBSE guides and technical manuals contain basic information on ventilation design that can be applied to most applications;

where a British or European standard exists that is specific to the application (for example, a cleanroom), it should be used as the basis of the design requirement;

[SHTM 03-01 Part A – PDF page 53]

air should always move from clean to less clean areas. A hierarchy of room cleanliness is given in Appendix 3;

differential pressure will prevent contamination between areas when doors are closed. Information on air leakage through gaps around closed doors and hatches for a range of differential pressures is given in Appendix 4;

the flow of air will prevent contamination between areas of different cleanliness when doors are open. Information on airflow through open doors and hatches is given in Appendix 5;

a methodology for calculating a design solution for a non-standard operating suite in terms of its room sizes, layout or number of people present is given in Appendix 8. This may be adapted as necessary to suit other less complex applications where air is required to cascade through rooms from clean to less clean areas.

Note: In all cases it is essential that the design solution adopted will ensure adequate scouring of the space being ventilated. The selected airflow rates, relative position of supply terminals, extract terminals, air transfer devices and pressure stabilisers will all have a bearing on the effectiveness of the room ventilation.

There are four routes by which airborne contaminants may appear in a room:

shed directly by the room occupants;

arising as a result of the work activities;

transferred from adjacent spaces;

through the supply air.

Particles shed directly by the room occupants can be controlled by:

restricting access to essential persons only;

the choice of the occupants’ clothing;

the room air-change rate.

Particles arising as a result of the work activity can be controlled by:

enclosing, semi-enclosing or otherwise controlling the work-based source;

the room air-change rate.

The transfer of particles from adjacent spaces can be controlled by:

a differential pressure between spaces when doors are shut;

airflow paths flowing from clean to less clean spaces when doors are open.

Particles entering with the supply air can be controlled by the selection of a suitable filter.

When designing ventilation for a healthcare application, the sources of airborne contamination, their degree of hazard to patients and/or staff and the ability of ventilation to control them should be taken into account. For any particular healthcare

[SHTM 03-01 Part A – PDF page 54]

application, the ventilation safety group (VSG) should be able to give advice on any specific risks to patients and staff.

The supply of air to a room has the following main functions:

to dilute airborne contamination;

to control air movement within such that the ingress or discharge of airborne contaminants from or to adjacent areas is minimised;

to control the temperature and, if necessary, the humidity of the space;

to aid the removal of and dilute fumes, odours and waste gases.

The supply air volume flow rate for any particular application will be that required to:

achieve the application’s recommended air-change rate;

provide closed and/or open-door protection;

achieve comfort or application-specific room conditions;

replace (make up) that removed by an installed extract system;

meet the fresh air requirement relating to the number of people anticipated to be present;

achieve the minimum fresh air requirement if air is recirculated.

Whichever is the greatest amount.

Note: Air-change rates are given in Appendix 2. These figures have been found to give enough dilution of airborne contaminants, provided the mixing of room air is reasonably uniform. Closed and open door protection volumes are given in Appendices 4 and 5. Fresh air requirement is at least 10 L/s/person. Minimum fresh air volume if recirculated is 20%, whichever is the greater.

Natural and/or mixed mode ventilation should be used wherever possible. Where mechanical ventilation is chosen, a downward displacement turbulent air distribution is generally preferred, though displacement ventilation may be used if appropriate.

The supply and extract terminals should be positioned to ensure that all parts of the room are actively ventilated and that where necessary the staff will be in a clean airflow path. Extract and air-out paths via door gaps, transfer grilles, pressure stabilisers and low-level active extract should be evenly distributed to encourage efficient scouring of the room. (See paragraphs 8.37–8.40 and 9.161–9.172 for additional guidance on location and types of terminal.)

Horizontal flow room air distribution with or without a coanda effect (see paragraph 9.162) can be a source of draughts and difficult to set up correctly. Its use should be confined to non-critical areas or situations where ceiling-mounted diffusers could be obstructed by movable equipment support tracks (for example, in imaging rooms). Alternatively, a displacement ventilation scheme may be considered.

[SHTM 03-01 Part A – PDF page 55]

Temperature and humidity control

Supply flow rates to achieve the required room conditions are calculated conventionally, taking account of all heat and moisture gains and losses, and of maximum permissible temperature differences between the room and supply air. In most applications the base heating load will be provided by a heating system. In critical systems the room or suite being considered will be within the heated building envelope so the ventilation will be sized to suit the casual gains or losses.

Temperature differences between supply and room air of up to 10 K for winter heating and 7 K for summer cooling should not be exceeded.

Room air humidity should be kept below 70% in order to minimise risks associated with condensation and mould growth. There is generally no lower limit in unoccupied spaces; however, see application-specific guidance.

Ventilation where anaesthetic agents are present

During treatment, anaesthetic gas or anaesthetic agents may be delivered to the respiratory tract of a patient either directly or using a carrier gas. Anaesthetic gases and agents are subject to workplace exposure limits and while beneficial to the patient are harmful to staff. Waste anaesthetic gas should be contained and removed by a suitable anaesthetic gas scavenging system (AGSS). Some leakage from the anaesthetic equipment and the patient’s breathing circuit will occur with all systems, particularly during connection and disconnection and from the interface with the patient. In recovery areas the patient will exhale the anaesthetic agent directly into the room air. The room ventilation scheme should ensure that any leakage or exhaled anaesthetic agents are diluted and removed.

Note: Staff tend to be standing and patients lying down when anaesthetic agents are delivered; also anaesthetic agents are slightly heavier than air, so locating the supply terminal at high level behind where staff normally stand, with an extract at low level adjacent to the source (for example, the anaesthetic gas terminal units), will ensure that staff are in a clean airflow path.

The design primary air supply to an operating suite anaesthetic room that is equipped with a N2O terminal or in which an anaesthetic agent is delivered to the respiratory tract of a patient using a carrier gas, or an operating department recovery room, should be 15 ac/h.

In delivery rooms the intake of anaesthetic gas is controlled on demand by the patient, who will then exhale directly into the room air. Locating the supply air at high level at the foot end of the bed with extract at low level at the head end will establish a clean airflow path and reduce the casual exposure of staff to the waste gas.

The primary air supply to any other room that is equipped with a N2O or N2O/O2 (Entonox) terminal or in which an anaesthetic agent is delivered to the respiratory tract of a patient using a carrier gas or in which the patient is subsequently recovered, where the anaesthetic is employed for the purpose of pain relief or sedation but not full anaesthesia, should be 15 ac/h. However, subject to risk assessment, consideration may be given to reducing this to no less than 10 ac/h, only where use of the anaesthetic gas release into the space will be both very infrequent and in very small quantities.

[SHTM 03-01 Part A – PDF page 56]

Note: Staff employed in operating suite anaesthetic rooms and an operating department recovery room will potentially be exposed to anaesthetic agents for the duration of their working day. In other areas (for example, maternity, imaging, treatment rooms), anaesthetic agents are only used for pain control and/or sedation. The strength, quantity and frequency of use may be significantly less, hence the the option to carry out a risk assessment.

Door protection

Air should flow from the cleaner to the less clean areas as shown in Appendix 3 and Figure A23 in Appendix 8. There are several factors that affect the likelihood of a reverse airflow through doorways:

when a person passes through a doorway, both the passage of the person and the movement of the door flap cause a transfer of air between the areas separated by the door;

when a door is left open, there is a transfer of air between the two areas separated by the doorway. This is caused by air turbulence, but is greatly increased by any temperature differential between the areas (a 1.4 m wide doorway may allow the transfer of 0.19 m3/s of air in each direction when there is no temperature difference, but when the temperature differential increases to say 2 K, the volume transferred may increase to 0.24 m3/s). This may be a problem if for example the heat gain from a fluid warming cabinet is not allowed for.

In order to reduce the likelihood of contamination of a clean area by a reverse airflow from a less clean area two methods of door protection are used:

closed door protection – a pressure differential is created across a closed door so that any air leakage is from the clean to the less clean area. Appendix 4 gives details of closed door leakage rates for a range of differential pressures;

open door protection – the pressure differential drops when a door is opened (see Appendix 6) and is effectively replaced by a flow of air through the doorway from the clean to the less clean area. The flow of air needs to be sufficiently large to ensure that significant reverse airflow cannot occur and will be related to the relative cleanliness of the areas being considered. Appendix 5 gives airflow rates for open-door protection related to door/opening size and the classification of the adjoining area.

Pressure stabilisers enable the room differential pressure to be set when the doors are shut, thus providing closed-door protection. When a door is opened, the stabilisers will close, forcing air to be directed through the doorway, thus providing open-door protection. Provided that the dilution criteria in Appendix 3 are met, the occasional small back-flows created (when two doors are opened simultaneously; or when there is a high temperature difference across an open door) will have little effect on the overall air cleanliness of the affected room.

In applications where it is critical to maintain a specific airflow and/or pressure regime, for example isolation rooms, all windows in the zone should be locked shut or sealed. Trickle vents, if fitted, should also be sealed.

The design of the ventilation system for an area depends on the overall configuration of the department. Where the department is served by more than one AHU the