7. Environmental Control
The primary objective of a ventilation control system is to keep the space served within the required environmental control limits, at the appropriate times – regardless of external conditions or internal loads – and with the minimum energy consumption.
The building heating load will normally be met by a wet heating system with ventilation provided to suit the activities within it. The control of the heating system will normally be compensated to the outside air temperature. Control of the ventilation will usually be via a building management system (BMS) with “outstations” in individual plantrooms and/ or for individual AHUs.
A BMS incorporating self-adaptive control algorithms that automatically adjust the set-point to suit the usage and load is preferred. This will enable the operating conditions and control tolerances to be set and monitored. It is often not possible to accurately predict building load variation at the design stage. Information provided by monitoring the operation of the plant via a BMS will enable optimum set-points to be established and energy consumption reduced.
The BMS may also be set to log the actual energy consumed by the system together with that recovered by the energy- recovery device. This will provide a useful check on overall operating efficiency and provide evidence that energy targets are being achieved. The provision of movement sensors within the controlled space in order to determine the actual occupancy will facilitate this process.
The failure of ventilation systems serving critical areas can have grave consequences for the delivery of healthcare. Control systems should therefore be simple, robust and reliable.
Computer-software-driven control systems are now the norm in building services. However, healthcare ventilation systems need to be available for operation outside of normal working periods when software support is not available. Should the software fail, it will be left to site staff, who may have little knowledge of the control algorithms, to restart the ventilation system. It is therefore essential to ensure that a simple means of restarting critical systems in the event of a software failure is provided (see also Chapter 9).
Where BMS use “outstations” to control plant, the “outstation” should be independently able to control the plant if the BMS link is lost.
Location of controls
Whether within the plant, duct or room, sensors should be located to provide accurate measurement of the condition of the air being monitored.
Sensors and control items such as control valves should be located close to the element being sensed or plant item being controlled in order to minimise time lags within the system. These may create over- shoot of conditions beyond the design envelope and result in additional energy consumption.
Where there is a requirement for close control of air-conditioning parameters in a number of zones (for example, an operating department), separate plant should be
[SHTM 03-01 Part A – PDF page 49]
provided for each zone in order to avoid the need for expensive over-cooling and reheating of individual zones. The control of most multi-zone systems within healthcare premises is based on off-coil control within the central plant, with trimmer heater-batteries on individual zones.
Note: In modern buildings the cooling load is often significantly greater than the heating load and may exist all year round. Whenever possible, the design should take advantage of free cooling when available.
Facilities to start, set back and stop the plant should be provided in the plantroom. Remote start and set-back control and indication, if required, should be provided at a manned staff location (for example at the reception or staff base).
Many ventilation systems may be completely shut down when the area served is not in active use (for example, operating suites). Alternatively, where there is a need to maintain a background condition, the ventilation output may be reduced by “setting back” the system (see paragraph 6.2 and associated Note). This will significantly reduce energy consumption and extend the life of filters and other system components
Multi-zone control methods and application
Close control of all air-conditioning parameters may be difficult to achieve with multi- zone systems, since each zone will in theory require a reheater and humidifier to give total control of humidity, if that is what is required. In reality, such close control is rarely required. It is therefore usual with multi-zone systems to provide control of zonal temperature only, with humidity control, where fitted, being based on average conditions within all zones, or a minimum condition within one zone.
Designers should consider whether it is necessary for the supply and extract fans to be interlocked – either so that the supply fan will not operate unless airflow is established within the extract system, or vice-versa depending on the required pressures within the rooms being served (see also Chapter 8).
The sequence switching of units in order to prevent transient reverse airflows will be particularly important in laboratories and pharmacies that contain fume cupboards, safety cabinets and other LEV systems.
Fire aspects
The control strategy for ventilation systems in the event of a fire should be set out in an agreed fire and smoke control strategy for the site (see Chapter 1).
All supply AHUs should have a smoke sensor linked to the fire control panel and mounted in the main supply duct immediately downstream of the AHU. In the event of a fire in the AHU or smoke being drawn into the system from an outside source, it should cause the AHU to shut down and the main supply-air damper and system fire damper(s) to close.
In critical areas a ventilation control panel should be mounted at the main entrance of the area that the ventilation serves (see Health Technical Memorandum 05-02 for more detailed guidance). Access to the panel should be restricted to the fire officer and appointed site AP(V). It should include independent on/off controls and an
[SHTM 03-01 Part A – PDF page 50]
indication of the status of the supply and extract systems. A notice should be affixed to the control panel stressing the need to liaise with departmental staff before switching off fan units
Note: In certain critical care areas, it is preferable to maintain the supply ventilation in case of a fire within the area. For example, in an operating department, while undergoing surgery, the patient cannot always be easily moved without significant risk. In the event of a fire in a staff or support area of the department, or adjoining zone, the continued supply of air to a theatre will maintain it at a positive pressure and protect the patient and staff from the effects of smoke. This will allow time for the patient to be stabilised so that they can be safely evacuated if necessary.
User requirements
Room temperature control
The limits for room temperature set- point are generally between 18ºC and 22ºC depending on the particular application. In some specialised applications (for example, operating departments), the user may require a wider range of adjustment (see Chapter 8).
The selection of temperature set-point for each room or zone may be by a control facility in the room/zone or be carried out remotely at the control panel or BMS. Where the control device is mounted within the room/zone and is adjustable by the user, it should be marked either “raise” and “lower” or “+” and “–”. It should control within a specified temperature range to suit the user requirement with a control tolerance of ±1 K. All other control set- points should be selectable either on the control panel or at the BMS interface.
Where local control is provided, an indication of temperature will be required locally or at a staff base (if appropriate) using an analogue or digital indicator. The indicator should be large enough to be read from the normal working position (for example at the operating table in a theatre). This may be mounted in a supervisory control panel, with the signal repeated on the main system control panel or BMS. It is important that this indicator displays the actual measured temperature and not the selected temperature.
Alarms and indication
Supply and extract systems should include indicator lamps on the control panels to confirm the operational status of each system. Where the usage is on a regular daily pattern, time control with a user-operated, timed manual override should be provided.
Where a system is provided for a particular space, the indicator should be in, or immediately adjacent to, that space, and local controls should be provided with permanent labels clearly defining their function (for example isolation suites).
If room differential pressure gauges are required, they should be mounted directly adjacent to the entry door of the room to which they apply at a height of 1.5 m above floor level so that they are in the eye line of staff entering the room. If a mechanical gauge is fitted, it should have a green sector to indicate the acceptable normal
[SHTM 03-01 Part A – PDF page 51]
pressure range. If electronic, it should have a permanent label affixed underneath it giving the normal acceptable pressure range.
Note: For specific departmental control parameters, see Chapter 8. For plant controls see Chapter 9.
Maintaining balanced air flow rates
Consideration must be given to the method of maintaining the correct proportional balance throughout a system when in use. This becomes particularly important where duct or terminal mounted filters are to be used. As the filters soil, the pressure and flow balance of the system would change unless control measures are included to enable automatic compensation/adjustment (e.g. constant volume boxes, variable speed drives).