Home › Scotland (NHS Scotland Assure / HFS) › SHFN 30 Part A › Pages (pages 41–48)

SHFN 30 Part A: Pages (pages 41–48)

HAI-SCRIBE Manual information for project teams (SHFN 30 Part A) · PDF pages 41–48 of 69 · Source file: shfn-30-part-a-v40-oct-2014.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHFN 30 Part A – PDF page 41]

A clinical wash-hand basin should be provided (see Health Building Note 00- 03).

Carpets should not be used in a treatment room.

Space should be available to allow for the storage of equipment and sterile supplies.

Disposal room

(SHPN 04-01)

This area should be secure and not be accessible to patients/public.

The disposal room is for temporary storage of supplies and equipment that have to be removed for cleaning, reprocessing or disposal, for example, items to be returned to the sterile services department (SSD).

The sizing and location of disposal rooms should be considered at the design stage, taking into account the predicted levels and types of waste to be generated and the planned operational policies relating to frequency and work flow of waste and linen collection.

D.S.R. (Domestic service room)

(HBN 00-03)

This room is used to deliver day-to-day cleaning services for a defined area. Cleaning materials and equipment in daily use should be stored in cupboards within this room.

Note: It should be noted that the requirements for DSRs have recently been under review by the domestic services review group.

The room should be provided with a sink with draining board and slop-hopper as well as a wash-hand basin situated well away from the equipment washing sink and slop hopper. There should be unrestricted access to the sink and slop- hopper.

Space should be provided for segregation and storage of mops, buckets and other cleaning equipment vacuum cleaner and scrubbing/polishing machine (for hard floors) and for lockable COSHH cupboard for cleaning supplies.

Day room/patient waiting areas

(HBN 00-03)

There is often conflict between the aesthetics of these areas and the prevention of contamination of the environment or furnishings and ease of cleaning/disinfection. This is especially the case in waiting areas such as in accident and emergency departments, primary care and minor injury units.

[SHFN 30 Part A – PDF page 42]

It is important that where blood and body-fluid spillages may occur, the environment should be able to be decontaminated effectively. Use of carpets should be the exception and then only after much consideration and risk assessment.

Note: There are special requirements for Mental Health Units which are categorised as low risk.

Play area

(HBN 00-03)

All equipment, finishes and furnishing will be wipable, impermeable and be able to withstand cleaning and disinfection. This is particularly important for play mats and soft floor coverings.

Nappy-changing area

(HBN 00-03)

Facilities for disposal of soiled nappies and for hand washing in the immediate environment are required along with a regular cleaning programme of equipment used.

The area for nappy-changing will have a surface that can be easily cleaned and disinfected.

Staff/Visitors’ toilets

(SHPN 04-01 and HBN 00-02)

These are heavily used and will provide enough space with wipable, impermeable, durable finishes to maintain a high standard of cleanliness.

There will be provision of disposal facilities for sanitary waste in both women’s, assisted, disabled and unisex toilets.

The number of toilets, wash-hand basins and hand drying facilities provided will be sufficient for the size of the facility (see Health Building Note 00-02). Minimum numbers for staff and patient toilets and visitor toilets in non-public areas are determined by NHS guidance documents. Provision for visitors in public areas will be determined by the Scottish Building Control technical standards.

Hand drying should be by single-use paper hand towels or hot air hand driers. If a facility is, in or closely adjacent to, areas where patients may be sleeping, hot air hand driers will be avoided due to noise.

[SHFN 30 Part A – PDF page 43]

Equipment storage

(SHPN 04-01, SHPN 36, and SHTM 63)

Storage areas need to be appropriate for the operational requirements of each clinical area.

The need for sufficient secure storage should not be underestimated. Many briefs start with sufficient storage, but this space is often lost to other areas during the design process. This can have implications for both clinical practice and infection prevention and control.

Storage away from areas of clinical activity is required for both small and bulky items of equipment to minimise clutter, enabling efficient environmental cleaning.

All healthcare premises need a storage area for large pieces of equipment such as beds, mattresses, hoists, wheelchairs and trolleys that are not currently in use. The use of equipment libraries can be an effective way of storing, maintaining and decontaminating large or electrical equipment.

Cleaning equipment, laundry and healthcare (including clinical) waste need to be stored in separate purpose-built areas to prevent cross-contamination.

Sufficient and appropriate storage will protect equipment from damage, contamination and dust, which may potentially carry microorganisms, but should also allow free access to floors and shelves for cleaning.

Storage for patients’ possessions

(HBN 00-03)

Adequate space should be allocated for the storage of patients’ possessions. Wardrobes and lockers used for storage of patients’ possessions should be selected to be easily and efficiently cleaned. Louvre doors should not be fitted, as they are difficult to keep clean.

Consideration and risk assessment should inform choice of furniture, vandalism and ligature issues affecting all types of accommodation.

Out-patient and day surgery changing facilities

(HBN 00-03)

In areas such as out-patients, imaging and minor injuries units, it will be necessary to provide sufficient changing/storage facilities for patients if clothing has to be removed and kept safe. These should be included at the planning stage and should be able to be cleaned easily.

[SHFN 30 Part A – PDF page 44]

Clinical staff changing

(HBN 04-01 and HBN 00-02)

By providing staff changing facilities, sanitary facilities, showers and sufficient locker space for outdoor clothing staff will be able to change out of their uniform on-site. Wash-hand basins and shower facilities for staff should be made available and easily accessible in case of substantial blood or body fluid contamination. There needs to be sufficient storage for clean scrub suits and footwear. Facilities for disposal should also be available. Specialist departments will require local specialist staff changing (eg theatres and aseptic suites). Where these are not available, staff should change and contaminated uniforms bagged.

Maintenance staff changing

(HBN 04-01 and HBN 00-02)

Changing facilities should be provided for maintenance staff who undertake activities that could expose them to contamination. There should also be access to showers in case of significant contamination.

 appropriately sized changing facilities should be provided for staff, to

encourage them to change out of their uniform on-site;

 wash-hand basins and sanitary facilities should be included in showers in

the event of contamination by blood or body fluid.

Linen cupboard

Each ward should have an area for the storage of clean linen which, in new build accommodation, should be purpose-designed. The area used for the storage of clean linen should ensure that linen is not exposed to contaminants. The areas are required to have:

 good ventilation;

 adequate lighting;

 impermeable flooring that is easy to clean and fitted with coving between the

floor and the wall to avoid accumulation of dust and dirt in corners and crevices;

 smooth, impermeable and easy to clean slatted shelving to ensure free flow

of air.

If linen trolleys are used to store linen within the ward area, they should be managed so that:

 they are kept clean and tidy and enclosed with an impervious covering to

ensure that linen is not exposed to dust;

 linen bags are not left open or lying on the floor with the potential for

exposure to dust which may potentially carry micro-organisms;

[SHFN 30 Part A – PDF page 45]

 appropriate procedures are in place to allow cleaning of linen trolleys.

Used linen storage

The following types of linen should be segregated at source before sending to the laundry;

 used linen;

 infectious linen;

 heat labile linen.

Central or local NHS Laundry facilities

Note: Prior to installation, it is important to ensure that validation, testing and recording of the laundry process (including thermal disinfection) can be undertaken, as this is vital for the effective decontamination of laundry in NHS settings. This is the responsibility of the maintenance manager or engineer.

The layout of laundry areas must be designed to ensure that effective cleaning can be undertaken. Finishes to walls, floors, work surfaces and equipment must be capable of withstanding regular cleaning and the impact of mechanical cleaning equipment. The area should be large enough to allow access for decontamination trolleys.

Laundry facilities should provide:

 suitable space for laundry machinery;

 suitable storage for used linen and for separation of used and laundered

linen;

 storage space which is designed to prevent odours from migrating from

storage areas to adjacent areas;

 storage space designed to accommodate trolleys, etc., used in the

transportation of linen;

 appropriate facilities to allow the segregation of used linen, heat labile linen

and infectious linen, in appropriate containers which are clearly identifiable;

 suitable facilities to allow compliance with hand hygiene practices;

 a laundry policy to ensure infection risks are minimised;

 a ventilation system that will minimise the level of airborne contamination

and dust to minimise the risk of cross infection.

If processing infectious linen suitable vent pipes should be routed to a safe area outwith the laundry and effluent from the drains must be sealed from the machine to the drainage area outwith the laundry.

Ward based machines (industrial or domestic):

[SHFN 30 Part A – PDF page 46]

 ward based machines must not be used within the NHS for processing

‘infectious linen’ or ‘contaminated uniforms’;

 as it is costly and difficult to validate domestic washing machines, these

should only be used in areas agreed by the IP&CT such as rehabilitation units for patients’ own laundering or laundering of heat labile baby clothes. Validation and thermal disinfection processes is not required or suitable for domestic machines;

 it is preferable to install industrial type machines in ward areas as in the long

term these are more cost effective due to durability, in addition some models have temperature recording facilities that can be used to ensure thermal disinfection is reached but this is not a requirement in this setting.

Tumble driers should be used to further support thermal disinfection where domestic washing machines are used.

Catering/food hygiene

(HBN 04-01)

There should be facilities for staff who prepare and serve food to wash their hands. Additionally;

 in centralised kitchens, physical separation must be provided for storage,

preparation and cooking areas including any equipment that is used which is effectively done by use of colour coding;

 cooked and raw products must be physically separated at all times;

 ward kitchens should have a separate staff wash-hand basin with non-touch

taps, liquid soap and paper towels;

 storage areas such as cupboards must be clean and intact;

 the refrigerator should have a thermometer either built in or separate and

this should record daily temperatures to ensure the fridge is 5°C or below.

Waste management

Guidance on the management of all wastes arising within healthcare facilities or wherever NHSScotland services are delivered is provided in Scottish Health Technical Note (SHTN) 3. SHTN 3 is published for use by NHS Boards’ staff and its contractors and comprises the following parts:

 Part A: Summary of requirements – best practice overview;

 Part B: Waste management policy template;

 Part C: Compendium of regulatory requirements;

 Part D: Exemplar waste procedures; and,

 Part E: Waste prevention and re-use guide.

[SHFN 30 Part A – PDF page 47]

Many of the regulatory requirements for NHS Boards’ wastes are captured within ‘Duty of Care’ under the Environmental Protection Act 1990 (as amended).

Responsibilities under ‘duty of care’

The ‘Duty of Care’ is described in Section 34 of the Environmental Protection Act 1990. The Act was recently amended in Scotland by the Waste (Scotland) Regulations 2012. Guidance on its use and interpretation can be found in the ‘Duty of Care – A Code of Practice’ published in October 2012.

The Code of Practice outlines the obligations of those involved in the waste management chain from waste producer to final disposal. It requires producers and others who are involved in the management of waste to prevent its escape and take all reasonable measures to ensure that the waste is dealt with appropriately from the point of production to the point of final disposal. In order to comply with this requirement NHS Boards should:

 ensure that waste is segregated in a manner which allows for the recovery

of materials;

 ensure that a written description accompanies all waste movements,

adequately describing the type and quantity of waste;

 ensure that those who manage the waste and sites receiving the waste are

authorised to do so; and,

 maintain records of all waste movements.

One of the main responsibilities under duty-of-care, which has major implications for IPC and the built environment, is to ensure that waste is stored safely on-site. Essentially:

 storage areas at ward and unit level should be secure and not publicly

accessible;

 storage areas should be sufficient in size to allow packaged waste to be

segregated and to avoid waste of different classifications being stored together in the same area;

 SHTN 3 provides further detail on waste segregation, receptacles and

storage.

Waste segregation and storage

Any new capital developments should have enough space for waste receptacles to be located close to the point of waste production.

Healthcare wastes such as potentially infectious waste and pharmaceutical waste should be segregated into colour-coded receptacles in accordance with SHTN 3. Healthcare waste receptacles should not be accessible to the public.

Receptacles for recyclates should be easily accessible and clearly marked using the best practice colour coding specified in SHTN 3. Receptacles for

[SHFN 30 Part A – PDF page 48]

recyclates should be available in all locations where domestic waste is produced.

Residual waste is the name given to domestic waste once recyclates have been segregated at source. This waste should be placed into clear (preferable) or black bags. Receptacles for this waste stream should be clearly labelled.

Dedicated secure storage areas for waste are best located at entrances to wards or departments, preferably with access from both ward and hospital corridor to facilitate collection by authorised personnel only.

Storage for used linen should be in a clearly designated area separate from waste. This should minimise any risks of used linen being accidentally taken for disposal or waste being taken to the laundry.

Dedicated waste storage areas should be able to be cleaned easily and efficiently. The holding area should be of sufficient size to hold wheeled-bins and waste sacks ensuring that healthcare waste is clearly segregated from other wastes to avoid contamination.

A designated, secure area is also necessary to hold receptacles from the whole site (central waste yard) from which waste can be collected for off-site treatment and recycling. Guidance on the design and facilities required in waste storage areas is available in SHTN 3.

Note: Similar consideration will be required to route, contain and retain waste arising from construction activities in order to prevent debris and dust permeating clinical areas.

Waste receptacles

Comprehensive guidance on the size and colours of waste receptacles is available in SHTN 3. Waste receptacles should be of suitable size to meet waste arisings taking collection arrangements into consideration. Receptacles should be easy to clean, hands-free (i.e. foot operated) and comply with the requirements of SHTM 83: ‘Firecode’.

Lids of waste receptacles that are used for healthcare waste need to be capable of being cleaned and disinfected. Avoid attaching temporary labels that would inhibit effective cleaning.

Healthcare waste (including healthcare waste generated in primary care and community settings)

In healthcare facilities such as care homes and primary care settings, all waste should be contained appropriately and kept secure at all times.

Note: There are special requirements for MHUs and Custodial accommodation.

The system and frequency of collection of waste service needs to be taken into account when planning facilities. Areas for temporary storage e.g. holding bays and/or intermediate rigid receptacles such as wheeled bins may be required.