SHFN 30 Part A: Pages (pages 49–56)
[SHFN 30 Part A – PDF page 49]
Temporary storage facilities should be washable, secure and animal-proof. Only rigid lockable receptacles should be stored in external areas.
There should be a strict routine for removing waste to ensure it does not remain uncollected for extended periods.
Storage capacity
Storage areas need to be fit for purpose and a suitable size to allow different waste types to be stored safely and separately. Collection frequencies including contingency requirements (in the event of a failure in waste collection) should be taken into consideration when specifying the size of storage areas. The design of the facility should also take account of accessibility and space needed for vehicles collecting the waste.
Waste segregation
The storage area should be sufficient for different waste streams to be segregated pending collection in line with local policy. This will normally (at minimum) require that domestic wastes, including source segregated recyclates is to be kept separate from healthcare wastes (such as orange bags) taking into consideration appropriate treatment and disposal routes. See SHTN 3 for further details.
Note: The Waste (Scotland) Regulations 2012 have effectively banned the use of food waste disposal units (macerators) and food waste digesters involving the discharge of ‘treated food’ into the public sewer network.
[SHFN 30 Part A – PDF page 50]
6. Engineering services
Note: This section discusses various aspects of engineering services and the Infection Prevention and Control implications of each.
Heat emitters and temperature control
General
The selection of heat emitters will not only have a spatial impact but also on infection prevention and control.
Wall-mounted radiators
Options to ensure safety are as follows:
low surface temperature heat emitters should be used;
where existing conventional radiators are being retained, guards/covers
should be fitted. Ease of covers removal to facilitate cleaning is essential. (paragraphs 6.3 and 6.4 also refer);
temperature controls should fail to a safe position.
Of these options, covered heat emitters have raised the most prevention and control of infection concern. Heat emitter covers allow dust to build up beneath and inside the heat emitter grille. This dust has been found to contain potentially pathogenic organisms, and when heat emitters are switched on during the winter months, dust and bacteria are dispersed by heat convection to the ward area.
Where heat emitter covers are used, regular planned maintenance and cleaning should be undertaken to prevent the problems described.
When installing wall-mounted heat emitters, it is necessary to provide adequate space underneath the emitter to allow easy access for cleaning machinery to be used. Gaps and dust traps should be minimised.
Note: Ceiling-mounted radiant panels are intrinsically safe as hot surfaces are out of reach while also eliminating dust-traps.
Pipe-work siting and access
Where pipe-work is surface mounted it should be contained in a smooth- surfaced box that is easy to clean.
Penetrations where pipes and cables pass through walls above false ceilings should be sealed.
[SHFN 30 Part A – PDF page 51]
Heating, general ventilation and lighting grilles
Heating, ventilation and lighting grilles need to be accessed easily for inclusion in cleaning programmes by cleaning and estates staff.
Ventilation
Ventilation ductwork
Ventilation ductwork should be installed in such a way that it can be accessed. (This is important for extract ductwork as this has the most significant accumulations of lint and dust requiring removal, particularly if heat reclamation systems are used).
Specialised ventilation
The same basic principle applies for all clinical areas whereby positive pressurisation is maintained by providing supply ventilation in cleanest areas cascading to dirty areas where negative pressure will be achieved. This will inhibit the spread of contamination.
In healthcare premises, certain activities will necessitate the provision of ventilation equipment with additional special features in order to achieve and maintain specific conditions. For infection prevention in specialist areas such as operating theatres, ventilation should ensure contaminated air does not enter designated clean areas by ensuring that air flows from the cleanest to sequentially less clean areas. This direction of air flow prevents contaminated air passing in the opposite direction.
Note: See Scottish Health Technical Memorandum 03-01 Parts A and B for comprehensive guidance on the design, installation and operational management of ventilation systems in healthcare premises.
The following will usually have specialised ventilation requirements for infection prevention in:
operating department;
source isolation;
bronchoscopy and sputum induction rooms, where a risk assessment has
indicated a tuberculosis risk;
protective isolation accommodation for highly immuno-compromised
patients;
cardiac catheter, interventional radiology units;
microbiology containment laboratories;
mortuaries.
Note: For information on ventilation for Isolation Rooms refer to Paragraphs 5.8 - 5.12.
[SHFN 30 Part A – PDF page 52]
Split and cassette air-cooling units
Only units that are readily amenable to regular cleaning in a working hospital unit should be used. If installed they should be cleaned as part of a regular planned maintenance scheme. Particular consideration should be paid to the accessibility of the condensate drip tray for cleaning and to the disruption to normal use of the accommodation while maintenance is being undertaken. A preferred solution would be not to install these units in critical patient areas.
Chilled beam units
These comprise heat-exchange beams in a ceiling through which is passed water to cool or heat air that passes across them. They should be installed so that they can operate without generating condensate. They must be accessible for regular cleaning and maintenance.
Hot and cold water systems
Note: Reference should be made to Scottish Health Technical Memorandum 04-01: Parts A and B for comprehensive guidance on the design, installation and operational management of water systems in healthcare premises.
The Water Quality (Scotland) 2010 Regulations contain provisions to ensure that the drinking water supply within buildings to which the public has access remains wholesome and is not adversely affected by the local distribution system.
Immuno-compromised patients are at particular risk from cryptosporidium. Very low numbers of cryptosporidium cysts can occasionally occur in mains potable water.
Storage and distribution of water
Many organisms capable of causing disease, particularly in highly susceptible hospital patients, such as Pseudomonas and Legionella, have been isolated from hospital water systems. Preventive measures include:
routine inspection of water storage tanks with cleaning as required;
identifying and removing dead-legs and blind ends;
keeping cold water systems cold and hot water systems hot; and
ensuring rapid turnover in water storage.
Temperature control is the preferred strategy for reducing the risk from Legionella spp. in water systems. This will require temperature monitoring on a regular basis. The recommended test frequencies are given in Scottish Health Technical Memorandum 04-01, Part B. It is good practice to ensure that hot and cold water pipe-work is insulated and separated. Cold water pipes should also be segregated from other heat sources and preferably not in the same service- ways to avoid unwanted heat transfer to the cold water supply.
[SHFN 30 Part A – PDF page 53]
Chemical and other water treatments that have been shown to be capable of controlling Legionella spp. to some extent may also be considered. They will only work in systems that are amenable to their use, for example those that do not have dead-legs and blind ends.
Scottish Health Technical Memorandum 04-01, Part B – ‘Operational policy’ provides guidance on the monitoring and maintenance of water systems (including water storage).
Sanitary facilities
WCs, urinals, bathrooms and showers should be designed to be easily cleaned and maintained. Wash-hand basins should be provided adjacent to WCs and urinals.
Showers are generally more practical than baths in the clinical situation and are easier to keep clean. Any fixture within a shower such as a seat should be easily cleanable, without small gaps and dust traps.
To minimise the possibility of bacterial colonisation of shower heads, they should be regularly cleaned and de-scaled.
Bidets may present infection risks, depending on design and patient group. The appliance should be rimless with an over-rim water supply. They are most frequently specified in maternity units. Therefore, if used, they should conform to the specifications given in SHTM 64: ‘Sanitary assemblies’ and HBN 00-02: ‘Sanitary spaces’. Baths and birthing pools in Maternity units should be easy to clean and not of a ™Jacuzzi type.
Note: SHTM 64 ‘Sanitary Assemblies’ and HBN 00-02 ‘Sanitary spaces’ contain guidance to assist the design team in the selection, specification and application of sanitary assemblies in healthcare buildings. They also give guidance on the appropriate cleaning and maintenance regimes.
Wet rooms
These require high quality water-resistant cladding on walls to prevent mould.
Water fittings
Water fittings (washers, etc.) should not support microbiological growth. All fittings should satisfy the requirements of the Water Supply (Water Fittings) Regulations 1999.
Flexible hoses used in water supply systems should be identified and risk- assessed for the possibility of contamination with harmful microorganisms. Where flexible hoses must be used (for example, on essential equipment such as hi-low baths), they must be lined with a suitable alternative to ethylene propylene diene monomer (EPDM), and be Water Regulations Advisory Scheme (WRAS)-approved. Care should be taken to avoid kinking or distorting them during installation (see Health Facilities Scotland Safety Action Notice
[SHFN 30 Part A – PDF page 54]
SAN (SC) 09/03 Flexible water supply hoses risks of harmful micro-organisms and paragraph 11.35 of SHTM 04-01 Part A).
Ice for patient consumption
Where suitable for use, ice machines should be of a type that dispenses ice by a non-touch nozzle.
Ice should be made directly from water that is of drinking quality. Ice for the immuno-compromised should be made by putting sterile water into single-use ice-making bags, then into a conventional freezer.
Further guidance can be found in the Safety Action Notice (SAN) 06/46
Electrical services
Lighting
Note: Efficient lighting in all areas of wards or departments enables cleaning staff to undertake cleaning more effectively. The Chartered Institution of Building Services Engineers’ LG2 – ‘Healthcare and hospital lighting’ gives guidance on lighting levels in healthcare facilities. SHTM 06-01 also refers.
Luminaires
Luminaires should be selected and installed to eliminate or minimise ledges/gaps/dust traps and, as far as is practicable, be accessible and easily cleanable.
Bedhead services
Bedhead services should be smooth, accessible and easy to wipe clean. Ledges, gaps and dust traps should be eliminated or minimised.
Sufficient dedicated 13-amp socket outlets should be provided in corridors and in individual rooms to enable cleaning appliances with 9m long leads to operate over the whole department.
Where possible, socket outlets should be provided flush-mounted or in trunking systems to enable easy cleaning and prevent the build up of dust.
Patient entertainment systems
Radio and TV headsets should be capable of being cleaned or disinfected between patient uses or be single use, whichever is the most economical method to adopt.
Risk mitigation measures should be considered, including the implications of power interruption when all electrical fittings are either non-touch of sensor operated.
[SHFN 30 Part A – PDF page 55]
Wastewater and sanitation
Wastewater is generated from a huge number of tasks carried out in healthcare buildings, which range from domestic cleaning, hand-washing, specialist laundries, surgical operations and areas such as renal dialysis units. Most of this wastewater contains pathogenic microorganisms and must be disposed of via a safely contained internal drainage system into the external waste water sewerage system.
Internal drainage system
An internal drainage system should use the minimum amount of pipe work, retain water and be airtight at joints and connectors. It should be sufficiently ventilated to retain the integrity of water seals.
The design should comply with the relevant British Standards and Codes of Practice, including BS EN 12056, Scottish Building Standards Technical Handbook and recommendations for spatial and access requirements for public health engineering services are contained in The Chartered Institution of Building Services Engineers’ Guide G, 2014.
Provision for inspection, rodding and maintenance should be located to minimise disruption or possible contamination, eg access points should not be sited in clean clinical areas.
Bedpan washer-disinfectors/macerators
Where reusable bedpans are used, ward areas require adequate and suitable bedpan washer-disinfectors that comply with BS EN ISO standards 15883-Parts 1-3: 2009, IEC 610010-2-040: 2005 and SHTM 2030 Part 1, 2 and 3.
Where fitted, bedpan washer-disinfectors should be installed according to the Scottish Water Bylaws 2004 Part 2 (4) and using fittings listed on the Water Supply Regulations Advisory Scheme (WRAS) directory.
When considering installation of bedpan macerators, it should be established that both internal drains and the external sewerage system can cope with the model proposed.
Where recommended by the manufacturer reusable supports should be decontaminated in the washer disinfector. Further advice should also be obtained from the Infection Prevention and Control team.
Medical gases and vacuum systems
Scottish Health Technical Memorandum 02-01 gives guidance regarding piped medical gases and vacuum systems and includes recommendations on: emergency procedures; power failure; access for cleaning contaminated vacuum systems; training and communication; maintenance and infection risk.
[SHFN 30 Part A – PDF page 56]
Pneumatic air tube transport systems
Guidance for the design and management of pneumatic transport systems can be found in Scottish Health Technical Memorandum 08-04.
The pneumatic piping system should be designed to permit cleaning and disinfection of the tubing.
Computer equipment
Prior to purchasing computers or hand held devices which are to be used in clinical areas it is important that these must be able to withstand cleaning and disinfection compatible with the device. As with other equipment this should be monitored for signs of damage.