SHFN 30 Part A: Post Project Evaluation (pages 33–40)
[SHFN 30 Part A – PDF page 33]
drafting operational procedures;
establishing baseline and future staffing profiles;
establishing baseline and future revenue budgets;
establishing final equipment requirements;
identifying policy issues for referral to the Commissioning Team or the
construction project team;
identifying staff training needs;
establishing the occupation programme for each user function, for
incorporating into the overall masterplan.
The Project Team may also need to be involved in processes for:
transfer of facilities;
phased or staged occupation;
strategy for equipping;
selection of equipment;
storage and subsequent cleaning/disinfection of any furniture or equipment;
commissioning domestic services for cleaning;
site visits;
artwork;
furnishing and fittings including decorating;
interior finishes and fixtures;
post-handover period;
decommissioning of redundant facilities;
period of handover to operational management.
Note: Although this must be robustly resisted, commissioning of building services is frequently curtailed to meet deadlines or put in the hands of inadequately qualified or inexperienced personnel. This is invariably to the detriment of user satisfaction, operational efficiency, HAI risk and running costs and should be avoided.
Post Project Evaluation
The purpose of post-project evaluation is to improve project appraisal, design, management and implementation. This typically takes place 12 months post- handover and is a learning process that should not be seen as a means of allocating blame. There are three stages:
project appraisal;
monitoring and evaluation of the project;
[SHFN 30 Part A – PDF page 34]
review of project operations.
It is useful for members of the Project Team to be included at this stage in the evaluation teams that are reviewing project alternatives. The outcomes (activity and its consequences) of the project will not be amenable to evaluation until the facility has been in use for some time. However, if the project is part of a phased refurbishment or new build, valuable lessons can be learned and implemented during ongoing project work.
Note: It is important that the project is evaluated in terms of its original objectives, not in the light of any new legislation or development.
Reference should be made to the HAI-SCRIBE questionsets in Part B - the Implementation Strategy and Assessment Process section of this guidance relating to the design and planning stage of any development.
Logistics
The design of the healthcare facility must realistically consider the logistics of a functioning facility. It is essential that systems are in place which will inhibit the spread of infection and resources and personnel are managed so that they do not contribute to the risk of infection.
Examples of logistical issues to consider include:
the delivery and distribution of clean materials and people via connecting
corridors and lifts;
the collection, transportation and storage pending removal or disposal of
waste materials;
the separation of clean and dirty traffic flows;
clinical workflows.
These issues require careful planning and design which recognise the potential for infection spread through the mismanagement of such issues.
Summary
The following are the main issues for designers and Project Team personnel to consider in designing a healthcare facility. However, the infection risk should be assessed in conjunction with other risks as conflicts can arise (e.g. with respect to the needs of dementia patients).
Design to facilitate cleanliness and cleaning:
use finishes that are impermeable, smooth, seamless and durable, as far as
practicable;
cove hard flooring up the walls for a short distance to provide an easy to
clean junction;
[SHFN 30 Part A – PDF page 35]
eliminate or minimise dead-legs and blind ends in water systems, both in the
original design and as the systems are modified;
provide hands-free operation for as many facilities as is practicable – for
example: bins, taps, lights, sanitary equipment, flushing, doors;
consider integral blinds as an alternative to curtains at internal windows.
To facilitate safe working practices (for example, tidiness, and hand hygiene):
provide sufficient space for activities to take place and to avoid cross-
contamination between adjacent spaces;
provide sufficient storage for patients’ possessions and for all supplies to
discourage clutter;
ensure proper segregation and management of waste, including healthcare
waste and linen;
provide sufficient domestic waste receptacles;
provide bedside waste disposal facilities for patient use;
eliminate or minimise difficult to clean gaps and ledges or horizontal
surfaces such as window sills which encourage clutter;
provide enough wash-hand basins and soap dispensers;
plan for and deliver good separation of clean and dirty activities;
provide sufficient space for storage and preparation of cleaning equipment
and materials;
provide suitable facilities for cleaning of equipment.
Design for easy cleaning:
it is always best practice to maintain a visibly clean environment that is free
from dust and soilage, and acceptable to patients, their visitors and staff;
good design can make cleaning immeasurably easier, for example
using finishes that are easy to clean;
in clinical areas, flooring should be seamless and smooth, slip-resistant, easily cleaned and appropriately wear-resistant.
consultation should take place with the local IPC team prior to purchase and
on planning.
The Infection Prevention and Control Team should be consulted throughout a building or renovation project and their advice and recommendations taken into account and documented.
[SHFN 30 Part A – PDF page 36]
5. Typical rooms: purpose and content
Note: For the purposes of this guidance, the following terminology is used (A full Glossary of terms can be found in Appendix 2):
a. Multi-bed room is a room that contains more than one bed. It is best practice for these to have both en-suite toilet with shower, clinical wash-hand basin and doors to the main ward area.
b. Single-bed room is a room with space for one patient and usually contains as a minimum: a bed; locker/ wardrobe; and clinical wash-hand basin. (NB: single-bed rooms without en-suite sanitary facilities are not recommended).
c. En-suite single-bed room this is the same as ‘b’ but with en-suite shower, WC and wash-hand basin. (In new build, space for a social support zone for overnight stay and a clinical support zone is also provided).
d. Enhanced Single room (with en-suite facilities) this is the same as ‘c’ but with a ventilation system that prevents uncontrolled escape of infectious aerosols from the room to adjacent areas. It can also provide a degree of dilution of infectious aerosols in the room for the safety of staff and visitors. The room should have extract ventilation that exceeds its supply, such that gaps in its fabric leak inwards not outwards.
e. Enhanced Single room (with en-suite facilities and ventilated lobby) this is the same as ‘d’ but with a lobby having positive pressure ventilation.
SHPN 04:01 Supplement 1: Within this guidance Isolation facilities either suite/room with specialised ventilation are parts d & e.
Generic rooms
Note: Information on sanitary fittings, taps, etc. is contained in paragraphs 4.45 – 4.73. For further information on room contents, refer to Activity Data Base (ADB) sheets generally issued as part of briefing information.
Isolation Facilities
The primary aim of Project Team is to prevent the spread of infection between patients, visitors and staff by control or containment of potentially pathogenic organisms. Many of these organisms can be controlled by basic IPC practices such as hand hygiene and environmental cleanliness and this can be facilitated by single room isolation. A small proportion of patients requiring isolation will require isolation facilities as per d & e. (SHPN 04-01 Supplement 1: ‘Isolation facilities in acute settings’).
The key to effective isolation on general wards is the provision of sufficient en- suite single-bed rooms to prevent patients known to be a risk for spreading
[SHFN 30 Part A – PDF page 37]
infections being cared for in open ward areas. Single rooms reduce the risk of cross-infection for non-airborne diseases. Most patients requiring segregation/isolation on general wards can be isolated effectively in en-suite single rooms.
NHS Boards should audit the use of en-suite single-bed rooms to determine local requirements.
Note: In Accident & Emergency departments, where it is feasible to do so, a dedicated room should be provided for patients with a known or suspected infectious agent/disease transmitted wholly or partly by the airborne route. If source isolation is required, this room should be at negative pressure to the corridor; a lobby is not required. This room should be suitable for general use when not required for isolation.
Multi-bed rooms can also be used to cohort patients with the same infection if they have en-suite toilet and shower, and a door to the main ward area. The possible need for this should be considered at the design stage.
Storage of, and ready access to, clean disposable PPE to support the practices set out in Health Protection Scotland’s National Infection Prevention and Control Manual is important to encourage its use plus appropriate waste receptacles for disposal once worn.
Gloves and aprons and other disposable PPE should be sited at the entrance to single-bed rooms.
Additional storage facilities will be required for the care and treatment of patients in isolation facilities, especially if the isolation is likely to last for some time:
the storage of the minimum amount of supplies needed;
lockable provision for personal clothing and possessions. (see Appendix 3,
paragraph 3/11 for additional information).
Design
Scottish Health Planning Note 04, Supplement 1 – ‘Isolation facilities for infectious patients in acute settings’ provides guidance on the facilities required for isolating infectious patients on acute general wards (source isolation). It also provides guidance on the ventilation parameters for an enhanced single bed room and ventilated lobby.
Ceilings
Removable ceiling tiles are not advised for specialist ventilated isolation rooms/suites (SHTM 60).
[SHFN 30 Part A – PDF page 38]
Doors
Doors design is critical to the design of a specialist ventilation isolation room/suite. For specific guidance on source isolation, refer to Scottish Health Planning Note 04-01, Supplement 1 – ‘Isolation facilities for infectious patients in acute settings’.
Enhanced single room with en-suite facilities and ventilated lobby ‘e’
Lobbies provide an area for staff to undertake hand hygiene and to don and remove PPE. (SHPN 04: Supplement 1).
Engineering requirements for special ventilated isolation rooms/suites
Maintenance programme and revalidation programmes should be established for specialised ventilated isolation rooms to ensure the design criteria are maintained and met at all times. Although it is impossible to give specific maintenance frequencies, each unit should be included in a Planned Preventive Maintenance (PPM) programme that includes pressure/air flow monitoring equipment.
Recommendations
single-bed rooms with en-suite sanitary facilities are optimum for infection
prevention and control design;
there should be sufficient en-suite single-bed rooms to prevent patients
known to be a risk for spreading infections being cared for in open ward areas. Healthcare providers should audit the use of en-suite single-bed rooms to determine where further local requirements and adaptations are greatest;
the provision of additional isolation facilities should be considered when
designing new healthcare buildings and renovating existing buildings.
Ancillary Areas
It is important that ancillary areas are of an acceptable standard to support effective infection prevention and control. Clean and dirty areas should be in separate rooms and the workflow patterns of each area should be clearly defined.
The design and finish of ancillary areas should facilitate good cleaning, have facilities for hand hygiene, and sufficient storage for supplies and equipment together with provision for the removal of Personal Protective Equipment to waste or to wash.
Infection Prevention and Control issues are determined on:
the use of the ancillary area;
who will have access; and
what type of activity will be carried out there
[SHFN 30 Part A – PDF page 39]
Ancillary areas include:
dirty utility;
clean utility;
clean linen store;
domestic services rooms (DSRs);
decontamination facility/disposal room;
day room/patient waiting areas;
play areas;
nappy-changing area;
storage;
visitors’ toilets;
laundry departments;
changing accommodation;
treatment room.
Key activity spaces for each of the above functions are described in HBN 00-03. SHPN 04-01 and SHPN 36 describe the design requirements for the above rooms in hospital or community facilities.
Dirty utility room
(SHPN 04-01, SHPN 36 and HBN 00-03)
A dirty utility room should include facilities for:
cleaning items of equipment;
testing urine;
disposal of body fluids;
decontamination of commodes;
temporarily holding items requiring reprocessing;
hand hygiene.
Space and facilities for holding, reprocessing or disposal of bedpans, urinals and emesis (vomit) bowls are required. Commodes, unused bedpans, urinals, vomit bowls and linen bag carriers can also be stored. Closed storage is required for aprons and gloves. Storage cupboards should be provided.
A working stock of clean goods should be stored within a Dirty Utility Room. Clean goods would include unused bedpans & urinals and cleaned commodes.
Where commodes are to be used, there should be sufficient space allowed for their decontamination and storage of a working stock.
[SHFN 30 Part A – PDF page 40]
A clinical wash-hand basin is necessary plus a deep sink for equipment with draining board (or macerator, if available) for urine disposal and a separate deep sink for decontaminating equipment.
There needs to be clear demarcation achieved between clean/unused equipment and soiled/dirty equipment. A defined clean-to-dirty workflow is also required.
Clean utility room
(SHPN 04-01 and HBN 00-03)
A clean utility room is required where drugs and lotions may be stored and prepared, a supply of clean and sterile supplies may be held and dressing trolleys prepared. Designated hand hygiene facilities are required but must be positioned sufficiently far away from infusate preparation to prevent splashing and contamination.
The room should be located adjacent to the treatment area.
It is important that planners/design teams think about the type of storage facilities provided. There are three options: cantilevered units, mobile units or units fixed to the floor with no gaps.
It is important that sufficient dedicated worktop area is provided to enable aseptic preparation to be carried out, e.g. preparation of intravenous infusion. This provision should be sufficiently distant from the wash hand basin as to prevent contamination.
Storage facilities should be able to be cleaned easily and quickly while protecting clean stores and equipment from dust and contamination. Sloping surfaces should be provided up to ceiling level to permit cleaning.
Clean linen store
(SHPN 04-01 and HBN 00-03)
Clinical areas should have designated areas for the storage of clean linen to maintain the cleanliness of the linen and allow easy access. Storage should be on slatted shelving or racking and be off the floor. Where shelving is fixed, it should be provided with kick boarding provided to avoid the need to clean the floor underneath. Shelving should be cleanable and not harbour dust.
Treatment room
(SHPN 04-01 and HBN 00-03)
A treatment room may be required for in-patient examination or investigations on the ward. It will certainly be needed in primary care settings and will require different design features according to its planned use, for example, immunisation, wound dressing or surgical intervention and investigations.