[SHFN 30 Part A – PDF page 17]

Specialty areas

Every specialist area will have different requirements and infection control issues so cannot be planned as standard departments.

Critical care. Ultra clean ventilation. Theatres. Hydrotherapy. Mortuaries. SCBUs and maternity.

Renal units. Oncology. Neurology. Paediatrics. Decontamination units. Pharmacy aseptic dispensary.

Internal environment

Ventilation. Single rooms, bays, theatres, pacing rooms, treatment rooms, internal sanitary areas, enhanced single bed rooms with positive pressure lobby for isolation.

Heating/ventilation. Dust-free options i.e. hidden heat panels versus radiators. Minor procedure rooms.

Lighting. Quantity. The use of sealed units.

Furnishings, fittings and artwork. Walls/floors/ceilings – hygiene versus aesthetics.

Water. Dead-legs. Water turnover. Appropriate temperature for hot and cold systems. Water coolers/fountains.

General services

Disposal of waste. NHS versus Private Sector. Storage.

Communications. IT systems (timely information on pathology, etc, operational policies, infection control policies, procedures and training).

Emergency plans. Water storage if water cut off/heating/medical gases and vacuum/suction/emergency generator, ventilation, etc.

Table 3 continued: Infection control issues for the Project Team to consider in the Capital Planning Process.

Note: This is not an exhaustive list

[SHFN 30 Part A – PDF page 18]

Design Development stages

It is during the design stages that the Project Manager should verify with the Infection Prevention and Control Team that advice given previously is being followed up. As members of the Design Team, drawings and specifications should be available to them to explain how the design fulfils their requirements at the 1:200 and 1:50 plan stages of the project. Suggestions for improvement in operability are encouraged at this stage.

Note: Plans should be physically signed-off on completion of this stage to confirm full collaborative agreement. This is set out in Part B - Implementation Strategy section of this documentation.

In alteration or refurbishment projects, consideration should also be given to the impact on existing local facilities, e.g. ventilation, water supplies, etc.

Note: The Project Manager will need to recognise that value engineering will take place and that collective decisions should be taken on the basis of value for money.

Provision of single-bed room accommodation and bed space

Reference should be made to SHPN 04-01: ‘Adult in-patient facilities’. CEL 27(2010) Provision of SHPN single room accommodation and bed spacing states that for:-

New build facilities

For all new-build hospitals and other healthcare facilities which will provide inpatient accommodation there should be a presumption that all patients will be accommodated in single rooms unless there are clinical reasons for multi- bedded rooms to be available. These reasons should be clearly identified and articulated in the appropriate Business Case and will be subject to Scottish Government agreement as part of the Business Case approval process.

Refurbishment of existing healthcare facilities

For projects where existing accommodation is being refurbished it is recognised that each building to be refurbished will present unique problems. Taking into account the constraints of the existing building, a minimum of 50% single room accommodation will be allowed but close to 100% will be expected. Issues related to the adaptability of existing engineering services will have to be assessed.

Bed space

In relation to the issue of bed spacing for multi-bedded rooms, the current advice remains unchanged. That is, taking into account the ergonomic criteria, primarily the space required for patient handling and other activities which take place in the immediate vicinity of the bed, it is recognised that the minimum bed

[SHFN 30 Part A – PDF page 19]

space should not be less than 3.6m wide x 3.7m deep. Further guidance can be found in the notebox following paragraph 4.27.

When carrying out refurbishment work to existing multi-bedded ward accommodation, the NHS Boards should seek to achieve this bed spacing. This may require considering reducing the number of beds in the room and a risk based approach should be applied. NHS Boards should also seek to achieve this bed spacing standard in accommodation which is not being refurbished or replaced. Again a risk based approach should be applied.

Sizing of space

As indicated above in new build projects the bed provision will be in single rooms and the optimum space standards are set out in SHPN 04-01: ‘Adult in- patient facilities’. Where single bedroom accommodation is not possible in the alteration or refurbishment of existing wards and the minimum bed space of not less than 3.6m wide x 3.7m deep cannot be achieved then a risk assessment will be required to establish that appropriate space between beds is provided in accordance with the type of clinical intervention to be undertaken in the immediate patient environment.

Design, accessibility and space in patient areas all contribute to ease of manual handling, cleaning and maintenance.

Spacing must take into account access to equipment around the bed and access for staff to hand hygiene facilities. Sufficient space for equipment (e.g. hoists) is a health and safety issue for staff and patients.

Where it is not possible to meet the guidance recommendations set out in SHPNs and HBNs, Healthcare facilities must provide sufficient sanitary facilities including showers/bathrooms to ensure easy access, convenience and independence.

The principle should be to maintain sufficient space for ergonomic reasons to allow activities to take place safely, such as moving of equipment, patient lifting and movement, as well as ongoing maintenance. The exact space needed will vary according to numbers and activity of staff, type of patient, and environmental factors such as ventilation and humidity. Health Building Notes (HBN) 00-03: ‘Clinical and clinical support spaces’ and HBN 00-02: ‘Sanitary spaces’ provide details on calculating the optimum spaces required.

Particular issues for consideration sizing space include:

 patient groups;

 transmission of micro-organisms;

 avoiding cross-infection;

 the environment and its role in cross infection;

 shared equipment;

 movement of patients.

[SHFN 30 Part A – PDF page 20]

 management of issues:

 clinical pressures;

 best use of single rooms;

 avoiding unnecessary movement of patients between areas.

Bed density

The increase in the prevalence of antibiotic–resistant bacteria and immuno- compromised in-patients was one of the compelling reasons for mandating the maximum provision of en-suite single rooms.

Provision of isolation/single rooms used to segregate patients will help prevent the spread of micro-organisms, especially those transferred by the airborne route or those easily disseminated into the immediate patient environment.

Note: The source of guidance related to the provision of single bedrooms and bed spacing requirements can be found in Scottish Health Planning Note 04-01: ‘Adult in-patient facilities’ and CEL 27 (2010) issued by Health Finance Directorate of the Scottish Government 20 July 2010.

As previously described, the provision of adequate space around the bed can significantly improve the quality of the patient’s experience and aid the clinical and healing process. Clinicians and carers need adequate space around the bed, arranged in a functionally suitable way, to undertake their work efficiently and safely, making the most effective use of resources. Facilities should also serve the psychological needs of patients and their families providing a place of safety and privacy.

Departmental issues

There are some departments in a healthcare facility where infection risk is higher. The adjacency of these departments should be arranged so as not to increase further the risk of infection.

For example, departments with patients at a higher risk of contracting infection should be located and serviced to minimise risk of contamination from departments where patients are an infection risk.

For particular information on the content and conditions to be maintained within various rooms reference should be made to the Scottish Health Planning Notes (SHPN) or Health Building Notes (HBN) still applicable in Scotland that are appropriate to the department under review.

[SHFN 30 Part A – PDF page 21]

Interior finishes, fixtures and fittings

Note: Throughout this section of the document there is frequent reference to interior finishes, fixtures and fittings not being physically affected by detergents and disinfectants. Health Facilities Scotland National Cleaning Specification provides details on cleaning procedures and frequencies for use within NHS Scotland Healthcare Facilities. Additionally, Appendix 11 of Health Protection Scotland’s belonging to National Infection Prevention and Control Manual gives guidance on the management of blood and body fluid spillages and states that use of:

10,000ppm available chlorine disinfectant is recommended for disinfection of surfaces contaminated with spills of blood or certain body fluids (cerebrospinal fluid; peritoneal fluid; pleural fluid; synovial fluid; amniotic fluid; semen; vaginal secretions; breast milk; any other body fluid with visible blood).

1,000ppm available chlorine disinfectant is recommended for disinfection of surfaces contaminated with spills of urine/faeces/vomit/sputum only.

In addition, the Transmission Based Precautions section of the same document states 1,000ppm available chlorine disinfectant is recommended for environmental decontamination when caring for: patients with symptoms of infection; asymptomatic patients who are suspected or incubating an infection; or patients colonised with an infectious agent (i.e. Transmission Based Precautions).

Among other things, consideration should be given to meeting the requirements set out in these documents when selecting interior finishes, fixtures and fittings.

Flooring in clinical areas

(SHTM 61: Flooring)

Flooring must be seamless, impermeable, slip-resistant, easily cleaned and appropriately wear-resistant. There should be coving between the floor and the wall to prevent accumulation of dust and dirt in corners and crevices. Any joints should be welded or sealed to prevent accumulation of dirt and damage due to water ingress. Wood, tiles and flooring with unsealed joints are difficult to keep clean and should be avoided.

In areas where frequent wet cleaning methods are employed, floors should be of a material that is unaffected by the agents likely to be used, such as a disinfectant solution of 1,000 parts per million available chlorine.

Floors that are particularly subject to traffic when wet (bathrooms, kitchens) should be seamless, impermeable and slip-resistant, but be easily cleaned. Consideration will be required as to the suitability of existing cleaning equipment and its compatibility with new floor finishes.

Carpets are not recommended in clinical areas. Exceptions may include palliative care setting and audiology departments, however if there is a risk of blood/body fluid contamination in these areas the carpets should be able to

[SHFN 30 Part A – PDF page 22]

withstand exposure to a disinfectant solution of 10,000 parts per million available chlorine.

Walls

(SHTM 56: Partitions)

Smooth wipable impermeable surfaces are recommended in clinical areas and design should ensure that surfaces are easily accessed and will not be physically affected by detergents and disinfectants. Additional protection to walls should be considered to guard against gouging and impacts from bedhead and trolley movements. Surfaces should be free from fissures and crevices. Floors or walls penetrated by pipes, ducts and conduits should be sealed to prevent entry of pests and ease cleaning.

Ceilings

(SHTM 60: Ceilings)

Smooth jointless impermeable ceilings should be used in operating theatres and special ventilated isolation rooms.

Suspended ceilings may be installed in general clinical areas and other areas. Smooth wipable impermeable surfaces are recommended in clinical areas and design should ensure that surfaces are easily accessed.

Dust and fungal spores may accumulate on the upper surfaces of ceiling tiles over time and dispersal on removal of tiles may pose an inhalation risk to highly immuno-compromised patients. An HAI-SCRIBE review should be carried out before such work is undertaken.

Note: Routine and repetitive maintenance activities do not require fresh risk assessments on every occasion they are carried out.

Doors

(SMTM 56: Doors)

Doors should be cleanable, that is, smooth, wipable and have impermeable surfaces to ensure that surfaces will not be physically affected by detergents and disinfectants. This applies especially in clinical areas where contamination with blood or body fluid is a possibility.

Doors should have handles that can be easily cleaned and dried. Additional protection to doors should be considered to guard against gouging and impacts from bed and trolley movement. Particular advice related to mental health units is contained in Appendix 3.

[SHFN 30 Part A – PDF page 23]

Windows

(SHTM 55: Windows)

Windows should be sealed and unopenable in operating theatres. Consideration should be given to the elimination of windows in such accommodation. Windows should be sealed and unopenable in ICUs, Neonatal, Oncology and Haematology departments and special ventilated isolation rooms. Internal ledges to all windows should be avoided to prevent build up of dust and clutter. Sloping ledges should be considered in clinical areas.

Fixtures and fittings

All surfaces should be easily accessed, wipable and will not be physically affected by detergents and disinfectants. All work surfaces should be impermeable, designed for easy cleaning and be free of fissures and unsealed joints. They should be able to withstand the effects of regular cleaning with both detergents and disinfectants.

Gaps, ledges, etc., should be eliminated or minimised as they will harbour dust, particularly where fixtures and fittings interact with walls and floors making them difficult to clean.

Sanitary fittings

(SHTM 64 Sanitary assemblies and HBN 00-02 Sanitary spaces)

Hand hygiene facilities

Compliance with hand hygiene guidelines can be improved by conveniently placed and well-designed hand hygiene facilities. The importance of facilities to encourage and facilitate good hand hygiene practices should be high on the list of priorities when designing and planning new healthcare premises or refurbishment of existing premises is being undertaken.

Wash-hand basin design

(SHTM 64 Sanitary Facilities)

Clinical wash-hand basins - Specification

The dimensions of a clinical wash-hand basin should be large enough to contain most splashes and therefore enable the correct hand-wash technique to be performed without excessive splashing of the user or surrounding surfaces. This can also occur if the water outlet is placed too high above the basin.

Clinical wash-hand basins should be wall-mounted using concealed brackets and fixings. They should also be sealed to a seamless waterproof splash-back to allow effective cleaning of all surfaces. It should be noted that tile grouting is difficult to keep clean.

[SHFN 30 Part A – PDF page 24]

They should not have a plug or a recess capable of taking a plug. A plug allows the basin to be used to soak and reprocess equipment that should not be reprocessed in such an uncontrolled way.

Clinical wash-hand basins should not have overflows as these are difficult to clean and become contaminated.

Taps should not be aligned to run directly into the drain aperture, as contamination from the waste outlet could be mobilised and splashing could occur.

Clinical wash-hand basins - Provision

The location and provision of clinical wash-hand basins should ensure that they are all readily available and convenient for use. The location of clinical wash- hand basins is as important as the bed-to-basin ratio. Multi-bed room rooms’ basins should be located to ensure access by staff with the minimum travel between patient and basin; for example, one clinical wash-hand basin on each side of the entrance or at opposite sides of the room.

Taps in augmented care wards should not have flow straighteners (aerators), as Biofilm can develop on flow straighteners, rosettes and aerators. It is therefore recommended that these are removed. However, the decision to remove flow straighteners, rosettes and aerators should be based on risk assessment, as their removal can create turbulent flow at increased pressure resulting in splashing of surrounding surfaces and flooring.

Hand hygiene facilities to support the practices as set out in Health Protection Scotland’s National Infection Prevention and Control Manual should be readily available in all clinical areas. There should be sufficient numbers and appropriate sizes of clinical wash-hand basins to encourage and assist staff to conform readily to hand hygiene practices as set out in the HPS manual.

Guidelines for the appropriate numbers and location of clinical wash-hand basins in wards are given in Scottish Health Planning Note 04-01 ‘Adult in- patient facilities’ and in other clinical areas in Health Building Note 00-03 Clinical and clinical support spaces. In order to encourage good practice and to give reasonable access, it is recommended that:

 in en-suite single bedrooms a clinical wash-hand basin should be located in

the bedroom and a general wash-hand basin for patient’s personal hygiene in the en-suite;

 in four bedded rooms there should be two clinical wash-hand basins in the

room and a general wash-hand basin for patient’s personal hygiene in the en-suite. (Note that there should be no more than four beds in a multi-bed room in line with Health Building Note 04-01); Space may preclude this being provided in refurbishment projects within existing premises and risk assessments may accept this situation given the provision of alcohol-based hand rub facilities as the first choice for routine hand hygiene;

 in intensive care and high dependency units (critical care areas), a clinical

wash-hand basin should be available by each bed space. It should be noted,