HBN 00-03: Health Building Note 00-03 – 13 Generic clinical admin spaces: Offices
[HBN 00-03 – PDF page 153]
13 Generic clinical admin spaces: Offices
Office/meeting room
13.3 Lamp repeat calls for controlled drug cupboards (if used) and a key cupboard may be located here.
Room description and layout
13.4 A small safe, an alarm panel (see ‘Bedhead services’) and cube lockers for the storage of staff personal belongings may also be provided.
13.1 An office/meeting room is intended as a multipurpose office within a clinical environment for handover meetings and technical reviews.
13.2 The room layout provided (see Figure 119) includes two workstations and a table and chairs for informal meetings/handovers in an enclosed office.
13.5 A printer may be provided in each office if a shared printer is not available nearby. However, consideration must be given to the negative sustainability issues relating to the provision of many small local printers.
Figure 119 Space requirements for enclosed office, two workstations, table and chairs
Engineering services outlet zone
Desk or desktop
Filing cabinet
Desk or desktop
Noticeboard
Noticeboard
Engineering services outlet zone
Engineering services outlet zone
Mobile under-desk storage
Mobile under-desk storage
Office zone
Stacking chairs
Chair Chair
Table
Meeting zone
Chair
Chair
[HBN 00-03 – PDF page 154]
13 Generic clinical admin spaces: Offices
Ergonomic drawings
Administration workstation
13.8 Desks should include wire management and equipment should be able to be plugged in at desk height. Task lighting should be considered.
13.6 This ergonomic drawing (see Figure 120) shows the space requirements for an administration workstation.
13.9 The 900 mm space required to withdraw a chair from the desk will increase to 1000 mm for heavy upholstered chairs.
13.7 Office furniture should comply with BS EN 1335- 1.
13.10 Where there is frequent passing behind a desk, the preferred 1500 mm space should be provided. This will also allow for wheelchair access.
Figure 120 Space requirements for an administration workstation
Privacy screen
Minimum 1500 required for wheelchair access
1500 (1200) to obstruction
ambulant passing
Space to sit at desk/approx depth of storage unit
Noticeboard
Mobile under-desk storage
Approximate
width of mobile
storage unit
1400 (1200) – see notes
Filing cabinet or bookcase
Space to withdraw chair from desk
Space for ambulant passing when chair withdrawn
[HBN 00-03 – PDF page 155]
Working at a desk/table
13.13 The space requirement for a wheelchair user is based on a standard wheelchair.
13.11 This ergonomic drawing (see Figure 121) illustrates the space requirements for working at a desk/table.
13.14 The working zone on the desk/table is 700 mm wide by 500 mm deep. This may be compromised if two users sit at 90 degrees to one another at the corner of the desk/table.
13.12 The chair shown is a standard stacking chair. Where larger chairs are used, the space should be increased by an additional 100 mm in each direction.
Figure 121 Space requirements for working at a desk/table
Space for withdrawal of chair from table
Clearance for knees and feet
Space for chair
Approx working zone at table
chair
Clear space
under table
Space for sitting at
table, 600 min is
for bench seating
Space for withdrawal of independent wheelchair
Clear space to side
for independent
wheelchair access
ambulant passing
Approx working zone at table
wheelchair
user at table
Space under table
wheelchair close to table
ambulant passing
[HBN 00-03 – PDF page 156]
13 Generic clinical admin spaces: Offices
Office: 1-person
Room description and layout
13.17 A printer may be provided in each office if a shared printer is not available nearby. However, consideration must be given to the negative sustainability issues relating to the provision of many small local printers.
13.15 Single-person offices (see Figure 122) should only be provided where full-time access to workstations and constant privacy are required.
13.16 Offices may be used for discussions and informal interviews as well as clinical administration tasks.
13.18 If the room is used for clinical control, the lamp repeat calls for controlled drugs cupboards (if used) and a key cupboard will be required. A small safe and an alarm panel (see ‘Bedhead services’) may also be provided.
Figure 122 Space requirements for a single-person office
Engineering services outlet zone
Desk Filing cabinet or bookcase
Engineering services outlet zone
Mobile under-desk storage
Visitors’ chair
Visitors’ chair
Filing cabinet or bookcase
[HBN 00-03 – PDF page 157]
Ergonomic drawings
Administration workstation
13.21 Desks should include wire management and equipment should be able to be plugged in at desk height. Task lighting should be considered.
13.19 This ergonomic drawing (see Figure 123) shows the space requirements for an administration workstation.
13.22 The 900 mm space required to withdraw a chair from the desk will increase to 1000 mm for heavy upholstered chairs.
13.20 Office furniture should comply with BS EN 1335- 1.
13.23 Where there is frequent passing behind a desk, the preferred 1500 mm space should be provided. This will also allow for wheelchair access.
Figure 123 Space requirements for an administration workstation
Privacy screen
Minimum 1500 required for wheelchair access
1500 (1200) to obstruction
ambulant passing
Space to sit at desk/approx depth of storage unit
Noticeboard
Mobile under-desk storage
Approximate
width of mobile
storage unit
1400 (1200) – see notes
Filing cabinet or bookcase
Space to withdraw chair from desk
Space for ambulant passing when chair withdrawn
[HBN 00-03 – PDF page 158]
13 Generic clinical admin spaces: Offices
Office: 2-person
Room description and layout
13.25 A printer may be provided in each office if a shared printer is not available nearby. However, consideration must be given to the negative sustainability issues relating to the provision of many small local printers.
13.24 Offices may be used for discussions and informal interviews as well as clinical administration tasks.
Figure 124 Space requirements for a two-person office
Engineering services outlet zone
Visitor’s chair
Visitor’s chair
Filing cabinet or mobile storage
Filing cabinet or bookcase
Engineering services outlet zone
Mobile under-desk storage
Noticeboard
Noticeboard
Mobile under-desk storage
Filing cabinet or mobile storage
Engineering services outlet zone
Engineering services outlet zone
[HBN 00-03 – PDF page 159]
Health Building Note 00-03 – Clinical, clinical support and specialist spaces
Ergonomic drawings
Administration workstation
13.28 Desks should include wire management and equipment should be able to be plugged in at desk height. Task lighting should be considered.
13.26 This ergonomic drawing (see Figure 125) shows the space requirements for an administration workstation.
13.29 The 900 mm space required to withdraw a chair from the desk will increase to 1000 mm for heavy upholstered chairs.
13.27 Office furniture should comply with BS EN 1335- 1.
13.30 Where there is frequent passing behind a desk, the preferred 1500 mm space should be provided. This will also allow for wheelchair access.
Figure 125 Space requirements for an administration workstation
Privacy screen
Minimum 1500 required for wheelchair access
1500 (1200) to obstruction
ambulant passing
Space to sit at desk/approx depth of storage unit
Noticeboard
Mobile under-desk storage
Approximate
width of mobile
storage unit
1400 (1200) – see notes
Filing cabinet or bookcase
Space to withdraw chair from desk
Space for ambulant passing when chair withdrawn