Home › Scotland (NHS Scotland Assure / HFS) › HBN 00-03 › Health Building Note 00-03 – 14 Specialist spaces

HBN 00-03: Health Building Note 00-03 – 14 Specialist spaces

Core guidance - Clinical and clinical support spaces (HBN 00-03) · PDF pages 160–165 of 166 · Source file: hbn-00-03-oct-2014.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[HBN 00-03 – PDF page 160]

14 Specialist spaces

Plaster room

Room description and layout

14.2 The room layout provided (see Figure 126) is based on option 2 of the double-sided couch access treatment room with the inclusion of a plaster sink and associated ventilation for plaster dust.

14.1 A plaster room is used for the fitting and removal of plaster casts.

14.3 The computer must be suitable for use in a dusty environment.

Figure 126 Space requirements for a plaster room

Plaster trolley

Dressing/ instrument trolley

Plaster sink

Sack holder

Paper towel dispenser

Couch with paper roll attached Clinical wash-hand basin

Engineering services outlet zone

Sack holder

Chair Glove and apron dispenser

Large sack holder

Privacy curtain

Chair

Clinical workstation

Engineering services outlet zone

Engineering services outlet zone

[HBN 00-03 – PDF page 161]

Figure 127 Space requirements for standing use of a clinical wash-hand basin

Ergonomic drawings

assembly

Clinical wash-hand basin

Space to use basin at high level, ie above 600 mm from floor level

14.4 These ergonomic drawings (see Figure 127) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

14.5 The basin should be fitted with non- touch taps.

Glove & apron dispenser

high level

Space to use basin at

Space to use

from floor level

14.6 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

14.7 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

Concealed waste

Minimum distance to side wall

~120 service duct

14.8 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

14.9 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

Comfortable reach to side of basin

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

Flush concealed services duct

14.10 Lever taps are not illustrated.

14.11 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 162]

14 Specialist spaces

Plaster sink

further information on plaster sinks, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’. The underside of the sink and area beneath it should be designed for ease of cleaning and to avoid dirt traps.

14.12 This ergonomic drawing (see Figure 128) shows the space requirements for a plaster sink 1200 mm long and 600 mm deep. However, plaster sinks range in length from 1000 mm to 1600 mm. For

Figure 128 Space requirements for a plaster sink

Paper towel dispenser Soap dispenser

Standing close

to plaster sink

to allow

infrequent

ambulant

passing

Ambulant

passing

Space to work at plaster sink

[HBN 00-03 – PDF page 163]

Clinical workstation

14.13 This ergonomic drawing (see Figure 129) shows the space requirements for a clinical workstation.

14.14 The clinical workstation is intended for accessing and updating patient records within a clinical environment. It should only be used for short periods of time.

Figure 129 Space requirements for a clinical workstation

Approximate

Approximate

sitting height

standing height

Chair

standing at

clinical

workstation

workstation

sitting at clinical

[HBN 00-03 – PDF page 164]

14 Specialist spaces

Couch-based plaster activities

14.16 The space is slighter larger than that allowed for general examinations or treatments to allow for plastering activities.

14.15 This drawing (see Figure 130) shows the space requirements for double-sided access to a three- section couch for plaster activities.

14.17 This space has not been defined by specific ergonomic research.

Figure 130 Space requirements for double-sided access to a three-section couch for plaster activities

Ceiling-mounted

hook

Mirror

1900 (1600 for seated users only)

Engineering services outlets requirements

see HTM 02-01 and HTM 08-03

couch height varies

changing

plaster activities

plaster activities

Mirror

Chair

Ceiling- mounted hook

Couch with paper roll attached

Plaster bucket on stand

activities

plastering

[HBN 00-03 – PDF page 165]

Health Building Note 00-03 – Clinical, clinical support and specialist spaces

Dressing and undressing: ambulant

14.18 These ergonomic drawings (see Figure 131) show the space requirements for ambulant dressing and undressing.

14.19 An identical space provision is suitable for semi- ambulant users though it should be located adjacent to a seating area.

Figure 131 Space requirements for ambulant dressing and undressing

Maximum height

of permissible

low-level

obstructions

Space for full arm movements

when dressing and undressing

Space for arm movements when dressing and undressing

Space at floor/low level for dressing and undressing

Space at floor/low

level for dressing

and undressing

Space for arm movements

when dressing and undressing