HBN 00-03: Health Building Note 00-03 – 12 Generic clinical admin spaces: Open-plan admin areas (pages 145–152)
[HBN 00-03 – PDF page 145]
Breakout space
Room description and layout
12.33 In open-plan admin areas, they provide extra capacity for workspace should all the shared workstations be occupied. Consideration should be given to providing power and data sockets/ outlets for a laptop and a telephone point.
12.31 Breakout spaces are intended to provide for ad hoc social interaction and/or discussions and may be used in either administration areas for staff or within clinical areas for patients or staff.
12.34 The room layout provided (see Figure 112) shows a breakout space for use within an administration area.
12.35 Breakout spaces may be located alongside the shared workstations they serve (as shown) or combined with other breakout spaces into a central resource for more flexibility in use.
12.32 The choice of furniture will depend upon the location and function of the space (for example within staff admin areas, chairs and a table for basic work functions, for patient use, easy chairs and a coffee table).
Figure 112 Space requirements for a breakout space within an administration area
approx 2300
approx 2700
[HBN 00-03 – PDF page 146]
12 Generic clinical admin spaces: Open-plan admin areas
Ergonomic drawings
Space to sit on an easy chair
12.37 When seats are pushed together in rows, the average seat width is 600–650 mm for seats without arms and 750 mm for seats with arms.
12.36 These ergonomic drawings (see Figure 113) show the space requirements for a person to sit on an easy chair.
Figure 113 Space requirements to sit on an easy chair
Preferred location of table
extended legs
easy chair
Clearance between
chair and table
for access
Space for seating
ambulant passing
Restricted leg space to allow person to pass
[HBN 00-03 – PDF page 147]
Working at a desk/table
12.40 The space requirement for a wheelchair user is based on a standard wheelchair.
12.38 This ergonomic drawing (see Figure 114) illustrates the space requirements for working at a desk/table.
12.41 The working zone on the desk/table is 700 mm wide by 500 mm deep. This may be compromised if two users sit at 90 degrees to one another at the corner of the desk/table.
12.39 The chair shown is a standard stacking chair. Where larger chairs are used, the space should be increased by an additional 100 mm in each direction.
Figure 114 Space requirements for working at a desk/table
Space for withdrawal of chair from table
Clearance for knees and feet
Space for chair
Approx working zone at table
chair
Clear space
under table
Space for sitting at
table, 600 min is
for bench seating
Space for withdrawal of independent wheelchair
Clear space to side
for independent
wheelchair access
ambulant passing
Approx working zone at table
wheelchair
user at table
Space under table
wheelchair close to table
ambulant passing
[HBN 00-03 – PDF page 148]
12 Generic clinical admin spaces: Open-plan admin areas
Quiet workspace
12.43 The room has been sized to discourage users from feeling too comfortable and wishing to monopolise the space.
Room description and layout
12.44 The design (including finishes) – see Figure 115 – should ensure privacy and a quiet environment.
12.42 This room provides a quiet space for confidential telephone conversations or laptop/deskwork by a single person.
12.45 It should contain power, data and telephone services.
Figure 115 Space requirements for quiet workspace ensuring privacy
Space to withdraw chair from desk
Noticeboard
Desk or desktop
Alternative door location
Minimum 1400 working space required
Optional glazed partition, acoustic and visual privacy to be considered
[HBN 00-03 – PDF page 149]
Staff communication base
Room description and layout
12.59 The security of the base when not manned/out-of- hours may be achieved by either placing it within a total locked zone of the building or by providing a lockable security grille or similar device to enclose the base.
12.46 A staff communication base is a workstation, typically with a split-level counter, intended as a clinical management base within a clinical area.
12.47 It replaces the “nurses base” from previous guidance; changes in working practices means the base will be used by a multidisciplinary team rather than just nurses.
12.60 Care needs to be taken when determining the counter design; high counters can make it difficult for staff and clients to communicate, especially where the client is of short stature, a child, in a wheelchair, or if the client or staff member is hearing impaired. High and particularly wide counters can also create ergonomic risks for staff, particularly short staff.
12.48 It should provide good observation of the clinical area served. Staff emergency call facilities should be provided at the desk.
12.49 A telephone and computer should be provided. Task lighting should be considered.
12.61 A low counter is typically around 720 mm above the floor and is suitable for wheelchair/seated users and children. In some circumstances consideration may be given to allowing both the member of staff and client to sit as it may create a more intimate situation.
12.50 Lamp repeat calls for controlled drugs cupboards (if used) will be located here. An alarm panel may be provided.
12.51 Access to a safe room/space must be provided behind the base to ensure staff safety. This could be access to a safe corridor.
12.62 A high counter, also known as a parcel shelf, may be provided to shield equipment etc from outside view, to provide a convenient writing surface for visitors or staff or to provide an additional safety barrier without the use of intimidating safety glass.
12.52 A local printer and fax machine may be located in a room behind the base or other nearby secure area.
12.53 A space for private discussions should be provided nearby. This may form a discrete part of the base with glass screens or an interview room may be provided for this purpose.
12.63 A high counter designed for direct interaction between staff and clients should not result in excessive reach across the work surface. The recommended height of a high counter is around 1200 mm and it should be designed to permit the location of a flat panel monitor on the work surface below (note: BS 8300 recommend a 1100 mm high counter to support standing users).
12.54 The number of workstations should be based on maximum staff usage at any one time.
12.64 Staff communication bases with both high and low sections are generally recommended.
12.55 Space around the base should ensure free movement of traffic when someone is standing in front of the base.
12.65 The recommended minimum working width for a member of staff at the base is 800 mm per person. A width of 1200 mm per person is generally only required for prolonged use but has been included in the examples for flexibility.
12.56 The layout provided (see Figure 116) illustrates the generic design issues and space requirements for a staff communication base. Actual design requirements will depend upon local requirements.
12.57 The main issues to consider when evaluating the requirements for a staff communication base are:
• the safety of staff at the base and security of the base out-of-hours;
12.66 BS 8300 recommends, and Approved Document M requires, that the minimum width of the low level section of counter is 1500 mm, preferably 1800 mm, to allow for a wheelchair user and attendant on one side or two wheelchair users to face each other diagonally.
• the height and size of the desk, which will relate to its access and use.
12.67 In addition to staff emergency call, power and data services, the following controls and/or indicators may be located at the base as appropriate:
12.58 Staff security may be achieved by providing a vertical or horizontal barrier in front of the base and a safe place behind the base.
[HBN 00-03 – PDF page 150]
12 Generic clinical admin spaces: Open-plan admin areas
• controls for general lighting, heating, medical gas isolation and entry systems;
12.68 For more details of the space requirements for access to the desk for wheelchair users see BS 8300.
• indicator panels for call systems, fire alarm and controlled drugs cupboards.
Figure 116 Space requirement for staff communication base
Optional security grille/enclosure
Optional security grille/ enclosure
Access to staff only area for safety
Optional protective hood, parcel shelf/top counter
approx 1200
ENCLOSED BASE
approx 800
ambulant passing
desk standing
Access to staff only area for safety
Space for two people ambulant/semi-ambulant passing
withdrawing from desk
ambulant passing
Space for bed movement
Space for wheelchair user access
Low-level counter for wheelchair user or children’s access – minimum overall width of low-level section 1500
PART OPEN BASE
Alarm panel
Mobile storage
Access to staff only area for safety
Space behind desk for one person only
OPEN BASE
Space behind desk for wheelchair access
[HBN 00-03 – PDF page 151]
Touchdown base
staff, standing or perching on a stool, does not cause an obstruction.
Room description and layout
12.72 An alarm panel and lamp repeat calls for controlled drugs cupboards (if used) may be located here.
12.69 A touchdown base is intended for accessing and updating electronic patient records and other computer work, adjacent to, but not within, an individual clinical room. It should only be used for short periods of time.
12.73 The computer screen should provide good visibility to the user. Task lighting should be considered.
12.74 The security of information should be considered when the computer is not in use/not manned.
12.70 The touchdown base may consist of a worktop (as shown) or mobile workstation and computer at standing height.
12.75 The base should include a telephone socket.
12.71 A touchdown base should be recessed sufficiently from any circulation routes so that a member of
12.76 The layout provided (see Figure 117) is based on single-person use.
Figure 117 Space requirement for a touchdown base, single-person use
Maximum projection of optional wall- mounted storage
Optional
observation window
into clinical space
Approx 1420, eye level small person
Touchdown base Circulation space varies
Optional stool
Working area length Approx 1750, eye level tall person
Space to stand and work and ro allow passing. 900 preferred if sitting
Space for two people ambulant/ semi-ambulant passing
Space for bed movement
1600 for sitting at touchdown base
[HBN 00-03 – PDF page 152]
12 Generic clinical admin spaces: Open-plan admin areas
Ergonomic drawings
Clinical workstation
12.78 The clinical workstation is intended for accessing and updating patient records within a clinical environment. It should only be used for short periods of time.
12.77 This ergonomic drawing (see Figure 118) shows the space requirements for a clinical workstation.
Figure 118 Space requirements for a clinical workstation
Approximate
Approximate
sitting height
standing height
Chair
standing at
clinical
workstation
workstation
sitting at clinical