[HBN 00-03 – PDF page 98]

8 Generic clinical support spaces: Utility

Figure 74 Space requirements for dirty utility room for bedpan processing

Paper roll dispenser

Clinical waste bin by sink

Zone for wall cupboards or adjustable shelves

Bedpan drainage rack where bedpan washer is used

Worktop with base cupboards underneath and wall cupboards/ shelves above

Disposal unit

Service duct

Urine bottle dispenser

Vomit bowl dispenser

Bedpan washer or macerator

Bedpan dispenser

Linen skip

Clinical wash-hand basin

Linen skip

Sack holder

Paper towel dispenser

Glove and apron dispenser

[HBN 00-03 – PDF page 99]

Figure 75 Space requirements for standing use of a clinical wash-hand basin

Ergonomic drawings

assembly

Clinical wash-hand basin

Space to use basin at high level, ie above 600 mm from floor level

8.64 These ergonomic drawings (see Figure 75) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

8.65 The basin should be fitted with non- touch taps.

Glove & apron dispenser

high level

Space to use basin at

8.66 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

Space to use

from floor level

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

8.67 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

Concealed waste

8.68 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

Minimum distance to side wall

~120 service duct

8.69 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

Comfortable reach to side of basin

8.70 Lever taps are not illustrated.

Flush concealed services duct

8.71 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 100]

8 Generic clinical support spaces: Utility

Disposal unit

8.72 This ergonomic drawing (see Figure 76) shows the space requirements for a disposal unit comprising a combined sink and hopper.

8.73 Subject to local infection control advice, consideration may be given to providing integrated units (that is, a combined unit with a washer or macerator, bucket sink, and base cupboard/storage unit).

Figure 76 Space requirements for disposal unit comprising combined sink and hopper

approx 900

Slop hopper Sink

Standing

close to

sink to

allow

infrequent

passing

Space to use slop

hopper at high

level ie 600 mm

above floor level

Space to use slop

hopper at low

level ie up to

600 mm from floor level

Space to use sink

infrequent

passing

while

someone

stands close

to the sink

Space to use slop hopper at low level ie up to 600 mm from floor level

Space to use slop hopper at high level ie 600 mm above floor level

Space to use sink

[HBN 00-03 – PDF page 101]

Washers and macerators

8.79 Electricity supply requirements for the washer or macerator are subject to manufacturers’ information.

8.74 Washers are available in tall and low profile models. Tall models are front loading, with the loading door generally at working height. Low profile units may be top or front loading.

8.80 Drainage requirements vary. They may be located in rear, side or bottom of the unit but are generally 110 mm for washers and 50 mm for macerators. The indicative room layout assumes a 110 mm waste located in the rear.

8.75 Most washers can process three bedpans and three urine bottles per cycle, with each cycle taking just under 10 minutes.

8.76 Consideration should be given to the safe storage of the detergents used in the cleaning process.

8.77 Macerators are generally low profile and top loading.

8.81 It is important to consider the spatial requirements and services for the equipment as early as possible in the planning process. Failure to do so can result in a loss of functional space within the room (for example to allow for service ducts), which may be detrimental to safe and efficient working.

8.82 This ergonomic drawing (see Figure 77) illustrates the space requirements for a macerator or washer.

8.78 When macerators are used, local infection control advice should be sought on the appropriate cleaning regime for the bedpan itself since the macerator will only deal with the bedpan liners.

[HBN 00-03 – PDF page 102]

8 Generic clinical support spaces: Utility

Figure 77 Space requirements for a macerator or washer

Washer

approx 600

Service duct

Front-loading tall washer

Space to load washer from the side

Space to use

washer at low

level ie up to

600 mm from floor level

Space to use

washer at high

level ie 600 mm

above floor level

Space to load washer from the front

Macerator or washer

approx 150

Top-loading washer/macerator

Service duct

approx 1450–1650

Space to load top- load washer from the front

Space to load front- load washer from the side

Space to use

washer/macerator

at high level ie

600 mm above floor level

Space to use

washer/

macerator

at low level ie

up to 600 mm

from floor level

Front-loading washer

Space to use washer/ macerator at low level ie up to 600 mm from floor level

Space to use washer/macerator at high level ie 600 mm above floor level

[HBN 00-03 – PDF page 103]

Standard base and wall cupboards

worktops or other obstructions project more than 500 mm, the reach dimensions illustrated relate to the front edge of the wall cupboard (that is, reaching into the cupboard would proved difficult).

8.83 This ergonomic drawing (see Figure 78) shows the space requirements to access standard, floor mounted, base and wall cupboards. Where

Figure 78 Space requirements to access standard, floor mounted base and wall cupboards

Recommended depth of cupboard depends upon depth of worktop

Distance between front of worktop and front of wall cupboard Depth of wall cupboard

Sloping top to wall cupboards will assist with cleaning/ infection control

Maximum height of wall cupboard

Maximum height that allows all users access

Clear space between worktop

and bottom of wall cupboard

Maximum height that allows full forward reach onto shelf etc

Space for working and ambulant passing, 1600 preferred for frequent passing

Space for ambulant passing

Standing close for infrequent passing

ambulant passing when someone is working at the worktop

Space for working. (900) to access base cupboard

[HBN 00-03 – PDF page 104]

8 Generic clinical support spaces: Utility

Dirty utility room

reduce the risk of spillages and cross contamination, and to increase working efficiencies.

Room description and layout

8.87 The room layout provided (see Figure 79) is not appropriate where significant quantities of equipment need to be held for reprocessing (that is, where a CCSD returns trolley is required).

8.84 This room is used for holding waste sacks prior to their removal to a disposal hold and for the disposal of small amounts of liquid human waste. Urinalysis may also take place here (using a dipstick). Small quantities of small items may be held here prior to reprocessing.

8.88 The illustrated space requirements for accessing modular base and upper cabinets is based on space to access standard cupboards, not using baskets or trays. However, adequate space is available for side access to baskets or trays.

8.85 The space required for holding waste sacks will depend on the local disposal policy. As soon as sacks have been filled, to avoid cluttering and build-up of odours, they should be sealed and taken away (as soon as possible thereafter) to the associated disposal hold to await collection.

8.89 The layout has taken on board research from the Loughborough University Healthcare Ergonomics & Patient Safety unit, DH research report B(05)02, Dec 2007.

8.86 The location of dirty utility rooms should minimise travel distances for staff from patient areas to

[HBN 00-03 – PDF page 105]

Figure 79 Space requirements for dirty utility room

Zone for wall cupboards or shelves

Worktop with base cupboards underneath

Glove and apron dispenser

Sack holder

Clinical wash-hand basin

Paper roll

dispenser

Paper towel dispenser

Sack holder

Disposal unit

Service duct

Sack holder

Clinical waste bin by sink

Sack holder