HBN 00-03: Health Building Note 00-03 – 8 Generic clinical support spaces: Utility (pages 98–105)
[HBN 00-03 – PDF page 98]
8 Generic clinical support spaces: Utility
Figure 74 Space requirements for dirty utility room for bedpan processing
Paper roll dispenser
Clinical waste bin by sink
Zone for wall cupboards or adjustable shelves
Bedpan drainage rack where bedpan washer is used
Worktop with base cupboards underneath and wall cupboards/ shelves above
Disposal unit
Service duct
Urine bottle dispenser
Vomit bowl dispenser
Bedpan washer or macerator
Bedpan dispenser
Linen skip
Clinical wash-hand basin
Linen skip
Sack holder
Paper towel dispenser
Glove and apron dispenser
[HBN 00-03 – PDF page 99]
Figure 75 Space requirements for standing use of a clinical wash-hand basin
Ergonomic drawings
assembly
Clinical wash-hand basin
Space to use basin at high level, ie above 600 mm from floor level
8.64 These ergonomic drawings (see Figure 75) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.
Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser
8.65 The basin should be fitted with non- touch taps.
Glove & apron dispenser
high level
Space to use basin at
8.66 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.
Space to use
from floor level
ie up to 600 mm
basin at low level,
Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)
Concealed waste
~120 service duct
Minimum distance to side wall
Paper towel dispenser
8.67 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.
(50) Minimum clearance between paper towel dispenser and duct
Projecting concealed services duct
Concealed waste
8.68 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.
Minimum distance to side wall
~120 service duct
8.69 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:
Space to use
from floor level
Space to use
ie up to 600 mm
basin at low level,
from floor level
ie above 600 mm
basin at high level,
passing
ambulant
“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”
Comfortable reach to side of basin
8.70 Lever taps are not illustrated.
Flush concealed services duct
8.71 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.
[HBN 00-03 – PDF page 100]
8 Generic clinical support spaces: Utility
Disposal unit
8.72 This ergonomic drawing (see Figure 76) shows the space requirements for a disposal unit comprising a combined sink and hopper.
8.73 Subject to local infection control advice, consideration may be given to providing integrated units (that is, a combined unit with a washer or macerator, bucket sink, and base cupboard/storage unit).
Figure 76 Space requirements for disposal unit comprising combined sink and hopper
approx 900
Slop hopper Sink
Standing
close to
sink to
allow
infrequent
passing
Space to use slop
hopper at high
level ie 600 mm
above floor level
Space to use slop
hopper at low
level ie up to
600 mm from floor level
Space to use sink
infrequent
passing
while
someone
stands close
to the sink
Space to use slop hopper at low level ie up to 600 mm from floor level
Space to use slop hopper at high level ie 600 mm above floor level
Space to use sink
[HBN 00-03 – PDF page 101]
Washers and macerators
8.79 Electricity supply requirements for the washer or macerator are subject to manufacturers’ information.
8.74 Washers are available in tall and low profile models. Tall models are front loading, with the loading door generally at working height. Low profile units may be top or front loading.
8.80 Drainage requirements vary. They may be located in rear, side or bottom of the unit but are generally 110 mm for washers and 50 mm for macerators. The indicative room layout assumes a 110 mm waste located in the rear.
8.75 Most washers can process three bedpans and three urine bottles per cycle, with each cycle taking just under 10 minutes.
8.76 Consideration should be given to the safe storage of the detergents used in the cleaning process.
8.77 Macerators are generally low profile and top loading.
8.81 It is important to consider the spatial requirements and services for the equipment as early as possible in the planning process. Failure to do so can result in a loss of functional space within the room (for example to allow for service ducts), which may be detrimental to safe and efficient working.
8.82 This ergonomic drawing (see Figure 77) illustrates the space requirements for a macerator or washer.
8.78 When macerators are used, local infection control advice should be sought on the appropriate cleaning regime for the bedpan itself since the macerator will only deal with the bedpan liners.
[HBN 00-03 – PDF page 102]
8 Generic clinical support spaces: Utility
Figure 77 Space requirements for a macerator or washer
Washer
approx 600
Service duct
Front-loading tall washer
Space to load washer from the side
Space to use
washer at low
level ie up to
600 mm from floor level
Space to use
washer at high
level ie 600 mm
above floor level
Space to load washer from the front
Macerator or washer
approx 150
Top-loading washer/macerator
Service duct
approx 1450–1650
Space to load top- load washer from the front
Space to load front- load washer from the side
Space to use
washer/macerator
at high level ie
600 mm above floor level
Space to use
washer/
macerator
at low level ie
up to 600 mm
from floor level
Front-loading washer
Space to use washer/ macerator at low level ie up to 600 mm from floor level
Space to use washer/macerator at high level ie 600 mm above floor level
[HBN 00-03 – PDF page 103]
Standard base and wall cupboards
worktops or other obstructions project more than 500 mm, the reach dimensions illustrated relate to the front edge of the wall cupboard (that is, reaching into the cupboard would proved difficult).
8.83 This ergonomic drawing (see Figure 78) shows the space requirements to access standard, floor mounted, base and wall cupboards. Where
Figure 78 Space requirements to access standard, floor mounted base and wall cupboards
Recommended depth of cupboard depends upon depth of worktop
Distance between front of worktop and front of wall cupboard Depth of wall cupboard
Sloping top to wall cupboards will assist with cleaning/ infection control
Maximum height of wall cupboard
Maximum height that allows all users access
Clear space between worktop
and bottom of wall cupboard
Maximum height that allows full forward reach onto shelf etc
Space for working and ambulant passing, 1600 preferred for frequent passing
Space for ambulant passing
Standing close for infrequent passing
ambulant passing when someone is working at the worktop
Space for working. (900) to access base cupboard
[HBN 00-03 – PDF page 104]
8 Generic clinical support spaces: Utility
Dirty utility room
reduce the risk of spillages and cross contamination, and to increase working efficiencies.
Room description and layout
8.87 The room layout provided (see Figure 79) is not appropriate where significant quantities of equipment need to be held for reprocessing (that is, where a CCSD returns trolley is required).
8.84 This room is used for holding waste sacks prior to their removal to a disposal hold and for the disposal of small amounts of liquid human waste. Urinalysis may also take place here (using a dipstick). Small quantities of small items may be held here prior to reprocessing.
8.88 The illustrated space requirements for accessing modular base and upper cabinets is based on space to access standard cupboards, not using baskets or trays. However, adequate space is available for side access to baskets or trays.
8.85 The space required for holding waste sacks will depend on the local disposal policy. As soon as sacks have been filled, to avoid cluttering and build-up of odours, they should be sealed and taken away (as soon as possible thereafter) to the associated disposal hold to await collection.
8.89 The layout has taken on board research from the Loughborough University Healthcare Ergonomics & Patient Safety unit, DH research report B(05)02, Dec 2007.
8.86 The location of dirty utility rooms should minimise travel distances for staff from patient areas to
[HBN 00-03 – PDF page 105]
Figure 79 Space requirements for dirty utility room
Zone for wall cupboards or shelves
Worktop with base cupboards underneath
Glove and apron dispenser
Sack holder
Clinical wash-hand basin
Paper roll
dispenser
Paper towel dispenser
Sack holder
Disposal unit
Service duct
Sack holder
Clinical waste bin by sink
Sack holder