[HBN 00-03 – PDF page 90]

8 Generic clinical support spaces: Utility

Figure 67 Space requirements for standing use of clinical wash-hand basin

Clinical wash-hand basin

assembly

Space to use basin at high level, ie above 600 mm from floor level

8.24 These ergonomic drawings (see Figure 67) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

8.25 The basin should be fitted with non- touch taps.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

Glove & apron dispenser

high level

Space to use basin at

8.26 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

Space to use

from floor level

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

8.27 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

8.28 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

Concealed waste

Minimum distance to side wall

~120 service duct

8.29 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

8.30 Lever taps are not illustrated.

Comfortable reach to side of basin

Flush concealed services duct

8.31 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 91]

Clean utility room

Room description and layout

access will be from the side). However, option 1 is slightly wider allowing the tall storage units to be arranged so that the room can accommodate an extra storage unit and racking as opposed to just mobile trolleys down the centre of the room.

8.32 This room is for storing sterile supplies and consumables, including infusion fluids, and for storing and preparing medicines, including controlled drugs.

8.36 The illustrated space requirements for accessing modular base and upper cabinets is based on space to access standard cupboards, not using baskets or trays. However, adequate space is available for side access to baskets or trays.

8.33 Empty supplies trolleys and dressings/instruments trolleys will be held here and restocked for distribution to wards and clinical areas.

8.34 Two room layouts have been provided (see Figures 68 and 69).

8.37 The illustrated space requirements for accessing modular racking is based on space to access open shelves.

8.35 Both layouts provide limited access to the tall storage units from the front (i.e. it is assumed

[HBN 00-03 – PDF page 92]

8 Generic clinical support spaces: Utility

approx 500

Clinical

wash-hand

basin

Supplies

trolley

Zone for racking

and/or supplies

trolleys

holder

Paper towel

dispenser

Sack

holder Sack

dispenser

Glove

and apron

Restricted

front access

to retracted

basket/tray

Drugs

fridge

Cupboard

for

flammable

items

Tall

storage

unit

Controlled

Drugs

cupboard

approx 500 Storage zone

Storage zone

approx 500

Storage zone

Restricted

front access

to retracted

basket/tray

Zone for racking

and/or supplies

trolleys

Supplies

trolley

Clinical

wash-hand

basin

Racking

holder

Paper towel

dispenser

Sack

holder Sack

Glove

and apron

dispenser

Drugs

fridge

Cupboard

for

flammable

items

approx 680

Storage zone

Wall-mounted twin Controlled Drugs cupboard

Tall

storage

unit

Tall

storage

unit

Figure 68 Clean supply room (option 1) Figure 69 Clean supply room (option 2)

[HBN 00-03 – PDF page 93]

Figure 70 Space requirements for standing use of a clinical wash-hand basin

Ergonomic drawings

assembly

Clinical wash-hand basin

Space to use basin at high level, ie above 600 mm from floor level

8.38 These ergonomic drawings (see Figure 70) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

8.39 The basin should be fitted with non- touch taps.

Glove & apron dispenser

high level

Space to use basin at

8.40 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

Space to use

from floor level

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

8.41 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

Concealed waste

Minimum distance to side wall

~120 service duct

8.42 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

8.43 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

Comfortable reach to side of basin

Flush concealed services duct

8.44 Lever taps are not illustrated.

8.45 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 94]

8 Generic clinical support spaces: Utility

Tall modular storage cabinets

8.47 This ergonomic drawing (see Figure 71) shows the space requirements to access a cabinet with 600 mm wide baskets/trays.

8.46 Tall modular storage cabinets are generally constructed to accommodate 600 × 400 mm baskets and trays to provide a variety of fixed or mobile storage options. The cabinets may be constructed to have either 400 mm or 600 mm wide facing baskets or trays.

8.48 Tall modular storage cabinets are generally 2100 mm high; the top shelves are higher than those recommended for normal fixed storage units because the baskets/trays can be angled to enable their contents to be accessed.

Figure 71 Space requirements to access tall modular storage cabinets with 600 mm wide baskets/trays

Baskets/trays may be angled to assist access

Maximum height of storage unit

Maximum height that allows all users access

Maximum height that allows full forward reach onto shelf etc

Optional door

Depth of storage unit

Depth of basket/ tray when retracted

Space to access baskets/trays from the front ambulant passing when someone is accessing baskets/ trays from the front Space to access baskets/trays from the side

[HBN 00-03 – PDF page 95]

Standard base and wall cupboards

worktops or other obstructions project more than 500 mm, the reach dimensions illustrated relate to the front edge of the wall cupboard (that is, reaching into the cupboard would proved difficult).

8.49 This ergonomic drawing (see Figure 72) shows the space requirements to access standard, floor mounted, base and wall cupboards. Where

Figure 72 Space requirements to access standard, floor mounted base and wall cupboards

Recommended depth of cupboard depends upon depth of worktop

Distance between front of worktop and front of wall cupboard Depth of wall cupboard

Sloping top to wall cupboards will assist with cleaning/ infection control

Maximum height of wall cupboard

Maximum height that allows all users access

Clear space between worktop

and bottom of wall cupboard

Maximum height that allows full forward reach onto shelf etc

Space for working and ambulant passing, 1600 preferred for frequent passing

Space for ambulant passing

Standing close for infrequent passing

ambulant passing when someone is working at the worktop

Space for working. (900) to access base cupboard

[HBN 00-03 – PDF page 96]

8 Generic clinical support spaces: Utility

Open shelves

8.53 The shelf intervals (that is, space between two shelves) should at least equal the depth of the shelves.

8.50 This ergonomic drawing (see Figure 73) shows the space requirements to access high open shelves. The same principles apply to modular open racking.

8.54 The illustrated access space is for general use (with shelves up to 450 mm deep). Where items are large or heavy the access space may need to increase by up to 500 mm.

8.51 The height and dimensions of the shelves should relate to the size and weight of items stored and frequency with which they will be handled.

8.55 Where heavy or otherwise difficult to move items are stored at the end of shelves a 200 mm clearance is required to the side of the object for safe access.

8.52 Frequently used items should be stored on shelves positioned at 300–1500 mm above floor level. Frequently used small items should be stored on shallow shelves at or near worktop height (that is, 900 mm). Heavy object should be stored below worktop height.

Figure 73 Space requirements to access high open shelves

Maximum reach

Space between shelves to be equal to

or greater than shelf depth, except

where baskets/trays are used

Minimum shelf

height (for small

items only)

Height below which reach into

shelf becomes difficult

Maximum shelf height for

full reach into shelf

Maximum shelf height. 300 is comfortable reach

ambulant passing

Depth of shelves

Space to access shelves while standing

Space to access shelves while bending

Space to access shelves while kneeling

[HBN 00-03 – PDF page 97]

Dirty utility room for bedpan processing

8.60 The room layout provided (see Figure 74) is based on the use of a macerator or washer.

Room description and layout

8.56 This room will fulfil the same functions as the dirty utility room with the addition of the disposal of the contents of bedpans and urine bottles into a macerator or bedpan washer.

8.61 Where a macerator is used, consideration should be given to providing both a macerator for the disposal of the liners and waste products and a washer for the subsequent cleaning of bedpan holders etc. This arrangement is currently a topic for discussion on the basis of perceived improved infection control but is not specifically recommended.

8.57 It will also be used for storing clean urine bottles, bedpans (or bedpan liners) and vomit bowls, and for holding dirty linen where used. Commodes and sani-chairs may be stored here.

8.62 The illustrated space requirements for accessing modular base and upper cabinets is based on space to access standard cupboards, not using baskets or trays. However, adequate space is available for side access to baskets or trays.

8.58 The location of the dirty utility rooms should minimise travel distances for staff from patient areas to reduce the risk of spillages and cross contamination, and to increase working efficiencies.

8.63 The layout has taken on board research from the Loughborough University Healthcare Ergonomics & Patient Safety unit, DH research report B(05)02, Dec 2007.

8.59 Local policy will determine whether to use disposable or reusable urine bottles and vomit bowls and/or whether to use bedpans with liners.