[HBN 00-03 – PDF page 106]

8 Generic clinical support spaces: Utility

Figure 80 Space requirements for standing use of a clinical wash-hand basin

Ergonomic drawings

assembly

Clinical wash-hand basin

Space to use basin at high level, ie above 600 mm from floor level

8.90 These ergonomic drawings (see Figure 80) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

8.91 The basin should be fitted with non- touch taps.

Glove & apron dispenser

high level

Space to use basin at

Space to use

8.92 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

from floor level

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

8.93 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

Concealed waste

Minimum distance to side wall

~120 service duct

8.94 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

8.95 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

Comfortable reach to side of basin

Flush concealed services duct

8.96 Lever taps are not illustrated.

8.97 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 107]

Disposal unit

8.98 This ergonomic drawing (see Figure 81) shows the space requirements for a disposal unit comprising a combined sink and hopper.

8.99 Subject to local infection control advice, consideration may be given to providing integrated units (that is, a combined unit with a washer or macerator, bucket sink, and base cupboard/storage unit).

Figure 81 Space requirements for a disposal unit comprising a combined sink and hopper

approx 900

Slop hopper Sink

Standing

close to

sink to

allow

infrequent

passing

Space to use slop

hopper at high

level ie 600 mm

above floor level

Space to use slop

hopper at low

level ie up to

600 mm from floor level

Space to use sink

infrequent

passing

while

someone

stands close

to the sink

Space to use slop hopper at low level ie up to 600 mm from floor level

Space to use slop hopper at high level ie 600 mm above floor level

Space to use sink

[HBN 00-03 – PDF page 108]

8 Generic clinical support spaces: Utility

Standard base and wall cupboards

8.100 This ergonomic drawing (see Figure 82) shows the space requirements to access standard, floor mounted, base and wall cupboards. Where

worktops or other obstructions project more than 500 mm, the reach dimensions illustrated relate to the front edge of the wall cupboard (that is, reaching into the cupboard would proved difficult).

Figure 82 Space requirements to access standard, floor mounted base and wall cupboards

Recommended depth of cupboard depends upon depth of worktop

Distance between front of worktop and front of wall cupboard Depth of wall cupboard

Sloping top to wall cupboards will assist with cleaning/ infection control

Maximum height of wall cupboard

Maximum height that allows all users access

Clear space between worktop

and bottom of wall cupboard

Maximum height that allows full forward reach onto shelf etc

Space for working and ambulant passing, 1600 preferred for frequent passing

Space for ambulant passing

Standing close for infrequent passing

ambulant passing when someone is working at the worktop

Space for working. (900) to access base cupboard

[HBN 00-03 – PDF page 109]

Medicine store/preparation room

Room description and layout

medicines storage/preparation is required outside clinical rooms. The illustrated space requirements (see Figure 83) for accessing modular base and upper cabinets is based on space to access standard cupboards, not using baskets or trays. However, adequate space is available for side access to baskets or trays.

8.101 This room is used for storing and preparing medicines, including controlled drugs. This space will only be needed if a central clean supply room is used instead of clean utility rooms and

Figure 83 Space requirements for medicine store/preparation room

Space above wall-mounted storage may be blocked off to reduce dust collection

Wall-mounted twin Controlled Drugs cupboard

Drugs fridge

Cupboard for flammable items

Wall-mounted twin Controlled Drugs cupboard

Clinical wash-hand basin

Sack holder

Sack holder

Paper towel dispenser

Glove and apron dispenser

[HBN 00-03 – PDF page 110]

8 Generic clinical support spaces: Utility

Figure 84 Space requirements for standing use of a clinical wash-hand basin

Ergonomic drawings

assembly

Clinical wash-hand basin

Space to use basin at high level, ie above 600 mm from floor level

8.102 These ergonomic drawings (see Figure 84) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

8.103 The basin should be fitted with non- touch taps.

Glove & apron dispenser

high level

Space to use basin at

Space to use

from floor level

8.104 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

8.105 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

Concealed waste

Minimum distance to side wall

~120 service duct

8.106 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

8.107 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

Comfortable reach to side of basin

Flush concealed services duct

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

8.108 Lever taps are not illustrated.

8.109 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 111]

Health Building Note 00-03 – Clinical, clinical support and specialist spaces

Tall modular storage cabinets

8.111 This ergonomic drawing (see Figure 85) shows the space requirements to access a cabinet with 600 mm wide baskets/trays.

8.110 Tall modular storage cabinets are generally constructed to accommodate 600 × 400 mm baskets and trays to provide a variety of fixed or mobile storage options. The cabinets may be constructed to have either 400 mm or 600 mm wide facing baskets or trays.

8.112 Tall modular storage cabinets are generally 2100 mm high; the top shelves are higher than those recommended for normal fixed storage units because the baskets/trays can be angled to enable their contents to be accessed.

Figure 85 Space requirements to access tall modular storage cabinets with 600 mm wide baskets/trays

Baskets/trays may be angled to assist access

Maximum height of storage unit

Maximum height that allows all users access

Maximum height that allows full forward reach onto shelf etc

Optional door

Depth of storage unit

Depth of basket/ tray when retracted

Space to access baskets/trays from the front ambulant passing when someone is accessing baskets/ trays from the front Space to access baskets/trays from the side