HTM 05-02: Appendix B: Periods of fire resistance

Firecode - Guidance in support of functional provisions (Fire safety in the design of healthcare premises) · PDF pages 87–88 of 112 · Source file: HTM_05-02_2015.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 05-02 – PDF page 87]

Appendix B: Periods of fire resistance

• resistance to the transfer of excessive heat (insulation), which applies to fire- separating elements.

The performance of those elements of the building which are required to achieve a specified period of fire resistance is determined by reference to BS 476-20–24:1987. Performance is assessed against one or more of the following criteria:

Table B1 summarises the specific requirements for each element in terms of the three performance requirements above.

• resistance to collapse (load-bearing capacity), which applies to load- bearing elements;

A suspended ceiling should not be relied upon to contribute to the fire resistance of a compartment floor.

• resistance to fire penetration (integrity), which applies to fire-separating elements;

[HTM 05-02 – PDF page 88]

Table B1 Periods of fire-resistance

Part of building Minimum provisions when tested to the relevant part of BS 4761 (minutes)

Method of exposure

Integrity Insulation

Load-bearing capacity2

Minimum provisions when tested to the relevant European standard3

See Table 5 Not applicable Not applicable R (see Table 5) Exposed faces

Structural frame, beam or column

Load-bearing wall See Table 5 Not applicable Not applicable R (see Table 5) Each side separately

REI 60 From the underside

Compartment floor 4,5

Not applicable

Each side separately

Compartment wall6

Single-storey buildings

EI 60 EI 30

Not applicable EI 30 Each side separately

Sub-compartment wall6

Not applicable EI 30 Each side separately

Wall to a fire hazard room

Protected shaft REI 60 Each side separately

Fire-fighting shafts REI 120 From side remote from shaft

REI 60 From shaft side

1. construction separating the shaft from the building

REI 60 Each side separately

2. construction separating fire- fighting stairway from the fire- fighting lift shaft and fire-fighting lift lobby

Cavity barrier8 Not applicable E 30 and EI 15 Each side separately

Not applicable EI 30 From the underside

Fire-resisting ceiling (as described in paragraph 5.42)

Notes:

1. BS 476-21 for load-bearing elements; BS 476-22 for non-load-bearing elements; BS 476-23 for fire-protecting suspended ceilings; and BS 476-24 for ventilation ducts. BS 476-8 results are acceptable for items tested or assessed before 1 January 1988.

2. Applies to load-bearing elements only (see B3.ii and Appendix E of Approved Document B).

3. The national classifications do not automatically equate with the equivalent classifications in the European column; therefore, products cannot typically assume a European class unless they have been tested accordingly.

• “R” is the European classification of the resistance to fire performance in respect of load-bearing capacity;

• “E” is the European classification of the resistance to fire performance in respect of integrity; and

• “I” is the European classification of the resistance to fire performance in respect of insulation.

4. See Table 5 for floors that are over 12 m and 30 m above ground level.

5. Guidance on increasing the fire resistance of existing timber floors is given in BRE Digest 208 – ‘Increasing the fire resistance of existing timber floors’.

6. Except for any limitations on glazed elements.

7. May be reduced if sprinklers are installed.

8. For the purposes of meeting the Building Regulations, cavity barriers will be deemed to have satisfied the provisions above, provided that they achieve an integrity requirement of at least 30 minutes and an insulation requirement of at least 15 minutes.