HTM 05-02: Appendix A: Glossary of terms
[HTM 05-02 – PDF page 83]
Appendix A: Glossary of terms
For the purposes of this document the following terms are defined:
Cavity barrier: a construction, other than a smoke curtain, provided to close a concealed space against penetration of smoke or flame, or provided to restrict the movement of smoke or flame within such a space.
Air transfer grille (fire and cold smoke): a device that will allow the passage of air in normal use, but when activated will contain both cold smoke and hot gases – usually activated by heat and an electrical interface with the detection and alarm system.
Circulation space: a space (including a protected stairway) mainly used as a means of access between a room and an exit from the building or compartment.
Class 0 surface spread of flame: the classification achieved by a material or composite product which is either:
Assisted patient evacuation: the assisted evacuation of patients by staff, which may include the use of support equipment (for example ski sheets, evacuation chairs, mattresses).
a. composed throughout of materials of limited combustibility; or
Atrium (plural atria): a space, or system of conjoined spaces, within the building that adjoins more than one storey.
Note
b. a Class 1 material (when tested in accordance with BS 476-7:1971 or 1987) which, when tested in accordance with BS 476-6:1981 or 1989, has a fire propagation index (I) of not more than 12 and a sub-index (i1) of not more than 6.
Shafts used solely for stairs, escalators, lifts or services are not classified as atria.
Class 0 is not a classification identified in any British Standard test.
Auto-suppression: mechanical methods of fire suppression that are activated automatically – such systems may include water sprinklers and CO2 flooding systems.
Basement storey: a storey with a floor which at some point is more than 1200 mm below the highest level of ground adjacent to the outside wall.
Compartment (fire): a building or part of a building, comprising one or more rooms, spaces or storeys, constructed to prevent the spread of fire to or from another part of the same building, or an adjoining building. (A roof space above the top storey of a compartment is included in that compartment.)
[HTM 05-02 – PDF page 84]
Compartment floor: a fire-resisting floor used to separate one fire compartment from another and having a minimum period of resistance of 60 minutes.
performance criteria to those ends. (It may have one or more leaves, and the term includes a cover or other form of protection to an opening in a fire-resisting wall or floor, or in a structure surrounding a protected shaft.)
Fire engineering: the application of scientific and engineering principles to the protection of people, property and the environment from fire.
Compartment wall: a fire-resisting wall used to separate one fire compartment from another and having a minimum period of resistance of 60 minutes (or 30 minutes in single-storey buildings).
Fire hazard: a set of conditions in the operation of a product or system with the potential for initiating a fire.
Emergency lighting: lighting provided for use when the power supply to the normal lighting fails.
Fire hazard room: a room or other area which, because of its function and/or contents, presents a greater hazard of fire occurring and developing than elsewhere.
Escape lighting: that part of the emergency lighting which is provided to ensure that the escape routes are illuminated at all material times.
Final exit: the termination of an escape route from a building giving direct access to a place of safety outside the building.
Fire resistance: the ability of an element of building construction, a component or a structure to fulfil, for a stated period of time, the required load-bearing capacity, fire integrity and/or thermal insulation and/or other expected duty in a standard fire resistance test.
Fire stop: a seal provided to close an imperfection of fit or design tolerance between elements or components, to restrict the passage of fire and smoke.
Fire-and-smoke damper: fire-and-smoke damper, triggered by AFD, which, when tested in accordance with BS EN 1366-2, meets the ES classification requirements defined in BS EN 13501-3:2005 and achieves the same fire resistance in relation to integrity as the element of the building construction through which the duct passes.
Note
Healthcare building: a hospital, treatment centre, health centre, clinic, surgery, walk-in centre or other building where patients are provided with medical care by a clinician.
Intumescent fire-and-smoke dampers may be tested to ISO 10294-5.
Height of a building (or storey): the distance from ground level at the lowest side of the building measured to the finished floor level of the top storey.
Fire containment air transfer grille: a device that will allow the passage of air in normal use, but when activated will contain the passage of fire and hot smoke.
Hospital street: a special type of compartment that connects final exits, stairway enclosures and department entrances, and serves as a fire-fighting bridgehead and a safe evacuation route for occupants to parts of the building unaffected by fire.
Material of limited combustibility: either:
Fire door: a door or shutter provided for the passage of persons, air or objects, which, together with its frame and furniture as installed in a building, is intended when closed to resist the passage of fire and/or gaseous products of combustion and is capable of meeting specified
• a non-combustible material; or
[HTM 05-02 – PDF page 85]
Appendix A: Glossary of terms
(including any exit route between the foot of the stairway and the final exit) that is adequately enclosed in fire-resisting construction.
• any material of density 300 kg/m3 or more which, when tested in accordance with BS 476-11, does not flame, and whose rise in temperature on the furnace thermocouple is not more than 20°C; or
Refuge: a place of temporary safety within a building. This may be an adjoining compartment or sub-compartment capable of holding all those threatened, without a significant change in level and from which there is potential for further escape should that become necessary.
• any material with a non-combustible core of 8 mm thickness or more, having combustible facings (on one or both sides) not more than 0.5 mm thick; or
Relevant boundary:
a. the actual boundary of the premises; or
b. the boundary of the site which the side of the building faces, and which is parallel, or at an angle of not more than 80°, to the side of the building; or
• any material of density less than 300 kg/m3 which, when tested in accordance with BS 476-11, does not flame for more than 10 seconds and whose rise in temperature is not more than 35°C on the centre (specimen) thermocouple and not more than 25°C on the furnace thermocouple.
c. the centre line of a road, railway, river or canal that adjoins the actual boundary; or
d. a notional boundary established between buildings, if two or more buildings share the same site.
Non-combustible: any material which is capable of satisfying the performance requirements specified in BS 476-4, or any material which when tested in accordance with BS 476-11 does not flame or cause any rise in temperature on either the centre (specimen) or furnace thermocouple.
Patient-access areas: those areas of the healthcare building to which patients have reasonable access either with or without supervision.
Swing beds: Single-bed rooms located in such a manner that they can be part of either the “male wing” or the “female wing”. Swing beds are generally provided where sleeping accommodation is segregated by sex, and then only in facilities providing in-patient mental health services or accommodation for people with learning disabilities.
Place of safety: a place where persons are in no danger from fire.
Smoke-retarding construction: construction intended to retard the passage of smoke.
Progressive horizontal evacuation: evacuation of patients away from a fire into a fire-free compartment or sub-compartment on the same level.
Protected shaft: a shaft that enables persons, air or objects to pass from one compartment to another, and which is enclosed with fire- resisting construction.
Protected stairway: a stairway discharging through a final exit to a place of safety
In the absence of an appropriate method of test and performance criteria, such construction should not contain unsealed joints and permanently open or openable areas. Joints between such construction and any abutting element should be tight and preferably sealed with a filler conforming to BS EN 1366-3 or BS EN 1366-4 (for example plaster), a mastic, or a flexible strip (for example neoprene), as appropriate.
[HTM 05-02 – PDF page 86]
Unprotected area: in relation to a side or external wall of building, this means:
• window, door or other opening; and
Any doors located within smoke-retarding construction, when tested in accordance with BS 476-31.1 with the threshold taped, and subjected to a pressure of 25 Pa, should have a leakage rate not exceeding 3 m3/h per metre.
Sub-compartments: areas into which the building can be divided to reduce travel distance and which provide 30 minutes’ resistance to fire.
• any part of an external wall which has a period of fire resistance less than that required for the elements of structure (integrity and load-bearing capacity only), and which provides less than 15 minutes’ fire resistance (insulation); and
Sub-compartment wall: a fire-resisting wall used to separate one sub-compartment from another and having a minimum period of fire resistance of 30 minutes.
• any part of the external wall which has combustible material more than 1 mm thick attached or applied to its external face, whether for cladding or any other purpose. (Combustible material in this context is a material which is neither “non-combustible” nor a “material of limited combustibility”.)
Travel distance: the horizontal distance to be travelled by a person from any point within the floor area to the nearest adjoining compartment, sub-compartment, escape stairway or external exit, having regard to the layout of walls, partitions, fittings and furniture.