Home › England (NHS England estates) › HTM 05-02 › 7. Access and facilities for the fire-and-rescue service

HTM 05-02: 7. Access and facilities for the fire-and-rescue service

Firecode - Guidance in support of functional provisions (Fire safety in the design of healthcare premises) · PDF pages 76–82 of 112 · Source file: HTM_05-02_2015.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 05-02 – PDF page 76]

7. Access and facilities for the fire-and-rescue service

d. the provision of fire mains within the

Requirement

building;

e. private fire hydrants;

Chapter 7 provides guidance to comply with the following Requirement from Part B of Schedule 1 of the Building Regulations 2010.

f. venting for heat and smoke from basement areas.

Requirement

Site access

Access and facilities for the fire service

B5

7.2 When considering site access for the fire- and-rescue service, the following should be considered:

a. the location and number of site access

points;

(1) The building shall be designed and constructed so as to provide reasonable facilities to assist firefighters in the protection of life.

b. the design of the internal roadways

with respect to width, radii of bends, gradients, clearance between and under buildings;

(2) Reasonable provision shall be made within the site of the building to enable fire appliances to gain access to the buildings.

c. the weight and turning circle of the fire

appliances.

7.1 The fire-and-rescue service, once alerted, will attend quickly and, once there, should be provided with adequate facilities to ensure the protection of life and property. Particular matters which require consideration are:

7.3 A minimum of two access points to the site, suitable for use by the fire-and-rescue service, should be provided for fire appliances. Their location should be agreed with all relevant authorities.

a. site access;

b. vehicular access around the buildings

for fire appliances;

c. access into the building for the fire-

fighting personnel;

7.4 New hospital roads that may be used by fire appliances should comply with Table 10 of this Health Technical Memorandum. One access point for the fire-and-rescue service may be an emergency access point dedicated solely for the use of the fire service.

[HTM 05-02 – PDF page 77]

7. Access and facilities for the fire-and-rescue service

Access around the building

7.6 Where access is provided to an elevation in accordance with Table 9, overhead obstructions should be avoided in the zone indicated in Figure 26.

7.5 Access around a healthcare building is required to enable high-reach appliances to be used where necessary, and to enable pumping appliances to supply water and equipment for fire-fighting and rescue activities.

7.7 Turning facilities should be provided in any dead-end route that is more than 20 m long.

overhead obstructions to be avoided in this zone

face of building at ground level or vertical plane of projecting upper storey

C D

A B

hard standing or access road obstruction

Type of appliance

Turntable ladder Hydraulic platform Dimension (m) Dimension (m)

A. Maximum distance of near edge of 4.9 2.0 hard standing from building

B. Minimum width of hard standing 5.0 5.5

C. Minimum distance of further edge of 10.0 7.5 hard standing from building

D. Minimum width of unobstructed space N/A 2.2 (for swing of appliance platform)

Note: 1. Hard standing for high-reach appliances should be as level as possible and should not exceed a gradient of 1 in 12.

2. Fire appliances are not standardised. Some fire services have appliances with a greater weight or different size. In consultation with the fire-and-rescue authority, the building control body should adopt the relevant dimensions and ground-loading capacity.

Figure 26 Relationship between building and access roads or hard standings for high-reach appliances

[HTM 05-02 – PDF page 78]

Firecode – fire safety in the NHS: HTM 05-02: Guidance in support of functional provisions for healthcare premises

This can be by hammerhead or turning circle, designed on the basis of Table 10 and Figure 27.

7.8 Access for fire appliances to healthcare buildings not fitted with internal fire mains should comply with the guidance in Table 9.

Total floor area (m²) Height above ground of top storey (m) Provide vehicle access to: Type of appliance

Up to 2000 Up to 9

Within 45 m

Pump

Over 9

15% of perimeter

High-reach

2000 to 8000 Up to 9

15% of perimeter

Pump

Over 9

50% of perimeter

High-reach

8000 to 16,000 Up to 9

50% of perimeter

Pump

Over 9

50% of perimeter

High-reach

16,000 to 24,000 Up to 9

75% of perimeter

Pump

Over 9

75% of perimeter

High-reach

Over 24,000 Up to 9

100% of perimeter

Pump

Over 9

100% of perimeter

High-reach

Note: The total floor area is the aggregate of all floors within the building.

Table 9 Fire-and-rescue-service access around hospitals not fitted with fire mains

Minimum width of gateways (m)

Appliance type Minimum width of road between kerbs (m)

Minimum clearance height (m)

Minimum turning circle between kerbs (m)

Minimum turning circle between walls (m)

Minimum carrying capacity (tonnes)

Pump 3.7 3.1 16.8 19.2 3.7 12.5

High-reach 3.7 3.1 26.0 29.0 4.0 17.0

Notes

1. Fire appliances are not standardised. Some fire services have appliances of greater weight or different size. In consultation with the fire-and-rescue authority, the building control body may adopt other dimensions in such circumstances.

2. Because the weight of high-reach appliances is distributed over a number of axles, it is considered that their infrequent use of a carriageway or route designed to 12.5 tonnes should not cause damage. It would therefore be reasonable to design the road base to 12.5 tonnes, although structures such as bridges should have the full 17-tonne capacity.

Table 10 Typical vehicle access route specification

Fire and rescue service vehicles should not have to reverse more than 20 m from the end of an access road

Fire service

Exit

vehicle

20 m max.

Turning circle, hammerhead

or other point at which

vehicle can turn

Figure 27 Turning circles

[HTM 05-02 – PDF page 79]

7. Access and facilities for the Fire and Rescue Service

b. the depth of basements;

c. floor area; and

Access and facilities for the fire service

d. the provision of hospital streets.

7.9 In low-rise buildings without deep basements, the needs of the fire service will be met by a combination of the normal means of escape and the measures required for vehicular access around the building.

Number and location of fire-fighting shafts – health buildings not provided with a hospital street

7.10 The requirements for additional facilities (fire-fighting shafts, fire mains and fire hydrants) for the fire-and-rescue service are determined by:

7.11 For health buildings not provided with hospital streets, fire-fighting shafts should be provided in accordance with the requirements of Table 11.

a. the height of the building;

Area of largest floor

No sprinklers Sprinklers

Over 3300 m2

Less than 900 m2 Between 900 m2 and 1800 m2

Between 1800 m2 and 3300 m2

Over 3300 m2 Less than 900 m2 Between 900 m2 and 1800 m2

Between 1800 m2 and 3300 m2

Below ground

Two basement storeys

Not required 3 plus 1 for every additional 1500 m2

Not required 3 plus 1 for every additional 1500 m2

More than 10 m (see note 2)

1 + lift 1 + lift 2 + lift 3 + lift plus 1 for every additional 1500 m2

1 + lift 1 + lift 2 + lift 3 + lift plus 1 for every additional 1500 m2

Above ground

Up to 12 m Not required Not required Not required Not required Not required Not required Not required Not required

Not required Not required Not required Not required

Between 12 m and 18 m

3 plus 1 for every additional 900 m2

Over 18 m (see note 2)

1 + lift 2 + lift 2 + lift 3 + lift plus 1 for every additional 900 m2

1 + lift 2 + lift 2 + lift 3 + lift plus 1 for every additional 1500 m2

45 m along a route suitable for laying hose 60 m along a route suitable for laying hose

Hose laying distance (see note 3)

Notes:

1. Depth of basements and heights of storey above ground are all measured from fire service vehicle access level.

2. One fire-fighting shaft should also include a fire-fighting lift.

3. Fire-fighting shafts, irrespective of building height, should be located to meet the maximum hose laying distances. In order to meet the hose laying criterion it may be necessary to provide additional fire mains in escape stairways. This does not imply that these stairs should be otherwise designed as fire-fighting shafts.

4. For further guidance on measuring the height of a building, reference should be made to Appendix C of Approved Document B (‘Fire safety’). To count the number of storeys in a building, count only at the position which gives the greatest number.

Table 11 The number of fire-fighting shafts

[HTM 05-02 – PDF page 80]

should be provided within 15 m of a final exit, which itself is within 18 m of a suitable fire service access point.

7.12 If a fire-fighting shaft is required to serve a basement it need not also serve the upper floors unless they also qualify because of the height or size of building. Similarly, a shaft serving upper storeys need not serve a basement that is not large or deep enough to qualify in its own right; however, a fire-fighting stair and any fire-fighting lift should service all intermediate storeys between the highest and lowest storeys that they serve.

7.13 Fire-fighting shafts should serve all floors through which they pass.

7.19 All hospital streets should have fire main outlets located at department entrances so that every part of every storey is no more than 45 m from a fire outlet connection, measured along a route that is suitable for laying hose. Fire hoses may wedge open cross-corridor fire doors designed to prevent the passage of smoke along the corridor; to prevent this it is recommended that sections of the hospital street that provide access to a department should be provided with a fire main outlet within that section of a hospital street.

Design and construction of fire- fighting shafts

7.14 Fire-fighting stairways and lifts should be approached from inside the building through a fire-fighting lobby.

7.20 Where healthcare buildings with a hospital street have upper storeys over 18 m above fire service vehicle access level, or a basement at more than 10 m below ground or fire service vehicle access level, lifts for use by the fire- and-rescue service are required; these should be:

a. located within the hospital street

7.15 Fire-fighting shafts should be equipped with fire mains having outlet connections and valves in every fire-fighting lobby except at access level.

immediately adjacent to a stairway;

b. accessed directly off the hospital street;

7.16 Where fire-fighting shafts include fire- fighting lifts, a fire-fighting lift installation includes:

c. within 18 m of an entrance suitable for

use by the fire-and-rescue service.

a. the lift car itself;

b. the lift well; and

Note

c. the lift machinery space together with

the lift control system and the lift communications system.

The fire-and-rescue service should be consulted on any additional requirements they may have for the lift to be suitable for their use.

Fire mains

7.17 The shaft should be constructed generally in accordance with clauses 7 and 8 of BS 5588-5. Fire-fighting lift installations should conform to BS EN 81-72 and to BS EN 81-1 or BS EN 81-2 as appropriate for the particular type of lift.

7.21 A fire main should be located in every fire- fighting shaft (see Table 11) or as required by paragraphs 7.18–7.20.

Health buildings provided with a hospital street

7.22 In healthcare premises with a floor over 50 m above ground or access level, wet rising mains should be provided. Where fire mains are

7.18 Fire-fighting shafts are not required in health buildings provided with hospital streets. In these buildings a minimum of two stairways

[HTM 05-02 – PDF page 81]

7. Access and facilities for the fire-and-rescue service

Note

provided in healthcare premises that are lower than this, either wet or dry mains are suitable.

7.23 Wet or dry fire mains should be designed and installed in accordance with BS 9990:2006.

The above guidance ensures that adequate water supplies are provided for those buildings which are not constructed within easy access of public hydrants.

Provision of fire hydrants

Venting of basements

7.24 Where a building that has any compartment of 280 m2 or more is being erected more than 100 m from an existing fire hydrant, additional hydrants should be provided:

a. buildings provided with fire mains –

hydrants should be provided within 90 m of dry fire main inlets;

b. buildings not provided with fire mains –

7.27 In addition to the measures above, there may be a need in case of fire to remove heat and smoke from basements. In a fire involving a basement, the products of combustion tend to escape via stairways, making access difficult for the fire-and-rescue service. Venting can reduce this problem, improve visibility and lower temperatures, making access for the fire service less difficult.

hydrants should be provided within 90 m of an entry point of the building and not more than 90 m apart.

7.28 Smoke outlets provide a route for heat and smoke to escape to the open air from the basement level(s). They can also be used by the fire service to let cooler air into the basement.

7.25 Each fire hydrant should be clearly indicated by a plate, affixed nearby in a conspicuous position, in accordance with BS 3251.

7.29 Smoke outlets connected directly to the open air should be provided from every basement storey, except for any basement storey that:

a. has a floor area of less than 200 m2;

b. is not more than 3 m below the adjacent

ground level.

7.26 Where no piped water supply is available or there is insufficient pressure and flow in the water main, or an alternative arrangement is proposed, the alternative source of supply should be provided in accordance with the following recommendations:

a. a charged static water tank of at least

7.30 Smoke outlets should:

45,000 L capacity; or

a. be positioned at high level in the space

they serve;

b. a spring, river, canal or pond capable of

b. be evenly distributed around the

perimeter of the building;

providing or storing at least 45,000 L of water at all times of the year, to which access, space and a hard standing are available for a pumping appliance; or

c. discharge into the open air outside the

building.

c. any other means of providing a water

supply for fire-fighting operations considered appropriate by the fire-and- rescue authority.

7.31 In each basement compartment/sub- compartment, the combined cross-sectional area of all smoke outlets should be not less than 2.5% of the compartment/sub- compartment floor area.

[HTM 05-02 – PDF page 82]

Firecode – fire safety in the NHS: HTM 05-02: Guidance in support of functional provisions for healthcare premises

capable of handling gas temperatures of up to 300°C for not less than one hour. It should come into operation automatically on the activation of:

7.32 If the outlet terminates at a point that is not readily accessible, it should be kept unobstructed and covered with a metal grille or louvre.

a. the sprinkler system; and/or

b. the fire detection and alarm system.

7.33 If the outlet terminates at a point which is readily accessible, it may be covered by a suitably indicated panel or pavement light which can be broken out or opened.

Construction of outlet ducts and shafts

7.34 Outlets should not prejudice the use of escape routes.

7.37 Outlet ducts and shafts, including any bulkheads over them, should be enclosed in non-combustible fire-resisting construction.

Mechanical smoke extract

7.35 As an alternative to natural venting, providing the basement is fitted with a sprinkler system to BS EN 12845, a mechanical extract system may be provided.

7.38 Where there are natural smoke outlet shafts from different basement compartments of the same basement storey, or from different basement storeys, they should be separated from each other by non-combustible fire- resisting construction.

7.36 The air extraction system should provide at least 10 air changes per hour and be