HTM 05-02: 6. External fire spread
[HTM 05-02 – PDF page 69]
6. External fire spread
Requirement
a portion of the roof should provide some fire resistance to prevent the fire spreading through the roof to other parts of the same building in different compartments (see also paragraphs 6.12 and 6.13).
Chapter 6 provides guidance to comply with the following Requirement from Part B of Schedule 1 of the Building Regulations 2010.
Requirement
6.4 With the exception of unprotected areas, the minimum period of fire resistance provided by external walls should be as in Table 8.
External fire spread
B4
Height to the top floor Minimum period of fire resistance
Not more than 5 m 30 minutes
Over 5 m 60 minutes
Notes:
(1) The external walls of the building shall adequately resist the spread of fire over the walls and from one building to another, having regard to the height, use and position of the building.
1. The minimum period of fire resistance relates to integrity and load-bearing capacity. The minimum provision for insulation is 15 minutes unless the external wall is less than 1000 mm from a boundary or adjacent building, when the requirement for insulation should be the same as that for integrity and load- bearing capacity.
2. An external wall that is also an element of structure should comply with Table 5.
(2) The roof of the building shall adequately resist the spread of fire over the roof and from one building to another, having regard to the use and position of the building.
Table 8 Minimum period of fire resistance of external walls
Space separation
6.1 In certain circumstances it may be necessary for the external walls or roofs of a healthcare building to provide a period of fire resistance to prevent fire spreading to adjacent buildings or parts of the same building in different compartments.
6.5 In healthcare buildings up to 12 m in height, the maximum percentage of unprotected area in an external wall, in relation to the distance to adjacent compartments, buildings or boundaries, should be determined from the graph in Figure 20 (Figure 21 provides guidance on how to establish the relevant boundary, and Figure 22 provides guidance on establishing the notional boundary).
6.2 For walls, this requirement is determined by a combination of space separation between buildings and the amount of unprotected area within the walls.
6.6 In healthcare buildings over 12 m in height, the maximum percentage of unprotected area in an external wall, in relation to the distance to adjacent compartments, buildings or boundaries, should be determined from the
6.3 Generally, roofs are the topmost element of the building and as a consequence are not required to provide a period of fire resistance from below. However, where a low-level roof abuts an external wall of a patient-access area,
[HTM 05-02 – PDF page 70]
Distance between face of building and relevant boundary (m)
Notes: i. Figure 22 provides guidance on how to establish the relevant boundary
12.5
ii. a relevant boundary may also be a notional boundary between two buildings on the same site; Figure 23 provides guidance on establishing the notional boundary;
7.5
iii. where the building is fitted with sprinklers throughout, the distance to the relevant boundary may be halved subject to a minimum distance of 1000 mm being maintained.
2.5
Percentage of unprotected area
Figure 20 Permitted unprotected area – method of determining the amount of unprotected area in an external wall
For a boundary to be relevant it should:
a. coincide with; or
this boundary is less than 80o to side C and is therefore relevant to side C
b. be parallel to; or
c. be at an angle of not more than
80o to
the side of the building.
C
this boundary is parallel to and therefore relevant to side D B D
this boundary coincides with and is therefore relevant A to side B
this boundary is parallel to side A
but the centre line of a road, river, canal or railway may be a relevant boundary
Figure 21 Relevant boundary area
[HTM 05-02 – PDF page 71]
6. External fire spread
Notional boundary
Site boundary
Building A Building B
Compliance with the provisions for space separation in respect of building A
Compliance with the provisions for space separation in respect of building B
The notional boundary should be set in the area between the two buildings using the following rules:
1. The notional boundary is assumed to exist in the space between the buildings and is positioned so that one of the buildings would comply with the provisions for space separation having regard to the amount of its unprotected area. In practice, if one of the buildings is existing, the position of the boundary will be set by the space-separation factors for that building. 2. The siting of the new building, or the second building if both are new, can then be checked to see that it also complies, using the notional boundary as the relevant boundary for the second building.
For further information about notional boundaries, see paragraph 13.6 in Approved Document B.
Figure 22 Notional boundary
Note
methods set out in the BRE Report 187 – ‘External fire spread: building separation and boundary distances’.
6.7 When calculating the amount of unprotected area:
a. small unprotected areas as indicated in
The national classifications do not automatically equate with the equivalent European classifications; therefore, products cannot typically assume a European class unless they have been tested accordingly.
Figure 23 may be disregarded;
b. an external surface of combustible
6.10 When a classification includes “s3,d2”, this means that there is no limit set for smoke production and/or flaming droplets/particles.
material more than 1 mm thick should be counted as an unprotected area amounting to half the actual area of the combustible material.
Surfaces of roofs
Canopies
6.11 All healthcare buildings providing in-patient facilities or invasive procedures should have roof coverings complying with the Approved Document B.
6.8 Provided a canopy is more than 1 m from a relevant boundary, the provision for space separation may be disregarded.
Junction of walls and low-level roofs
Surfaces of external walls
6.9 The surfaces of external walls of healthcare premises should provide a surface spread of flame classification of Class 0 (European Class: B-s3,d2).
6.12 Where a roof abuts an external wall, the roof should provide a minimum period of fire resistance of 60 minutes (integrity and insulation) for a distance of 3 m from the wall (see Figure 24).
[HTM 05-02 – PDF page 72]
The unprotected area of the external wall of a stairway forming a protected shaft may be disregarded for separation distance purposes
Compartment floor
Compartment wall
Unprotected areas which may be disregarded for separation distance purposes
Dimensional restrictions
4 m minimum distance
Represents an unprotected area of not more than 1 m² which may consist of two or more smaller areas within an area of 1000 mm × 1000 mm
1500 mm minimum distance
Dimension unrestricted
Represents an area of not more than 0.1 m²
Figure 23 Unprotected areas which may be disregarded
3 m
Shaded area of low-level roof (including any rooflights) to provide a minimum period of fire resistance of 60 minutes (integrity and insulation)
External wall no fire resistance
Low-level roof (flat or pitched) with no fire resistance
Figure 24 Fire-resistance at junction of external walls and low-level roof
[HTM 05-02 – PDF page 73]
6. External fire spread
merit some departure from the usual measures to restrict the fire spread within buildings, specifically:
6.13 Where sprinklers are installed throughout the area below the low-level roof, paragraph 6.12 above does not apply.
• the fire load is well defined; and
Junction of compartment and sub- compartment walls and external walls
6.14 Where:
a. a compartment wall (or sub-
compartment wall) meets an external wall; or
b. a protected shaft meets an external wall,
• where the car park is well ventilated, there is a low probability of fire spread from one storey to another. Ventilation is the important factor and, as heat and smoke cannot be dissipated so readily from a car park that is not open-sided, fewer concessions are made. The guidance in paragraphs 6.19 to 6.24 below is concerned with three ventilation methods – open-sided (high level of natural ventilation), natural ventilation and mechanical ventilation.
a 1 m wide storey-height strip of external wall that has a similar period of fire resistance should be provided to prevent lateral fire spread (see Figure 25).
6.17 Not withstanding the recommendations of Table 1, where it is proposed to include car parking under any part of the healthcare premises, the following additional requirements should be provided.
6.15 Where sprinklers are installed on both sides of the compartment (or sub-compartment wall), paragraph 6.14 does not apply.
All car parks
Additional requirements for car parks
6.18 Access from the car park to a healthcare building should be through a protected lobby. In addition, vertical access from the car park to the building should be via a stairway or stairways, provided with protected lobbies,
6.16 Buildings or parts of buildings used as parking for cars and other light vehicles are unlike other buildings in certain respects which
compartment or subcompartment wall
External wall minimum 1000 mm in length
Plan
Minimum distance between openings 1000 mm measured on the diagonal compartment or subcompartment wall
Plan
Figure 25 Junction of compartment or sub-compartment wall and external wall
[HTM 05-02 – PDF page 74]
serving the car-park storeys and providing access to one storey only of the building.
park, if the finish meets all relevant aspects of the guidance requirements of Chapters 4 and 5 of this guidance.
Open-sided car parks
(ii) any fire door;
(iii) any attendant’s kiosk not
exceeding 15 m2 in area; and
(iv) any shop mobility facility.
6.19 If the building, or separated part containing the car park, complies with the following provisions, it may be regarded as an open- sided car park for the purposes of fire resistance assessment in Table A2 of Approved Document B – ‘Fire safety’. The provisions are that:
Car parks that are not open-sided
a. there should not be any basement
storeys;
b. each storey should be naturally
6.20 Where car parks do not have the standard of ventilation set out in paragraph 6.19, they are not regarded as open-sided and a different standard of fire resistance is necessary (the relevant provisions are given in Table A2 of Approved Document B). Such car parks still require some ventilation, which may be by natural or mechanical means, as described in paragraphs 6.21 or 6.22. The provisions of paragraph 6.19 apply to all car-park buildings, whatever standard of ventilation is provided.
Natural ventilation to car parks
ventilated by permanent openings at each car parking level, having an aggregate vent area not less than 1/20th of the floor area at that level, of which at least half (1/40th) should be equally provided between two opposing walls (where one element of structure supports or carries or gives stability to another, the fire resistance of the supporting element should be no less than the minimum period of fire resistance for the other element, whether that other element is load- bearing or not);
c. if the building is also used for any other
6.21 Where car parks that are not open-sided are provided with some, more limited, natural ventilation, each storey should be ventilated by permanent openings (which can be at ceiling level) at each car-parking level. These should have an aggregate free-vent area of not less than 1/40th of the floor area at that level, of which at least half should be split equally (1/160th on each side) and provided between two opposing walls (see Approved Document F – ‘Ventilation’ for additional guidance on normal ventilation of car parks).
purpose, the part forming the car park is a separated part and the fire resistance of any element of structure that supports or carries or gives stability to another element in the other part of the building should be no less than the minimum period of fire resistance for the elements it supports;
Mechanical ventilation to car parks
d. all materials used in the construction of
the building, compartment or separated part should be non-combustible, except for:
(i) any surface finish applied to a
6.22 In most basement car parks, and in enclosed car parks, it may not be possible to obtain the minimum standard of natural ventilation openings set out in paragraph 6.21. In such cases a system of mechanical ventilation should be provided as follows:
a. the system should be independent of
any other ventilating system (other than
floor or roof of the car park, or within any adjoining building, compartment or separated part of the structure enclosing the car
[HTM 05-02 – PDF page 75]
6. External fire spread
e. the fans should be rated to run at 300°C
for a minimum of 60 minutes, and the ductwork and fixings should be constructed of materials having a melting point not less than 800°C.
any system providing normal ventilation to the car park) and be designed to operate at 10 air changes per hour in a fire condition (see Approved Document F – ‘Ventilation’ for guidance on normal ventilation of car parks);
b. the system should be designed to
6.23 For further information on equipment for removing hot smoke, refer to BS EN 12101-3: 2002.
run in two parts, each part capable of extracting 50% of the rates set out in (a) above, and designed so that each part may operate singly or simultaneously;
c. each part of the system should have an
6.24 An alternative method of providing smoke ventilation from enclosed car parks is given in the BRE Report 368: ‘Design methodologies for smoke and heat exhaust ventilation’ and BS 7376-7:2006.
independent power supply that would operate in the event of failure of the main supply;
d. extract points should be arranged so
that 50% of the outlets are at high level and 50% at low level;