Home › England (NHS England estates) › HTM 05-02 › 5. Internal fire spread (structure)

HTM 05-02: 5. Internal fire spread (structure)

Firecode - Guidance in support of functional provisions (Fire safety in the design of healthcare premises) · PDF pages 54–68 of 112 · Source file: HTM_05-02_2015.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 05-02 – PDF page 54]

5. Internal fire spread (structure)

Requirement

Chapter 5 provides guidance to comply with the following Requirement from Part B of Schedule 1 of the Building Regulations 2010.

Requirement

Internal fire spread (structure)

B3

(1) The building shall be designed and constructed so that, in the event of fire, its stability will be maintained for a reasonable period.

(2) A wall common to two or more buildings shall be designed and constructed so that it adequately resists the spread of fire between those buildings. For the purposes of this sub- paragraph a house in a terrace and a semi-detached house are each to be treated as a separate building.

(3) Where reasonably necessary to inhibit the spread of fire within a building, measures shall be taken, to an extent appropriate to the size and intended use of the building, comprising either or both of the following:

a. sub-division of the building with fire-resisting construction;

b. installation of suitable automatic fire suppression systems.

(4) The building shall be designed and constructed so that unseen spread of fire and smoke within concealed spaces in its structure and fabric is inhibited.

a. resistance to collapse; that is, the ability

Elements of structure

to maintain load-bearing capacity (which applies to load-bearing elements only);

b. resistance to fire penetration; that is, an

5.1 The fire resistance of an element of construction is a measure of its ability to withstand the effects of fire in one or more ways, as follows:

ability to maintain the integrity of the element; and

[HTM 05-02 – PDF page 55]

5. Internal fire spread (structure)

c. resistance to the transfer of excessive

heat; that is, an ability to provide insulation from high temperatures.

5.4 Roof structure and structure that only supports a roof may not require fire-resistance for life safety purposes unless:

a. the stability of the building depends on

the roof; or

b. the roof serves as a floor, for example a

rooftop car park or plantroom; or

c. the roof is used as an escape route.

5.2 To prevent the premature failure of the structure, the load-bearing elements of the building are required to have a minimum period of fire resistance in terms of resistance to collapse or failure of load-bearing capacity. The purpose of providing the structure with fire resistance is to:

a. minimise the risk to the occupants,

5.5 The minimum period of fire resistance provided by the elements of structure should be as in Table 5.

many of whom may still be in a temporary place of safety within the building awaiting evacuation;

b. reduce the risk to fire-fighters; and

c. reduce the danger to people in the

vicinity of the building.

5.6 Reductions in periods of fire resistance are permitted only where sprinklers are installed throughout the building. Partial sprinkler coverage will not provide the same extent of protection for structural elements.

5.3 For the purposes of this document, elements of structure are:

a. a column, beam, or other member

forming part of a structural frame;

b. a load-bearing wall;

5.7 Partial sprinkler protection can help mitigate localised fire risks in a building and therefore may offer other benefits for the design. A fire engineer should be consulted on a solution that provides enhancements based on partial sprinkler coverage which should be supported by fire engineering evidence.

c. a floor.

Minimum period of fire resistance provided by elements

of structure

Unsprinklered Sprinklered

Single-storey healthcare buildings 30 minutes 30 minutes

60 minutes 30 minutes* (60 minutes in respect of basements*)

Healthcare buildings with storeys up to 12 m above ground or basements no more than 10 m deep

90 minutes 60 minutes*

Healthcare buildings with storeys over 12 m above ground or basements more than 10 m deep

Healthcare buildings with storeys over 30 m Not permitted 90 minutes*

Notes:

* The reduction in fire resistance is conditional upon a life safety sprinkler system installed and maintained in line with BS EN 12845.

Elements of structure in relation to basements include the ground-floor slab.

Where one side of a basement is (due to the slope of the ground) open at ground level, giving an opportunity for smoke venting and access for fire-fighting, it may be appropriate to adopt the standard of fire resistance applicable to above-ground structures for elements of structure in that storey.

In order to reduce the fire resistance to elements of structure, the whole building must be protected by a sprinkler installation design.

Table 5 Fire resistance of elements of structure

[HTM 05-02 – PDF page 56]

Compartmentation

Materials used to meet this provision can be found in the Glossary (Appendix A) under “Material of limited combustibility”.

5.15 Where sprinklers are installed throughout the whole building, the requirement for elements of structure and compartment walls to be constructed of materials of limited combustibility does not apply.

5.8 The requirement for compartmentation is discussed in Chapters 2 and 3. Within patient- access areas, compartmentation is used to divide a storey into places of temporary safety which may be used for refuge. In addition, compartmentation prevents rapid fire spread throughout the building and reduces the likelihood of large fires.

Openings in compartment walls and floors

5.9 For buildings more than one storey in height, all floors should be compartment floors.

5.16 All openings in floors and compartment walls should be protected to provide at least the same period of fire resistance as the compartment structure.

5.10 In healthcare premises, the maximum size of a compartment is generally determined by its use; it is strongly recommended that the size of the management department determines the size of a compartment (see paragraph 3.22).

5.17 To maintain the integrity of compartmentation, openings should be limited to:

a. doors which have a period of fire

5.11 The maximum area of a compartment should not exceed:

• 2000 m2 in a multi-storey building;

resistance not less than that of the compartment structure (that is, integrity performance);

• 3000 m2 in a single-storey building.

b. openings for pipes of not more than

5.12 The minimum period of fire resistance (integrity and insulation) provided by compartment walls should be:

a. for single-storey healthcare buildings –

160 mm diameter which, if exposed to a temperature of 800ºC, will not soften or fracture to the extent that flames or hot gases will pass through the wall of the pipe;

30 minutes (except where this conflicts with the requirements of Table 5); or

c. pipes of materials other than those in (b)

b. for all sprinklered healthcare buildings

above of not more than 40 mm diameter;

– 30 minutes; or

d. pipes of any diameter that are provided

c. for all other healthcare buildings –

with a proprietary seal which has been shown by test (for the diameter of pipe proposed) to maintain the fire resistance of the compartment structure;

60 minutes, including those with basements more than 10 m deep and those four storeys or more above ground level.

e. ventilation ducts that comply with the

requirements of BS 5588-9 (see Figure 16);

5.13 All compartment floors are considered as elements of structure and should satisfy the requirements of Table 5.

Elements of structure and compartment walls

f. refuse and laundry chutes of non- combustible construction that are accessed through fire-resisting doors; and

g. protected shafts.

5.14 Elements of structure and compartment walls are required to meet the above provisions.

[HTM 05-02 – PDF page 57]

5. Internal fire spread (structure)

Junction of compartment walls with roofs

Glazing in sub-compartment walls

5.23 Uninsulated fire-resisting glazed screens may only be provided in sub-compartment walls provided they satisfy the following requirements:

5.18 Compartment walls should be taken up to the underside of the roof covering or deck, and fire-stopped to maintain the fire resistance. The compartment wall should also be continued across any eaves cavity.

a. the glazing should provide a minimum

period of 30 minutes’ fire resistance (integrity only);

b. the area of integrity-only glazing should

be limited to a maximum of 1 m2 in any room.

5.19 A zone of the roof 1.5 m wide on either side of the wall should have a covering of designation AA, AB or AC (see Approved Document B, Appendix A, paragraph 6) on a substrate or deck of a material of limited combustibility.

Note

5.24 There is no limit on the use of glazed screens that provide a minimum period of fire resistance of 30 minutes (integrity and insulation).

Double-skinned insulated roof sheeting, with a thermoplastic core, should incorporate a band of material of limited combustibility at least 300 mm wide centred over the wall.

5.25 Where sprinklers are fitted, there is no limit on the use of glazed screens that provide a minimum period of fire resistance of 30 minutes (integrity only), provided the glass is not of the type referred to as “modified toughened”.

Protected shafts

5.20 As an alternative to paragraphs 5.18 and 5.19 the compartment wall may be extended up through the roof for a height of at least 375 mm above the top surface of the adjoining roof covering.

Glazing in a compartment wall

5.26 Openings in floors for stairways, lifts, escalators, and pipes and ducts not complying with paragraph 5.17 should be enclosed in a protected shaft that has the same period of fire resistance (integrity, insulation and, where applicable, load-bearing capacity) as the compartment floor (see Figure 13).

5.21 Any glazing provided in a compartment wall should have the same period of fire resistance (integrity and insulation) as the compartment wall. Glazing should have a permanent, legible mark giving the manufacturer, product name, fire-resistance rating and any requirement for impact safety performance according to BS 6206 or BS EN 12600.

Sub-compartment walls

Openings in sub-compartment walls

5.27 The protected shaft should form a complete barrier to fire between different compartments to which the shaft connects and should be constructed from materials of limited combustibility. Where services (pipes, cables, ducts etc) are required to pass through the enclosing structure they should be adequately fire-stopped to maintain the fire resistance of the protected shaft. Where pipes are required to pass through the enclosing structure, they should be designed in accordance with Figure 14.

5.22 All openings in sub-compartment walls should be protected to provide a minimum period of fire resistance of 30 minutes.

5.28 Any internal glazing provided to a protected shaft should have the same period of

[HTM 05-02 – PDF page 58]

Compartment wall

Door Door Door Door External wall

Protected shaft A bounded on three sides by compartment walls and on fourth side by an external wall

Protected shaft C a services duct bounded on four sides by compartment walls Protected shaft B bounded on four sides by compartment walls

Note: The protected shaft should meet the relevant provisions for compartment walls

Figure 13 Protected shafts

Structure

Not less than

1000 mm Not less than

1000 mm

Pipe specification (b) Sleeve (or pipe) of specification (a) to be in contact with pipe

Pipe material and maximum nominal internal diameter (mm)

(c) Any other material

(a) Non- combustible material1

(b) Lead, aluminium, aluminium alloy, uPVC2, fibre cement

Structure enclosing a protected shaft which is not a stairway or lift shaft

Any other situation

Notes: 1. Any non-combustible material (such as cast iron, copper or steel) which, if exposed to a temperature of 800°C, will not soften or fracture to the extent that flame or hot gas will pass through the wall of the pipe. 2. uPVC pipes complying with BS 4514 and uPVC pipes complying with BS 5255.

Figure 14 Pipes penetrating fire-resisting structure

[HTM 05-02 – PDF page 59]

5. Internal fire spread (structure)

fire resistance (integrity and insulation) as the protected shaft.

mechanism of a hydraulic lift and ventilation ductwork provided for the purposes of pressurising the stairway.

5.29 The use of roof lights over protected shafts used for stairways should be limited to those that provide a Class 1 surface spread of flame on both upper and lower surfaces.

5.33 Protected shafts containing a stairway should be provided with an opening window, or similar, providing a clear ventilation area of 1 m2.

Protected lobbies

5.30 The use of protected shafts should be limited to:

a. stairways;

b. lifts;

5.34 Protected shafts for stairways and lifts should be provided with protected lobbies except where they are accessed from a hospital street.

c. escalators;

d. chutes;

e. ducts;

f. pipes.

5.35 Protected lobbies should not be located so that they form part of a through route; that is, they should not be located across a corridor if the corridor continues beyond the protected lobby (see Figure 15).

5.31 No accommodation should be included within protected shafts.

5.36 Guidance on the recommended dimensions for internal lobbies is provided in Health Building Note 00-04 – ‘Circulation and communication spaces’. This recommends that where swing doors are used, a minimum clear

5.32 Pipes conveying oil or gas and ventilation ductwork should not be located in the same protected shaft as a stairway or lift – except pipes conveying oil as part of the operating

ii. stairway accessed from a hospital street (protected lobby not required)

i. stairway accessed from a circulation space (protected lobby required)

FD30S

Protected

lobby

FD30S

FD30S

Hospital street

Circulation space

Figure 15 Protected lobbies to stairways

[HTM 05-02 – PDF page 60]

length (that is clear of the furthest point that door(s) will swing into) is provided of:

a. 1.570 m for general traffic access; and

b. 4.100 m for bed/trolley access.

5.41 Table 6 gives examples of fire hazard rooms. The list is not exhaustive, and the onus rests with the designer to assess the fire risk associated with all rooms to determine the need to enclose in fire-resisting construction.

5.37 Protected lobbies should:

Chemical stores Store rooms

Cleaners’ room Relatives’ overnight stay room

a. be constructed from materials of limited

Clothes storage Ward kitchens

combustibility and have the same fire resistance as the protected shaft; and

Disposal rooms Communal bathrooms in mental health premises (see paragraph 2.52)

b. contain no other accommodation except

Hub rooms Linen stores

that allowed for protected shafts.

Lift motor rooms Staff on-call rooms

Main staff changing and locker rooms

Patient bedrooms provided specifically for:

Fire stopping

• people with mental health needs

• people with learning disabilities

Key

Doors to these rooms to be kept locked shut

5.38 In addition to any other provisions in this document for fire-stopping, joints between fire- separating elements should be fire-stopped and all openings for pipes, ducts, conduits or cables to pass through any part of fire- separating elements should be:

Door to be fitted with appropriately designed free-swing self-closing devices

a. kept as few in number as possible;

Doors to be fitted with self-closing devices

Self-closing devices not required.

b. kept as small as practicable; and

c. fire-stopped (which in the case of a pipe

Table 6 Examples of fire hazard rooms

or duct, should allow thermal movement).

5.42 Fire hazard rooms and areas should be enclosed in 30 minutes’ fire-resisting construction (integrity and insulation). Walls may be terminated at ceiling level provided that:

a. the ceiling is non-demountable and has

5.39 Guidance on the process of design, installation and maintenance of passive fire protection is available in ‘Ensuring best practice for passive fire protection in buildings’ (ISBN: 1 87040 919 1) produced by the Association for Specialist Fire Protection (ASFP).

a minimum period of fire resistance of 30 minutes when tested (complete with any lighting units) from below in accordance with BS 476 (Parts 20 and 22);

Fire hazard rooms and areas

b. ducts perforating the ceiling are fitted

with fire dampers;

c. conduits, pipes etc perforating the

ceiling are fire-stopped and comply with the requirements of paragraph 5.27.

5.43 Where sprinklers are installed, the need to enclose fire hazard rooms in fire-resisting construction should be risk-assessed.

5.40 For most building types, it is normally required to protect escape routes with fire- resisting walls, ceilings and doors (protected corridors). In healthcare premises this is not considered acceptable, since the excessive number of fire-resisting doors, all fitted with self-closing devices, would be a hindrance to staff and patients during the everyday running of a healthcare building. For this reason, the technique advocated for healthcare buildings is to identify and segregate fire hazard rooms by at least 30 minutes’ fire-resisting construction.

[HTM 05-02 – PDF page 61]

5. Internal fire spread (structure)

Glazed screens

Location and operation of fire and smoke dampers and fire dampers

5.44 Uninsulated glazed screens should not be provided to fire hazard rooms; however, there is no limit on the use of glazed screens that provide a minimum period of fire resistance of 30 minutes when tested to the relevant parts of BS 476 (integrity and insulation) or BS EN 12600.

5.49 Ventilation ducts should maintain the period of fire resistance of the construction through which they pass; this includes but is not limited to fire hazard rooms, sub- compartments, compartments, cavity barriers and protected shafts.

Ventilation systems

5.50 The type of dampers permitted in each form of construction is indicated in Table 7.

5.45 Mechanical ventilation is used extensively in healthcare premises, including specialist systems for primary patient treatment in operating departments, critical care areas and isolation rooms. It is also installed to ensure compliance with quality assurance of manufactured items in pharmacy and sterile services departments and to protect staff from harmful organisms and toxic substances (for example in laboratories).

5.51 All dampers should be installed in accordance with the manufacturer’s tested details so that they maintain their integrity against the passage of fire for the required period of fire resistance. They should be adequately fixed into, or to, the construction they are protecting. A damper that is supported only by the ductwork in which it is located, or by timber battens, frames or other methods that do not provide the fire resistance required, is not acceptable.

5.46 In the event of a fire, large quantities of smoke and toxic gases can be given off, which potentially could be transferred through the ductwork to rooms and areas remote from the fire. Therefore, measures are required to:

a. limit the spread of fire, smoke and other

products of combustion within the ductwork between protected areas;

b. prevent a breach in the integrity of an

5.52 Dampers provided in 30-minute fire- resisting ceilings should be adequately supported either by the ceiling or from the structural soffit. In the ceiling situation, it is also essential to ensure that the integrity of the fire- resisting ceiling is maintained. It is not acceptable to form an opening, install a diffuser or grille and fit a damper above if the gap between the ceiling opening and the damper does not achieve 30 minutes’ fire resistance.

enclosing fire-resisting element of construction where penetrated by ductwork.

5.47 Ventilation systems should be designed and installed to comply with Health Technical Memorandum 03-01 – ‘Specialised ventilation for healthcare premises’ and BS 5588-9.

5.53 Where, due to the specialist nature of the ventilation system, the inclusion of dampers is not recommended, fire rated ductwork will be required. This would typically occur with the provision of fume cupboards, isolation rooms and kitchen extract systems, for example. The fire rated ductwork should meet the same performance requirements of the elements through which it passes and should be installed in accordance with the manufacturer’s tested detail.

5.48 Ventilation systems should not be common to both patient areas and hazard departments. Fresh-air intakes should be positioned to avoid the possibility of the intake of smoke and toxic gases.

[HTM 05-02 – PDF page 62]

Fire and smoke damper

Fire damper (Thermal

Air transfer grille – cold

activated by AFD

activation)

smoke (activated by

Air transfer grille (thermal activation)

AFD)

Compartment floor X X X

Compartment wall X X X

Protected shaft X X X

Sub-compartment wall X X X

Cavity barrier N/A N/A

Fire hazard room X

Door to fire hazard rooms N/A N/A X

Doors in sub- compartment walls N/A N/A X

Doors in compartment walls N/A N/A X X

Doors to protected shafts N/A N/A X X

Notes:

Fire smoke dampers and air transfer grilles activated by the fire alarm provide more responsive containment than thermally activated devices and are considered preferable.

Air transfer grilles should not be fitted in fire doors unless accompanied by a test certificate provided by the door manufacturer.

Table 7 Permissible locations of transfer grilles, fire dampers, and fire and smoke dampers

Fire-resisting wall

Fire stopping

Ductwork

Fire damper

Actuation of dampers: i) in accordance with BS5588: Part 9; ii) by the operation of the detection and alarm system either side of the compartment or sub-compartment wall; or iii) by operation of fusible link in walls to fire hazard rooms

Figure 16 Fire and smoke damper in compartment, sub-compartment wall or wall to fire hazard room

[HTM 05-02 – PDF page 63]

5. Internal fire spread (structure)

5.54 Ductwork passing through, or over, hazard rooms should be provided with fire dampers in accordance with Figure 17.

i. ductwork passing through but not serving fire hazard room

30-minute fire- 30-minute fire- resisting wall resisting wall

Ductwork

Fire Fire stopping stopping

Fire hazard room

i. fire dampers not required;

ii. ductwork in the hazard room to have 30 minutes’ fire resistance (integrity and insulation) when tested to the relevant parts of BS 476.

ii. ductwork passing over fire hazard room fitted with fire-resisting ceiling

Ductwork

Fire-resisting ceiling

30-minute fire- 30-minute fire- resisting wall resisting wall

Fire hazard room

i. fire dampers not required;

ii. ceiling to be non-demountable and have a minimum period of fire resistance of 30 minutes, when tested (complete with any lighting units) from below in accordance with BS 476 Parts 20 and 22.

iii. ductwork serving fire hazard rooms

Supply ductwork

Fire damper

i. ducts should not pass through the hazard room if the duct serves the fire hazard room and other rooms beyond the fire hazard room;

Fire hazard Other room room

ii. the fire hazard room should be served by spurs fitted with fire dampers operated by fusible links;

Fire damper

Extract ductwork

iii. where flexible connections are used, they should comply with BS 5588-9 and not pass through the fire- resisting walls

Figure 17 Options for the design of ductwork passing through or serving a fire hazard room

[HTM 05-02 – PDF page 64]

5.61 Guidance on the construction and fixing of cavity barriers is provided in Appendix E.

5.55 Where ventilation systems utilise air transfer grilles, Table 7 indicates the types of air transfer grille permitted in the different forms of construction.

5.56 The fire resistance may be achieved by the ductwork material itself, or through the application of a protective material.

Operation of ventilation plant

5.62 With the exception of the ceiling void above operating departments (see paragraph 5.66), 30-minute fire-resisting barriers should be provided to subdivide concealed roof or ceiling voids, so that the maximum dimension of uninterrupted roof or ceiling void should not exceed 20 m. Wherever possible, cavity barriers should be positioned to coincide with fire-resisting walls.

5.63 Thirty-minute fire-resisting cavity barriers should also be provided:

a. to prevent the interconnection of vertical

and horizontal cavities;

b. at the intersection of fire-resisting

construction and elements containing a concealed space;

c. within the void behind the external face

5.57 The ventilation plant should not necessarily automatically shut down on the operation of the automatic fire detection and alarm system. For example, in areas where the automatic shutdown of ventilation plant will impede the clean air-flow paths and room-air dilution rates, this may lead to an increased risk of healthcare-associated infections. Where, due to operational reasons, the ventilation plant continues to run, override facilities will be required and the shutdown of the system should be controlled from panels located either at department entrances or adjacent to the main fire alarm indicator panels.

of rain-screen cladding, at every floor level and on the line of compartment walls abutting the external wall.

Cavity barriers

5.64 Cavity barriers should not be provided:

a. in cavity walls, as illustrated in Figure 18;

or

b. in double-skinned insulated roof

sheeting, as illustrated in Figure 19; or

c. below a floor next to the ground or

oversite concrete providing:

5.58 Concealed spaces or cavities in the construction of a building may permit the rapid spread of fire and smoke. It is possible for fire and smoke to be transferred to areas remote from the seat of the fire by way of uninterrupted concealed spaces. For this reason, it is essential that fire-resisting barriers are provided to restrict the size of these concealed spaces.

(i) the cavity is less than 1000 mm in

height; or

(ii) it is not accessible by persons; and

(iii) there are no openings in the floor

such that it is possible for combustibles to accumulate in the cavity.

5.59 In healthcare premises, the subdivision provided through the requirements for hazard protection, sub-compartmentation and compartmentation is such that generally the additional subdivision of ceiling voids for cavity barriers is not required. The exception to this is where sub-compartment walls and walls to fire hazard rooms are terminated at 30-minute fire- resisting ceilings.

5.65 Openings in barriers should be limited to those for:

a. doors which have at least 30 minutes’

5.60 Irrespective of the above, there is a requirement to prevent the interconnection of horizontal and vertical cavities.

fire resistance;

[HTM 05-02 – PDF page 65]

5. Internal fire spread (structure)

Section through cavity wall

Close cavity at top of wall (unless cavity is totally filled with insulation)

Opening Close cavity around opening

Two leaves of brick or concrete each at least 75 mm thick

Note: Combustible materials should not be placed in or exposed to the cavity, except for:

a. timber lintels, window or door frames, or the ends of timber joists; b. pipes, conduit or cable; c. DPC, flashing cavity closer or wall tie; d. thermal insulating material (two leaves of brick, block or concrete each at least 75 mm thick, 100 mm maximum cavity width)

Figure 18 Cavity wall not requiring a cavity barrier

i. acceptable without cavity barriers

The insulation should make contact with both skins of sheeting

ii. cavity barriers required

Figure 19 Cavity barriers in double-skinned insulated roof sheeting

[HTM 05-02 – PDF page 66]

b. pipes (see paragraph 5.32);

e. be beneficial in terms of business

continuity.

c. cables or conduits;

d. openings fitted with a suitably mounted

automatic fire and smoke damper (see Table 7);

5.70 The control of a fire at an early stage extends the time available to evacuate and enhances the protection provided to adjoining places of temporary safety.

e. ducts which, unless they are fire-

resisting, are fitted with a suitably mounted automatic fire damper where they pass through the cavity barrier.

5.71 An extended evacuation time will help where staff numbers are limited or where the attendance of additional responding staff may be delayed.

Cavity barriers above operating departments

5.72 The control of a fire can reduce the need for onward phases of evacuation. This will benefit very high dependency patients and help maintain continuity of care.

5.66 The complexities of ventilation ductwork systems above operating departments mean that the provision of cavity barriers may seriously compromise service access and means of escape for maintenance staff. Therefore cavity barriers should not be provided over operating departments.

5.67 Additionally, operating departments have restricted access and are well supervised when in use, and hazard areas are enclosed within fire-resisting construction.

5.73 For premises providing care only for independent patients, the inclusion of sprinklers may support the use of smoke-retarding construction as an alternative to 30 minutes’ fire-resisting construction. Any solution adopting this approach should be fully supported by fire engineering evidence to demonstrate that an equivalent level of safety will be maintained as with a standard HTM- compliant design solution.

Sprinklers

5.74 To avoid conflict, the AFD zoning arrangements should take precedence over the sprinkler system, including in the cause and effect.

5.75 Life-safety systems are defined in BS EN 12845 as “sprinkler systems forming an integral part of measures required for the protection of life”.

5.68 With the exception of buildings over 30 m in height, the guidance in this document does not require the installation of sprinklers in patient care areas of healthcare buildings. However, the design team is expected to consider the advantages that might be gained by installing life-safety sprinklers throughout the building or to specific areas. Where specific hazards are identified in the building, it may be more appropriate to consider the application of an alternative fire suppression system, such as high pressure water mist technologies.

5.69 Life-safety sprinklers will:

a. limit the size of a fire;

5.76 The performance of life-safety sprinklers can be enhanced by the specification and installation of quick-response sprinkler heads that enable the activation of the system quickly after the heads have reached their operating temperature. This response is quicker than conventional heads that have been developed for property protection.

b. control fire spread;

c. provide additional time to evacuate;

5.77 Where a sprinkler system is specifically recommended within this document, it should

d. limit fire damage; and

[HTM 05-02 – PDF page 67]

5. Internal fire spread (structure)

specified minimum water volume of a single full capacity tank, as appropriate to the hazard; or

be provided in the building or separated part and designed and installed in accordance with either:

a. the requirements of BS 5306-2,

(iv) one tank should be equivalent to

including the relevant hazard classification together with the additional requirements for life safety; or

b. the requirements of BS EN 12845,

half the specified water volume of a single full capacity tank and the other should not be less than half the minimum volume of a reduced capacity tank (see BS 5306-2, Table 25), as appropriate to the hazard.

including the relevant hazard classification together with the special requirements for life safety systems.

Note

Note

Any sprinkler system installed to satisfy the requirements of this Health Technical Memorandum or Part B of the Building Regulations should be regarded as a life- safety system. However, there may be some circumstances where a particular life-safety requirement specified in BS 5306-2 or BS EN 12845 is inappropriate or unnecessary.

The requirement for inflow should be met. Whichever water storage arrangement is used at (iii) or (iv) above, the total design capacity of the water supply, including any inflow for a reduced capacity tank, should be at least equivalent to a single full capacity tank complying with Tables 21–24 of BS 5306-2, as appropriate to the hazard and pipework design.

5.78 Water supplies for non-residential sprinkler systems should consist of either:

Systems designed and installed to BS EN

a. systems designed and installed to

BS 5306-2; or

5.80 These systems consist of either:

a. two single water supplies complying

b. systems designed and installed to

BS EN 12845.

with BS EN 12845, clause 9.6.1, where each is independent of the other; or

5.79 These systems consist of either:

b. two stored water supplies, where:

a. two single water supplies complying

(i) gravity or suction tanks should

with BS 5306-2, clause 13.1.2, where each is independent of the other; or

satisfy the all requirements of BS EN 12845, clause 9.6.2 b) other than capacity; and

b. two stored water supplies, where:

(ii) any pump arrangements should

(i) gravity or suction tanks should

comply with BS EN 12845, clause 10.2; and

be either Type A, Type D or their equivalent (see BS 5306-2, clause 17.4.11.6); and

(iii) the capacity of each tank is

(ii) any pump arrangements should

comply with BS 5306-2, clause 17.4.1.5; and

equivalent to half the specified minimum water volume of a single full capacity tank, as appropriate to the hazard; or

(iii) the capacity of each tank should

be equivalent to at least half the

[HTM 05-02 – PDF page 68]

(iv) one tank should be at least

Effect on other fire precautions

equivalent to half the specified water volume of a single full capacity tank and the other should not be less than the minimum volume of a reduced capacity tank (see BS EN 12845, clause 9.3.40), as appropriate to the hazard.

Note

5.85 In those parts of healthcare buildings where sprinkler systems are provided, the effect of sprinklers on the overall package of fire precautions has to be considered to ensure that a cost-effective fire safety strategy is provided. Where sprinklers are installed in healthcare premises in accordance with the above guidance, some of the requirements of this document may be modified to take account of the effect of sprinkler operation at an early stage of fire development.

5.86 Where sprinklers are installed, the guidance may be modified subject to a suitable and sufficient risk assessment being undertaken and the information being recorded in the fire safety manual. Examples include:

a. progressive horizontal evacuation

The requirements for inflow should be met. Whichever water storage arrangement is used at (iii) or (iv) above, the total capacity of the water supply, including any inflow for a reduced capacity tank, should be at least equivalent to a single full capacity tank complying with BS EN 12845, Tables 9 and 10 or clause 9.3.2.3, as appropriate to the hazard and pipework design.

(paragraphs 3.6–3.15);

b. glazing in sub-compartment walls

(paragraphs 5.23–5.25);

c. elements of structure (paragraphs 5.1–

5.7 and 5.14–5.15);

5.81 Where pumps are used to draw water from two tanks, each pump should be arranged to draw water from either tank and so that any one pump or either tank could be isolated.

d. compartmentation (paragraphs 5.8–

5.13);

e. fire hazard rooms and areas

5.82 The sprinkler water supplies should generally not be used as connections for other services or other fixed fire-fighting systems.

(paragraphs 5.40–5.44);

f. external fire spread (paragraphs 6.5– 6.15);

g. number and location of fire-fighting

5.83 In patient-access areas of healthcare premises, the sprinkler system should be a life- safety system, fitted with quick-response heads as defined in the Fire Protection Association’s ‘LPC rules for automatic sprinkler installations’.

shafts (paragraphs 7.11 and 7.13).

5.84 Areas of the building not provided with sprinkler protection should be separated from those areas that are protected, by the provision of 60-minute fire-resisting structure (integrity and insulation).