Home › England (NHS England estates) › HTM 05-02 › 4. Internal fire spread (linings)

HTM 05-02: 4. Internal fire spread (linings)

Firecode - Guidance in support of functional provisions (Fire safety in the design of healthcare premises) · PDF pages 51–53 of 112 · Source file: HTM_05-02_2015.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 05-02 – PDF page 51]

4. Internal fire spread (linings)

Requirement

Chapter 4 provides guidance to comply with the following Requirement from Part B of Schedule 1 of the Building Regulations 2010.

Requirement

Internal fire spread (linings)

B2

(1) To inhibit the spread of fire within the building, the internal linings shall:

a. adequately resist the spread of flame over their surfaces; and

b. have, if ignited, a rate of heat release of a rate of fire growth which is reasonable in the

circumstances.

(2) In this paragraph “internal linings” means the materials or products used in lining any partition, wall, ceiling or other internal surface.

4.3 Wall and ceiling finishes should meet the classifications in Table 4.

Roof lights

4.1 The surface finish applied to walls and ceilings can contribute to the spread of a fire. Some finishes will rapidly propagate the development of fire by “surface spread of flame”. This not only makes the fire difficult to control, but also provides additional fuel, which will increase the severity of the fire.

4.4 Roof lights should also meet the requirements of Table 4.

4.2 Surface finishes that can be effectively tested for “surface spread of flame” are rated for performance by reference to the method specified in Table 4 below.

4.5 However, plastic roof lights with a Class 3 rating for surface spread of flame may be used, provided that the limitations imposed by paragraph 4.9 are observed.

[HTM 05-02 – PDF page 52]

Location National classification European class

Small rooms (not more than 4 m2) C-s3,d2

Circulation spaces B-s3,d2

Other rooms B-s3,d2

Notes:

The limitations on surface finishes do not apply to:

a. demountable sanitary “back panels” commonly used in health premises to provide access for maintenance behind washbasins,

toilets, showers etc; and

b. rooms providing a specialist function (for example audiology booths) where other functional criteria dictate the surface finish.

The national classifications do not automatically equate with the equivalent classifications in the European column; therefore, products cannot typically assume a European class unless they have been tested accordingly.

When a classification includes “s3,d2”, this means that there is no limit set for smoke production and/or flaming droplets/particles.

Table 4 Classification of linings

a. the maximum area of each diffuser or

Thermoplastic materials

roof light;

b. the maximum total area of diffusers and

roof lights;

c. the minimum separation between

diffusers and roof lights.

4.6 Thermoplastic materials (see Appendix D) that cannot meet the performance requirements given in Table 4 may be used in roof lights and lighting diffusers in suspended ceilings if they comply with the requirements in paragraphs 4.10 and 4.12.

4.9 Thermoplastic roof lights and lighting diffusers with a classification of lower surface TP(b) (see Appendix D) and roof lights with a Class 3 rating may be used in all areas, with the following restrictions:

4.7 The guidance on the use of thermoplastic lighting diffusers applies irrespective of whether the lighting diffuser forms part of the ceiling or is attached to the soffit of, or suspended beneath, a ceiling (see Figure 11).

a. the maximum area of each diffuser or

roof light should be no more than 5m2;

a. Diffuser forming part of ceiling

b. the maximum total area of diffusers and

Ceiling

roof lights, as a percentage of the floor area of the space in which they are located, should be no more than 15%;

b. Diffuser in fitting below, and not forming part of, ceiling

c. the minimum distance between roof

Ceiling

lights should be not less than 3 m (see Figure 12).

Figure 11 Lighting diffuser in relation to ceiling

4.10 Thermoplastic roof lights with a classification of upper surface TP(b) should not be used.

4.8 Thermoplastic roof lights and lighting diffusers with a classification of lower surface of TP(a) (see Appendix D) may be used in all locations, except stairways, with no restrictions on:

4.11 Thermoplastic lighting diffusers should not be used in a fire-resisting ceiling unless they have been satisfactorily tested as part of a ceiling assembly that provides the appropriate fire protection.

[HTM 05-02 – PDF page 53]

4. Internal fire spread (linings)

4.12 The minimum distance from a relevant boundary of thermoplastic roof lights with a classification of upper surface of TP(a) should be not less than 6 m.

5 m maximum dimension of group of panels

5 m max.

3 m minimum

5 m² is maximum area of diffuser or rooflight in any

one 5 m × 5 m group

5 m max.

Key

3 m minimum dimension between groups of panels Panel of diffuser or rooflight

Separated groups of panels or rooflights

Notes: a. Upper and lower surface of suspended ceiling, between plastic panels, to comply with paragraph 6.1 in Approved Document B. b. No restriction on Class 3 roof lights in small rooms.

Figure 12 Layout restrictions on Class 3 rooflights, TP(b) rooflights and TP(b) lighting diffusers