HTM 05-02: 3. Means of warning and escape – Emergency and escape lighting / 3. Means of warning and escape – Security
[HTM 05-02 – PDF page 49]
3. Means of warning and escape
3.73 If practical, plantrooms should be sub- compartmented to separate essential services (for example power and ventilation) serving very high dependency areas from other plant equipment and machinery (for example lift motors, maintenance areas etc).
Emergency and escape lighting
3.78 Guidance on emergency escape lighting is contained within BS 5266. For healthcare premises buildings, this is supplemented by Health Technical Memorandum 06-01 – ‘Electrical services: supply and distribution’ and the CIBSE guide – ‘Lighting guide LG2: hospitals and healthcare buildings’, which provide additional guidance on hospital emergency lighting and details of the electrical supply required.
3.79 Emergency escape lighting should be provided to all areas in accordance with BS 5266. Emergency escape lighting includes escape route lighting, open area lighting and high-risk task area lighting, each of which has specific recommendations in terms of location and luminance.
3.74 In hospitals, electrical distribution is generally provided by essential and non- essential electrical circuits. To enable services to be maintained, the essential circuits are provided with standby generators that operate when there is a failure of mains electricity serving the site or building. These are designed to provide an emergency electrical back-up supply within 15 seconds of a mains failure.
3.80 All emergency escape lighting should have a minimum duration time of three hours and should incorporate fully automatic network testing facilities.
3.81 Where possible, central battery or self- contained emergency escape lighting fittings must derive power from essential circuits.
Plant areas
3.75 In terms of supporting resilience, additional precautions are necessary; for example, the distribution boards for the essential and non- essential circuits may be in the same location but should be in separate metal cabinets. Likewise, essential and non-essential circuits are normally segregated; however, where this is not possible, essential services cables should be wired in fire-resistant cable. (Note: electrical distribution systems serving life safety and fire- fighting applications as detailed in BS 8519 must always be wired in fire-resistant cable.)
3.82 The means of escape from plantrooms should be designed to take account of the fire hazard presented by the equipment or contents of the room and any hindrance to the movement of the occupants (for example low headroom).
3.76 In addition to the above, within each hospital department separate circuits are generally provided for circulation spaces. Therefore, failure of a lighting circuit supplying a circulation space should not affect the lighting circuits in the adjacent rooms, and vice-versa.
3.83 The escape route should be clear of obstructions and have a clear height of at least 2 m throughout its length.
3.84 Where a minimum of two exits are provided, the maximum travel distance from any point within a plantroom should not exceed 25 m to the nearest exit from where alternative means of escape are provided. Of this 25 m, the maximum single direction of escape should not exceed 12 m.
3.77 While these features provide a degree of resilience, they do not fully address potential failure modes such as final circuit, distribution board or phase failure. Furthermore, HTM 06- 01 recommends that emergency escape lighting in all areas can be operational within 0.5 seconds of interruption to the normal supply, which is not achievable solely through the use of standby generators.
[HTM 05-02 – PDF page 50]
b. patients would be able to disperse,
3.85 Where only one exit is provided, the maximum travel distance should not exceed 12 m.
not necessarily following the safest evacuation route or abscond, possibly placing themselves or others at risk; and
c. it would also be more difficult to
3.86 Where only one exit is provided, or where there is a danger of people being trapped, alternative means of escape such as ceiling hatches and fixed ladders should be provided.
establish that everyone had safely escaped from the evacuated area of the building.
3.87 Where the plantroom can be shown to be of very low risk (for example only containing air- handling plant), the distances above may be extended to 25 m and 35 m respectively.
3.90 In areas where security or maintaining patient segregation is important, the staffing levels should be sufficient to allow the operation of a key-operated, or other staff-controlled, means of escape.
Security
3.88 In certain situations it may be essential to maintain a high level of supervision and segregation during an evacuation.
3.91 Any slight delay in opening doors (compared with an automatic system) should be compensated for by the ability of sufficient numbers of well-trained staff team to undertake a controlled evacuation quickly.
3.89 In these situations, secure doors that are released automatically on the activation of the fire alarm system may not be acceptable, since:
a. it would be very difficult for staff to
maintain segregation of patients;