Home › England (NHS England estates) › HTM 05-02 › 3. Means of warning and escape – Final exits / 3. Means of warning and escape – Operating departments

HTM 05-02: 3. Means of warning and escape – Final exits / 3. Means of warning and escape – Operating departments

Firecode - Guidance in support of functional provisions (Fire safety in the design of healthcare premises) · PDF pages 47–48 of 112 · Source file: HTM_05-02_2015.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 05-02 – PDF page 47]

3. Means of warning and escape

c. the provision of adequate paved

Note

footpaths and dropped kerbs to the assembly points;

d. the gradients of external escape routes;

Additional requirements for the enclosure and ventilation of stairways are provided in paragraphs 5.26–5.33.

e. the proximity of external escape routes

to the external wall of the building; and

Final exits

f. the need to maintain segregation of patients if required by the emergency evacuation strategy – see Chapter 2.

Departments providing intensive care

3.58 The design of all exits should recognise the need to maintain the delicate balance between the requirements of means of escape and those of security. It is not possible to provide definitive guidance on this issue; however, any solution should be agreed between the enforcing authorities, the trust management and its local security management specialist.

3.63 In these departments, any movement or evacuation of patients may be life-threatening; consequently, additional precautions are required to address the implications of:

a. fire and smoke in an adjacent

compartment outside the intensive care area;

b. fire and smoke within the department

3.59 Automatic final exit doors should be freely openable by hand under any condition, including power failure; otherwise, adjacent non-automatic outward-opening doors must be provided.

itself.

3.60 Final exit doors should not be provided with a step and should open onto an area which is level for a distance of at least 1 metre.

External escape routes

3.64 The aim of any design should be to prevent a fire in an adjacent compartment either on the same storey or on a storey above or below requiring the evacuation of an intensive care area. The compartmentation and HVAC should be designed so that an adequate period of time is provided to enable a fire to be detected and extinguished before it threatens the occupants.

3.61 Should it become necessary to evacuate an entire building or part of a building, adequate external assembly positions should be available. Suitable positions may be roadways, hard standings or suitably designed parts of the landscaping.

3.62 The following points should be considered when designing external escape routes:

a. the location of assembly positions to

3.65 With the exception of doors from a hospital street, every door opening in the compartment wall should be provided with a protected lobby, each door of which will provide a minimum period of fire resistance of 30 minutes (integrity). This arrangement will reduce the possibility of smoke ingress from a fire outside the department.

permit access for ambulances, while maintaining adequate circulation space for other emergency vehicles;

b. the provision of adequate artificial

lighting;

[HTM 05-02 – PDF page 48]

Operating departments

Sub-compartmentation in departments providing intensive care

3.66 All departments providing intensive care should be divided into at least two sub- compartments in order to separate the “nursing area” from the “utility area”. The following provides an example:

• Sub-compartment one – staff base:

3.69 Operating departments, by their very nature, are considered to be very high dependency areas. Evacuation of patients from these departments may be life-threatening; therefore, additional measures should be provided to allow sufficient time to prepare patients for evacuation (see paragraphs 3.70 to 3.73).

– bed areas;

– clean utility;

– dirty utility;

3.70 Consideration should be given to subdividing the operating department to enable local transfer of patients from the immediate threat to a temporary place of safety; this could be achieved by:

– linen store;

a. sub-compartmenting the operating

– status laboratory;

• Sub-compartment two – entrance area:

department with 30 minutes’ fire resistance; or

– staff changing;

b. installing life safety sprinklers (see

– staff rest rooms;

– seminar rooms;

paragraphs 5.75–5.96) and dividing the operating department with smoke- retarding construction.

– cleaners’ store;

Note

– main equipment store;

– bulk store;

– on-call area.

Heating and ventilation systems

The extent of the sub-division within the operating departments should be risk- assessed, taking into account its size and the number of operating rooms, and operational criticality of the department (that is, business continuity).

3.67 The HVAC systems provided to intensive care areas are designed so that the pressure within the department is maintained at a level slightly above that of the adjacent areas. In a fire emergency, the continuing operation of these systems will assist in preventing smoke and other products of combustion entering the intensive care area.

3.71 The design of the sub-compartmentation, the location of smoke-retarding construction and the operation of fire and smoke dampers should not impede the clean air-flow paths and room-air dilution rates, as this may lead to an increased risk of healthcare-associated infections. It is therefore essential that experts in theatre ventilation systems are fully involved in the design of all fire safety measures in operating theatres.

3.72 Further guidance on the design of specialised ventilation for operating theatres is contained in HTM 03-01 Part A.

3.68 In departments providing intensive care, the HVAC systems should be designed so that they continue to operate in a fire emergency. The shutdown of these systems should be controlled from remote panels located either at the department entrance or adjacent to the main fire-alarm indicator panel.