[HTM 05-02 – PDF page 43]

3. Means of warning and escape

3.38 Entrances from the hospital street to adjoining compartments should:

3.42 In departments and areas where beds or patient trolleys will not be used, the minimum clear width of escape routes should be:

a. not be located in the same street sub-

a. for up to 200 people – 1200 mm;

compartment as entrances to stairways and lift enclosures;

b. for over 200 people – an additional

b. be located so that an alternative means

275 mm for every additional 50 people.

of escape from each compartment is always possible (see Figure 8).

Vertical escape

3.39 Stairways should be located so that the maximum travel distance from the exit of the stairway enclosure to a final exit from the hospital street is no more than 60 m. However, it should be noted that there are additional requirements for fire-and-rescue service access into hospital streets, see paragraphs 7.18–7.20.

Additional requirements for hospital streets with only three sub-compartments

3.43 In the majority of healthcare premises the practice of designating certain stairways as escape stairways and others as accommodation stairways only is not acceptable, since in an emergency any stairway will be used if necessary. Therefore all stairways, other than those contained within and only serving an atrium, should be designed as escape stairways to permit vertical evacuation by the most appropriate method, see paragraphs 3.53 to 3.55.

3.44 Most healthcare premises will normally contain an adequate number of stairways due to functional requirements; however, the minimum number of stairways should always meet the provisions in Table 2 below.

3.40 On upper storeys, stairways should be provided in two of the three sub- compartments, and the third sub-compartment should be capable of accommodating all the occupants with the associated beds and medical equipment of the largest adjoining compartment.

Number of patient beds on

Number of stairways

any one upper storey

Width of escape routes

1–100

101–200

201–300

301–400

Table 2 Provision of stairways

3.41 Generally, within departments where beds and patient trolleys are being moved, the width of the circulation spaces required for these activities should be adequate for escape purposes. However, elsewhere, the width of escape routes should be determined by the number of people who would normally be expected to use them in an emergency. In addition, the use of steps should be avoided on circulation routes. Changes in level should be overcome using ramps.

3.45 Every building providing healthcare should be provided with a minimum of two stairways. Where hospitals are provided with hospital streets, the stairways should be located within the hospital street. In hospitals not provided with hospital streets, each compartment should have access to a stairway by way of a circulation space – see Figure 2.

Note

3.46 In all healthcare premises, stairways should be located so that alternative means of escape is always available from every compartment and sub-compartment.

Guidance on suitable widths of circulation routes within hospital departments, for operational purposes, is available in Health Building Note 00-04 – ‘Circulation and communication spaces’.

[HTM 05-02 – PDF page 44]

Assisted patient evacuation

3.47 External stairways should not be provided for escape purposes from patient-access areas.

3.48 Stairways should always be remote from each other so that in the event of fire at least one is available for evacuation purposes.

Escape lifts

3.53 All stairways to areas that provide sleeping accommodation or contain dependent or very high dependency patients should be designed to permit the evacuation of patients on mattresses (mattress evacuation) or other similar methods. The stair width is not determined by the number of people expected to use the flight in a fire emergency, but by the requirements of mattress manoeuvrability, and therefore the guidance in Approved Document K – ‘Protection from falling, collision and impact’ in relation to landing depths need not be applied.

3.49 Where departments providing care and treatment for very high dependency patients or bariatric patients are accommodated on upper floors, at least two escape lifts should be provided. These should be sufficiently remote from each other to ensure that at least one is always available in the event of a fire.

3.54 Table 3 and Figure 10 below provide guidance on dimensions to facilitate assisted patient evacuation.

Note

Width of stairways not intended for assisted patient evacuation

It is unrealistic to believe that the total evacuation of occupants from upper floors of multi-storey buildings can be achieved solely by the use of lifts. Therefore escape stairways will always be required.

3.55 Where stairways provide escape from areas used only by independent patients, the width of the stairway should be determined from the guidance in paragraph 3.42.

All stairways

3.50 The dimensions of escape lifts and lobbies should comply with Figure 9 below.

3.56 All stairways should terminate at final exit or escape level and:

a. provide access to the outside; or

b. discharge to a route from the base of

the stairway to the outside, which provides the same period of fire resistance as the protected shaft and which contains no accommodation except that permitted for a protected shaft; or

3.51 In large buildings or extensive hospital complexes it may be appropriate to utilise non- escape lifts as part of the evacuation strategy. In such instances the lifts should be in a separate fire compartment and separated by distance from the fire-affected part of the building. An assessment will be required to support the use of non-escape lifts in an evacuation; this should consider the guidance of BD 2466 – ‘Guidance on emergency use of lifts or escalators and fire and rescue service operation’.

c. discharge to a hospital street.

Additional requirements for stairways

3.57 Escape stairs should not discharge to an atrium.

3.52 All escape lifts should be designed to comply with the guidance in Health Technical Memorandum 05-03: Part E – ‘Escape lifts’ and BS 5588-8 – ‘Fire precautions in the design, construction and use of buildings: Code of practice for means of escape for disabled people’ and Health Technical Memorandum 08-02 – ‘Lifts’.

[HTM 05-02 – PDF page 45]

3. Means of warning and escape

car size

(1800)

handrail

1000–1080

trolley/ equipment

(2700)

clear car size

600 (500)

approx 2440 with pump attached to end of bed

(1370)

(3370)

width of space for attendants to turn bed 180 degrees

CL

4310 (3980)

length of space for attendants to turn bed 180 degrees

Figure 9 Dimensions of escape lifts and lobbies

[HTM 05-02 – PDF page 46]

A Minimum clear landing width

B Minimum clear stair width

C Minimum clear landing depth

(mm)

(mm)

(mm)

allows assisted patient evacuation only

allows assisted patient evacuation and restricted ambulant passing

1600* allows assisted patient evacuation plus ambulant passing 1800*

* Stair width is not determined by the number of people expected to use the stairs in a fire emergency, but principally by the requirements of assisted patient evacuation.

The evacuation strategy and the notes below will determine the optimum requirements for stair widths and landing depths.

For a clear landing width of 3400 mm, the minimum clear landing depth for assisted patient evacuation is 1450 mm. 1600 mm is the recommended depth to enable ambulant passing and to equal the stair clear width. See BS 8300.

For a clear landing width of 3800 mm, the minimum clear landing depth for assisted patient evacuation is 1350 mm. 1800 mm is recommended to equal the stair width. See BS 8300.

Table 3 Alternative stair and landing dimensions to facilitate assisted patient evacuation

Example landing depth for 1500 clear stair width. Alternative dimensions see Table 3

C (1550)

B (1500)

Example stair width, see table

DOWN

1500 clear stair width. Alternative dimensions see Table 1

Example landing width to facilitate “U-turn” dragging mattress, for

A (3220) 120 (100)

Figure 10 Assisted patient evacuation down a stairway