HTM 05-02: 3. Means of warning and escape – Hospital streets
[HTM 05-02 – PDF page 40]
i. Maximum travel distance no more than 30 m to an adjoining compartment or subcompartment Subcompartment Compartment or subcompartment
30 m maximum
OR
ii. Maximum travel distance no more than 30 m to a stairway or final exit Subcompartment
Stairway or final exit
30 m maximum
Figure 6 Travel distances within a sub-compartment
(iii) so that the maximum distance from
Hospital streets
3.37 A hospital street should:
a compartment exit to a final exit is no more than 90 m;
a. be constructed to the same fire-resisting
e. at upper levels – have access to a
standards as a fire compartment;
b. have a minimum clear width of 3 m;
minimum of two stairways each in separate sub-compartments, which are located so that:
c. be divided into a minimum of three sub-
(i) the maximum distance between
stairways does not exceed 60 m;
compartments, each with a maximum length of 30 m;
(ii) the maximum single direction of
d. at ground floor – have a minimum of two
final exits located:
travel within the street does not exceed 15 m;
(i) at every extremity of the hospital
(iii) the distance from a compartment
street;
(ii) so that the maximum travel
exit to a stairway is no more than 30 m; and
distance between final exits is no more than 180 m measured along the length of hospital street;
f. contain no other accommodation except sanitary accommodation (see Figures 7 and 8).
[HTM 05-02 – PDF page 41]
3. Means of warning and escape
i. Basic design
Minimum width of street 3000 mm Final exit at every extremity
Hospital accommodation Hospital accommodation
Final exit – minimum width of street – 3000 mm
Hospital accommodation Hospital accommodation
Final exit
60-minute fire-resisting compartment walls
ii. Basic subdivision
Maximum distance – 90 m to a final exit
Hospital accommodation Hospital accommodation
Lifts Lifts
Hospital accommodation
Maximum distance – 60 m to a final exit
Hospital accommodation Hospital accommodation
60-minute fire-resisting Maximum travel distance compartment walls between final exits – 180 m
Street subdivisions 30-minute fire-resisting subcompartment walls
Figure 7 Hospital streets at ground level
[HTM 05-02 – PDF page 42]
Key...............................
Hospital street
i. Basic design
Hospital accommodation
Hospital accommodation Hospital accommodation
30 m maximum travel distance to nearest
15 m maximum single direction of escape travel
stairway
distance
Stairway enclosures maximum
15 m maximum single direction of escape travel
distance
60 m apart
Stairway enclosures maximum 60 m apart
Hospital accommodation Hospital accommodation
60-minute fire-resisting compartment walls
ii. Basic subdivision Hospital accommodation
Lifts
Hospital accommodation Hospital accommodation
Lifts
Hospital accommodation Hospital accommodation
60-minute fire-resisting compartment walls
The arrangement indicated below is not acceptable, as a fire affecting the hatched area of the hospital street would prevent escape from compartments 1 and 2
Street subdivision 30-minute fire- resisting subcompartment walls
Hospital street
Compartment 3 Compartment 1 Compartment 2
Figure 8 Hospital streets on upper floors