i. Maximum travel distance no more than 30 m to an adjoining compartment or subcompartment Subcompartment Compartment or subcompartment

30 m maximum

OR

ii. Maximum travel distance no more than 30 m to a stairway or final exit Subcompartment

Stairway or final exit

30 m maximum

Figure 6 Travel distances within a sub-compartment

(iii) so that the maximum distance from

Hospital streets

3.37 A hospital street should:

a compartment exit to a final exit is no more than 90 m;

a. be constructed to the same fire-resisting

e. at upper levels – have access to a

standards as a fire compartment;

b. have a minimum clear width of 3 m;

minimum of two stairways each in separate sub-compartments, which are located so that:

c. be divided into a minimum of three sub-

(i) the maximum distance between

stairways does not exceed 60 m;

compartments, each with a maximum length of 30 m;

(ii) the maximum single direction of

d. at ground floor – have a minimum of two

final exits located:

travel within the street does not exceed 15 m;

(i) at every extremity of the hospital

(iii) the distance from a compartment

street;

(ii) so that the maximum travel

exit to a stairway is no more than 30 m; and

distance between final exits is no more than 180 m measured along the length of hospital street;

f. contain no other accommodation except sanitary accommodation (see Figures 7 and 8).

[HTM 05-02 – PDF page 41]

3. Means of warning and escape

i. Basic design

Minimum width of street 3000 mm Final exit at every extremity

Hospital accommodation Hospital accommodation

Final exit – minimum width of street – 3000 mm

Hospital accommodation Hospital accommodation

Final exit

60-minute fire-resisting compartment walls

ii. Basic subdivision

Maximum distance – 90 m to a final exit

Hospital accommodation Hospital accommodation

Lifts Lifts

Hospital accommodation

Maximum distance – 60 m to a final exit

Hospital accommodation Hospital accommodation

60-minute fire-resisting Maximum travel distance compartment walls between final exits – 180 m

Street subdivisions 30-minute fire-resisting subcompartment walls

Figure 7 Hospital streets at ground level

[HTM 05-02 – PDF page 42]

Key...............................

Hospital street

i. Basic design

Hospital accommodation

Hospital accommodation Hospital accommodation

30 m maximum travel distance to nearest

15 m maximum single direction of escape travel

stairway

distance

Stairway enclosures maximum

15 m maximum single direction of escape travel

distance

60 m apart

Stairway enclosures maximum 60 m apart

Hospital accommodation Hospital accommodation

60-minute fire-resisting compartment walls

ii. Basic subdivision Hospital accommodation

Lifts

Hospital accommodation Hospital accommodation

Lifts

Hospital accommodation Hospital accommodation

60-minute fire-resisting compartment walls

The arrangement indicated below is not acceptable, as a fire affecting the hatched area of the hospital street would prevent escape from compartments 1 and 2

Street subdivision 30-minute fire- resisting subcompartment walls

Hospital street

Compartment 3 Compartment 1 Compartment 2

Figure 8 Hospital streets on upper floors