Home › England (NHS England estates) › HTM 05-02 › 3. Means of warning and escape – Sub-compartmentation / 3. Means of warning and escape – Travel distances

HTM 05-02: 3. Means of warning and escape – Sub-compartmentation / 3. Means of warning and escape – Travel distances

Firecode - Guidance in support of functional provisions (Fire safety in the design of healthcare premises) · PDF pages 37–39 of 112 · Source file: HTM_05-02_2015.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 05-02 – PDF page 37]

3. Means of warning and escape

Note

the management and operational arrangements by making the boundaries of compartments coterminous with departmental boundaries.

3.23 Additional requirements for compartmentation are provided in Chapter 5.

Sub-compartmentation

It is not possible to give precise recommendations on the location of alternative exits; the aim should be to locate these as far apart as practical and if possible in opposite walls. In the event of a fire, at least one exit should always be available.

Escape routes over flat roofs

3.21 If more than one escape route is available from a storey, or part of a building, one of those routes may be by way of a flat roof, provided that:

a. the route is for staff only;

b. the roof should be part of the same

building from which escape is being made;

c. the route across the roof should lead to

3.24 The maximum size of a compartment permitted by this document – although appropriate for fire containment (see paragraph 5.11) – is nevertheless considered too large if the area contains patient-access areas. In the event of a fire, a large number of patients could be overcome by the spread of fire, smoke and toxic gases. Therefore, compartments containing patient-access areas should be divided into smaller sub-compartments to limit the number of patients who may be affected by a fire. Wherever possible, there should be a balance of patients between sub- compartments.

a storey exit or external escape route;

d. the part of the roof forming the escape

3.25 A compartment should be sub- compartmented if:

a. it has a floor area greater than 750 m2;

or

b. it contains departments to which more

than 30 patients will have access at the same time; or

route and its supporting structure, together with any opening within 3 m of the escape route, should be fire-resisting (to a minimum period of 30 minutes if the roof is used solely as an escape route, or to a period provided in Table 5 if the roof is also used as a floor); and

c. it contains sleeping accommodation for

e. the route should be adequately defined

more than 30 patients.

and guarded by walls and/or protective barriers which meet the provisions in Approved Document K.

Note

Compartment/department relationships

For out-patient departments in hospitals, the floor area may be increased to 1000 m2 before sub-compartmentation becomes necessary.

3.26 Sub-compartments should be enclosed by walls having a minimum period of fire resistance of 30 minutes, which should terminate at the underside of:

a. a compartment floor; or

b. a roof.

3.22 The provision of compartments to facilitate progressive horizontal evacuation should not be looked upon only in terms of means of escape. The management responsibilities, such as the extent of the area under their control, the day- to-day management, fire drills, the management of evacuation etc, will have a significant impact on the design, integrity, size and configuration of compartments. For these reasons it is strongly recommended that the design of a compartment should recognise and integrate

[HTM 05-02 – PDF page 38]

c. 18 m for all other parts of healthcare

Exits from sub-compartments

buildings.

Note

3.27 Each sub-compartment should be provided with a minimum of two exits to adjoining but separate compartments or sub-compartments.

3.28 In healthcare buildings, the left-hand arrangement illustrated in Figure 4 is not acceptable.

There will be exceptions to these distances in certain parts of healthcare premises buildings (for example aseptic preparation units, operating departments, linac rooms). Where these distances are exceeded, it must be justified in the fire strategy document.

Travel distances

3.29 The distance to adjacent compartments, sub-compartments, hospital streets, stairways and final exits should be limited to ensure that the occupants can escape from the effects of a fire within a reasonable period of time.

3.31 Any part of an enclosed escape route that has single direction of escape only, and exceeds 4.5 m, should be protected by 30-minute fire-resisting construction (integrity and insulation). This does not include travel within a room, but applies to “stub” corridors or a small corridor recess.

Single direction of escape

3.30 The maximum travel distance before there is a choice of escape routes should be no more than:

a. 15 m for in-patient accommodation; or

b. as specified in paragraphs 3.85–3.87; or

3.32 Only glazing that provides a minimum period of fire resistance of 30 minutes (integrity and insulation) may be provided on circulation spaces that give a single direction of escape. Where a sprinkler system is installed, there is no requirement for insulation provided that the

B

A

SC1 SC3

SC1 SC3

SC2

SC2

The subcompartmentation in example B is acceptable since a fire in any one subcompartment would not block the safe exit from others.

The subcompartmentation in example A is unacceptable since a fire in SC3 would block the exit from SC1 and SC2.

Figure 4 Exits from sub-compartments

[HTM 05-02 – PDF page 39]

3. Means of warning and escape

b. an adjoining compartment and to a

glazing is not the type referred to as “modified toughened”.

stairway or final exit (see Figure 5).

3.33 Escape from an inner room via an access room is permitted provided the access room is not a fire hazard room.

3.35 The maximum travel distance from any point within a sub-compartment should be no more than 30 m to:

a. an adjoining compartment or sub-

Total travel distance

compartment; or

b. a stairway or final exit (see Figure 6).

3.34 The maximum travel distance from any point within a compartment should be no more than 60 m to:

3.36 Single-direction-of-escape travel distance is an element of maximum travel distance.

a. each of two adjoining compartments; or

Compartment 1 Compartment 2 Compartment 3

60 m maximum

60 m maximum

i. Maximum travel distance no more than 60 m to each of two adjoining compartments

OR

Compartment 1 Compartment 2

60 m maximum

60 m maximum

ii. Maximum travel distance no more than 60 m to an adjoining compartment and to a stairway

Figure 5 Travel distances within a compartment