HTM 05-02: 3. Means of warning and escape –  / 3. Means of warning and escape – Progressive horizontal evacuation
[HTM 05-02 – PDF page 33]
3. Means of warning and escape
Requirement
Chapter 3 provides guidance to comply with the following Requirement from Part B of Schedule 1 of the Building Regulations 2010.
Requirement
Means of warning and escape
3.3 Health Technical Memorandum 05-03 Part B – ‘Fire detection and alarm systems’ provides general principles and technical guidance on the design, specification, installation, commissioning, testing, operation and maintenance of fire alarm systems in healthcare premises. It should be read in conjunction with BS 5839-1 and the relevant parts of BS EN 54.
Principles of means of escape
B1 The building shall be designed and constructed so that there are appropriate provisions for early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.
3.4 The design and construction of the building should ensure that at all times, patients, visitors and staff can move away from a fire to: a place of temporary safety inside the building on the same level, from where further escape is possible, ultimately to a place of safety outside the building; or lead directly to the outside.
Fire detection and alarm
3.5 This chapter provides guidance on means of escape by reference to:
a. the potential for horizontal evacuation,
3.1 The design and construction of the building should ensure that fires are detected at the earliest possible opportunity and that suitable warning is then given to the occupants and the emergency services.
which is achieved by dividing the storey into compartments and sub- compartments;
b. the height above ground of the treatment
area;
c. travel distances and escape routes;
d. the provision of an adequate number of
stairways to facilitate vertical escape;
3.2 The provision of adequate means for detecting a fire and raising the alarm is of vital importance. Early detection permits time for orderly evacuation and allows the fire to be tackled at an earlier stage, thus minimising the damage caused. Detection is dependent on both staff observation and the automatic detection and alarm systems.
e. emergency and escape lighting.
[HTM 05-02 – PDF page 34]
Progressive horizontal evacuation
which contains patient-access areas should be divided into a minimum of three compartments. One of these compartments may be a hospital street (see paragraphs 3.37–3.40).
3.6 The need for progressive horizontal evacuation is discussed in Chapter 2. This principle will be met if the requirements in paragraphs 3.7–3.43 and Figure 2 below are achieved.
3.12 Where sprinklers are installed, the fire- resistance of the compartment walls may be reduced to 30 minutes (integrity and insulation), see paragraph 5.12.
Floors over 12 m above ground level
3.7 In a fire emergency, each compartment should be capable of accommodating, as well as its normal occupants, the designed occupancy of the most highly occupied adjoining compartment. This should include space to accommodate beds and medical equipment required to ensure continuity of care.
Note
3.13 Every level over 12 m above ground that contains patient-access areas should be divided into a minimum of four compartments. Where no hospital street is provided, each compartment should have a minimum floor area of 500 m2; where one of the compartments is a hospital street, the area of the hospital street may be less than 500 m2.
For a definition of ground level, see “Height of a building” in the Glossary.
3.14 Where sprinklers are installed, the minimum floor area of each compartment required by paragraph 3.13 above may be reduced to 350 m2.
Floors up to 12 m above ground level with an area of less than 1000 m2
General
3.8 Every level with a floor area of less than 1000 m2 and which contains patient-access areas should:
a. contain no more than 30 patients; and
b. be divided into a minimum of two
compartments.
3.15 In a fire emergency each compartment should be capable of accommodating, in addition to its normal occupants, the designed occupancy (including all relevant life support systems) of the most highly occupied adjoining compartment.
Exits from compartments
3.9 Where a compartment provides sleeping accommodation, the maximum number of beds in the compartment should be no more than 20.
3.16 Exits from compartments should be by way of a circulation space and provided in accordance with the guidance in Figure 2.
3.10 On floors above ground-floor level where sprinklers are installed, the fire-resistance of the compartment walls may be reduced to 30 minutes (integrity and insulation), see paragraph 5.12.
Floors up to 12 m above ground level with an area of more than 1000 m2
3.17 While it is permissible to locate clinical and some non-clinical departments adjacent to each other, the means of escape through the non-clinical area must be designed to safely accommodate the evacuation of patients (that is, escape routes should be sufficiently wide enough to accommodate beds/trolleys).
3.11 Every level up to 12 m above ground level that has a floor area of more than 1000 m2 and
3.18 It is not permissible to evacuate any non- clinical area through a clinical area unless the
[HTM 05-02 – PDF page 35]
3. Means of warning and escape
1. Storeys up to 12 metres above ground with a floor area of less than 1000 m² – a minimum of two exits required as shown below
Maximum of 30 patients on each storey
Compartment one
Compartment two
A A
Where compartment provides sleeping accommodation – maximum of 20 beds in each compartment
B
Exit A – by way of a circulation space to: (i) a stairway; or (ii) a final exit. Exit B – to an adjoining compartment (see also paragraphs 3.16–3.20)
2. Storeys up to 12 metres above ground with a floor area of more than 1000 m² – a minimum of three exits required as shown below
Compartment one
Compartment two
Compartment one
Compartment two
B
B
A
A
C C
B B
D D Hospital street
A
Compartment three
Exit B – to an adjoining compartment (see also paragraphs 3.16–3.20) Exit C – by way of a circulation space to the hospital street Exit D – by way of the hospital street only to a stairway or final exit
Exit A – by way of a circulation space to: (i) a stairway; or (ii) a final exit. Exit B – to an adjoining compartment (see also paragraphs 3.16–3.20)
3. Storeys over 12 metres above ground – a minimum of three exits required as shown below
Compartment three
Compartment one
Compartment two
Compartment one
Compartment two
B
B
B
A A
C C
B B
C
D D
Hospital street
A A
B
Exit B – to an adjoining compartment (see also paragraphs 3.16–3.20) Exit C – by way of a circulation space to the hospital street Exit D – by way of the hospital street only to a stairway or final exit
Exit A – by way of a circulation space to: (i) a stairway; or (ii) a final exit. Exit B – to an adjoining compartment (see also paragraphs 3.16–3.20)
Figure 2 Requirements for progressive horizontal evacuation (paragraphs 3.6–3.15)
[HTM 05-02 – PDF page 36]
b. a circulation space in an adjoining
route through the clinical area is via a circulation route only.
compartment or sub-compartment (see Figure 3).
3.19 From ward bedrooms only, it is acceptable to directly escape to:
a. an adjacent ward bedroom in an
adjoining compartment or sub- compartment; or
3.20 Where a storey is divided into three or more compartments, the exits from each compartment should be located so that there are at least two alternative exits that provide horizontal escape to adjoining but separate compartments.
Compartment 1 Compartment 2
Notes:
i. the escape door in the compartment wall should be available for use at all times and should never be locked;
ii. the bedroom door and the escape door should be opposite each other and the route between them kept clear;
ward bedroom ward bedroom
iii. escape should be from circulation space through one ward bedroom only, through the compartment wall then through one ward bedroom only to the circulation space.
Compartment 1 Compartment 2
ward bedroom
Note:
i. in this instance escape from the circulation space in compartment 2 should not be via the ward bedroom into compartment 1
Key..................................
circulation space
Figure 3 Escape from ward bedrooms