HTM 05-02: 2. Principles of fire safety in healthcare premises

Firecode - Guidance in support of functional provisions (Fire safety in the design of healthcare premises) · PDF pages 22–32 of 112 · Source file: HTM_05-02_2015.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 05-02 – PDF page 22]

2. Principles of fire safety in healthcare premises

Introduction

ensures that the concept of “inclusive design” has been applied.

2.4 Healthcare premises accommodating dependent and very high dependency patients should be divided into a series of compartments that may be further divided into sub-compartments which should be constructed to provide the appropriate level of fire safety (see Chapters 3 and 5).

2.1 In healthcare buildings, particularly in patient access areas, the immediate and total evacuation of the building in the event of fire would be a major logistics exercise and, from a patient safety perspective, not desirable. Patients with restricted mobility, patients who use wheelchairs, and patients confined to bed cannot negotiate escape routes, particularly stairways, unaided. Patients under medication may require staff assistance, and patients who are dependent on electrical/mechanical equipment for their survival cannot always be disconnected and moved rapidly without serious consequences.

2.5 Where the evacuation involves very high dependency patients, additional consideration must be given to the distance of travel that might be necessary to reach a place of safety where essential treatment and care could be recommenced.

Fire safety philosophy

Fire evacuation strategy

2.2 HTM 05-02 assumes that there are sufficient adequately trained staff on duty in the building to implement the emergency plan. However, while the total evacuation of smaller buildings, or smaller healthcare premises within other buildings, accommodating occupants considered to be independent might be practical, the evacuation of an entire hospital in the event of fire would be an enormous exercise in which patients might be placed at risk due to trauma or their medical condition.

2.6 The basic strategy for fire evacuation of dependent and very high dependency patients should be to move them on their bed or in a wheelchair to a safer area (refuge or place of relative safety) on the same floor and then (if required) to evacuate the patients to another floor in the building or to outside.

2.7 There are three main stages of evacuation:

a. Stage 1 – horizontal evacuation from

2.3 Should evacuation become necessary, except for those premises with independent occupants, it should be based on the concept of progressive horizontal evacuation, with only those people directly at risk from the effects of fire being moved. Adopting this approach

the area where the fire originates to an adjoining sub-compartment or compartment;

[HTM 05-02 – PDF page 23]

2. Principles of fire safety in healthcare premises

b. Stage 2 – horizontal evacuation from the

should give sufficient time for non-ambulant and partially ambulant patients to be evacuated vertically to a place of safety, should it become necessary to evacuate an entire storey.

2.11 Active fire protection systems such as automatic fire detection systems, warning systems and fire suppression systems may be incorporated into the building so that the time available for escape is maximised.

entire compartment where the fire originates to an adjoining compartment on the same floor. Subsequent additional horizontal evacuation to adjacent compartments may be undertaken (thereby putting additional fire resistance between the building occupants and the threat) prior to undertaking vertical evacuation; and

c. Stage 3 – vertical evacuation to a lower

floor, or to the outside.

2.12 Patient-access areas should be designed to allow for progressive horizontal evacuation other than in premises where patients fall into the independent category.

2.8 There are three fire conditions when evacuation is necessary or should be considered:

a. Extreme emergency – where there is an

immediate threat to safety from fire or smoke;

2.13 Areas to which patients have access should not be located on storeys where evacuation in a fire emergency would necessitate travelling up a stairway to a final exit.

b. Emergency – no immediate threat, but

Hospital streets

fire or smoke likely to spread from an adjoining area;

c. Precautionary – no immediate threat to

life or safety, but there is a fire on an adjoining floor or in an adjacent building.

2.9 In extreme emergency situations, the sequence of evacuation should be:

a. those in immediate danger;

2.14 The hospital street provides an essential link between hospital departments and stairways and lifts; it is the main circulation route for staff, patients and visitors. Although many hospitals will be provided with hospital streets, they are not an essential requirement. In smaller hospitals, such as community hospitals, and other healthcare premises, hospital streets are generally not provided.

b. ambulant patients;

c. the remaining patients who are not

ambulant.

2.15 A hospital street is a special type of compartment that connects final exits, stairway enclosures and department entrances. It has two functions from a fire safety aspect:

Progressive horizontal evacuation

a. if the spread of fire within a department

cannot be brought under control, the occupants of the department affected may be evacuated via the hospital street to parts of the hospital not affected by the fire; and

b. it will serve the fire-and-rescue service

as a fire-fighting bridgehead.

2.10 The principle of progressive horizontal evacuation is that of moving occupants from an area affected by fire through a fire-resisting barrier to an adjoining area on the same level, designed to protect the occupants from the immediate dangers of fire and smoke (a refuge). The occupants may remain there until the fire is dealt with or await further assisted onward evacuation by staff to another similar adjoining area or to the nearest stairway. This procedure

[HTM 05-02 – PDF page 24]

Vertical escape

• Dependent – all patients except those classified as “independent” or “very high dependency”.

2.16 Vertical escape in healthcare premises should only be conducted if a fire cannot be controlled within the space of origin and there is additional risk to occupants outside of the fire compartment of origin. This approach to fire safety is adopted due to the additional risks that are present to both staff and patients during the vertical escape phase.

• Very high dependency – those whose clinical treatment and/or condition creates a high dependency on staff. This will include those in intensive care areas, operating theatres, coronary care etc and those for whom evacuation would prove potentially life-threatening.

Independent patients

2.17 In healthcare premises, the practice of designating certain stairways as escape stairways and others as accommodation stairways only is not acceptable, since in an emergency any stairway will be used if necessary. Therefore all stairways should be designed as escape stairways other than those contained wholly within and only serving an atrium.

2.20 Areas containing independent patients or occupants who can escape from a fire unaided do not have such a reliance on horizontal evacuation, and therefore the need for compartmentation both horizontally and vertically is reduced.

2.18 It is recognised that there are many benefits in using lifts to assist with vertical evacuation, especially when evacuating dependent and very high dependency patients, and appropriate guidance is provided in Chapter 3.

2.21 In most cases, the use of Approved Document B will be sufficient (purpose group 2a, or 5 depending on the type of premises). However, where doubt may exist about the mobility of patients, advice should be sought from clinicians to ensure that no part of patient care or treatment would prevent them from quickly responding in the event of a fire.

Specific considerations based on patient dependency

2.19 Firecode has three classifications for patient dependency:

2.22 Based on an assessment of each type of patient care, it may be necessary in some instances to apply the recommendations within this document in addition to those of Approved Document B.

• Independent – patients are considered to be independent if:

Note

– their mobility is not impaired in any

way and they are able to physically leave the premises without staff assistance; or

– they experience some mobility

Although the occupancy of an area may be identified as independent, consideration should be given to the need for patients categorised as dependent or very high dependency who may need to be evacuated through that area. In such circumstances the means of escape provisions should reflect the measures necessary for the evacuation of higher dependency occupants.

impairment and rely on another person to offer minimal assistance. This would include being sufficiently able to negotiate stairs unaided or with minimal assistance, as well as being able to comprehend the emergency wayfinding signage around the facility.

[HTM 05-02 – PDF page 25]

2. Principles of fire safety in healthcare premises

Dependent patients

adequate period of time is provided to enable a fire to be detected and extinguished before it threatens occupants.

2.23 The guidance in this document provides additional guidance above that of Approved Document B, which is necessary to meet the increased dependency of patients who fall within this category (and those within the very high dependency category).

Very high dependency patients

2.28 The HVAC systems provided to intensive care areas are designed so that the pressure within the department is maintained at slightly above that of the adjacent areas. In a fire emergency, the continuing operation of these systems will assist in preventing smoke and other products of combustion entering the intensive care area.

2.24 In operating theatres and areas that provide intensive care, any movement or evacuation of patients may be life-threatening; consequently, additional precautions are required to address the implications of:

a. fire and smoke in a compartment either

adjacent or below;

b. fire and smoke within the department

itself.

2.29 Although it is accepted that some occupants, because of their condition or treatment, should not be moved, provision must still be made for external evacuation. The need for a vertical movement strategy for such occupants must be recognised, and appropriate measures must be installed to reduce the risk associated with such an action.

2.25 The enclosing of departments with fire- resisting construction and the strategic planning of adjacent compartments goes some way to mitigating the risk. The time required for evacuation is longer, as it is often necessary to move the patient, ventilators, monitoring equipment and support staff as one unit, and the design should seek to maximise the protection to the occupants allowing for extended start-up times.

2.30 Protected lobbies are provided to those areas of the premises that require additional means to protect against the movement of smoke. Where risk assessment has demonstrated a need, very high dependency treatment areas should be provided with a lobby, which should be sized appropriately to fully accommodate a bed, the associated ancillary equipment and nursing staff, and should include sufficient additional floor space to allow for any manoeuvring as necessary.

2.26 Some of the equipment, such as the ventilator, are integral parts of the anaesthesiologist’s equipment and so are provided with an electrical back-up supply. However, this type of equipment is often large and unwieldy, and the evacuation must be pre- planned, as double doorsets are required to facilitate the efficient movement of ancillary equipment.

2.31 Where smoke movement into an area accommodating very high dependency patients has been identified as a potential risk (that is, where no hospital streets have been provided), every door opening in the compartment wall should be provided with a protected lobby, each door of which will provide a minimum period of fire resistance of 30 minutes.

2.32 Any future change in dependency is likely to result in a significant change to the fire precautions applicable. This applies equally to premises designed for independent patients.

2.27 The aim of any design should be to prevent a fire in an adjacent compartment either on the same storey or on a storey above or below, requiring the evacuation of a intensive care area. The compartmentation and HVAC (heating, ventilation and air-conditioning) systems should be designed so that an

[HTM 05-02 – PDF page 26]

Healthcare premises in Purpose Group 5 – Assembly and Recreation

Facilities providing in-patient mental health services and in-patient accommodation for people with learning disabilities

2.37 In this context, an in-patient service is defined as a unit with “hospital beds” that provides 24-hour nursing care. Such a unit may be in a hospital campus or a community setting, and may be provided by the NHS or by independent sector providers.

2.33 It is becoming more common for health centres, clinics and GP surgeries to provide facilities for minor invasive investigations or procedures that require the use of a local anaesthetic. These will be DTS and DSS services regulated by the Care Quality Commission – see Appendix H. Generally the procedures will be undertaken in a minor procedure room, or treatment room possibly with an adjacent recovery area where patients may remain under observation until the effects of the anaesthetic have worn off.

2.38 In-patient beds should be distinguished from placements registered for the provision of care, which are provided by local authorities and independent sector providers and registered by the CQC. These provide accommodation, usually in a room in a multiple occupancy facility, and a care/support package funded by health and social services.

2.39 The guidance in HTM 05-02 applies only to in-patient services and not placements.

2.34 In many cases the use of an anaesthetic will restrict mobility so that patients will require assistance to escape in the event of a fire. Therefore in DTS and DSS premises the means of escape from relevant areas should be designed so that it is always possible, in the first instance, to escape:

a. horizontally to a place of relative safety

2.40 In-patient mental health services cover the following range of services:

from where further horizontal or vertical evacuation is possible; or

b. directly to a place of safety at ground

level.

• Acute in-patient bed – acute in-patient wards for working age adults (18–65) providing intensive medical and nursing support for patients in periods of acute psychiatric illness.

2.35 The place of relative safety should either be a separate 30 minute sub-compartment, or a refuge in an escape stairway that is enclosed in 30 minute fire-resisting construction, either of which should be large enough to accommodate the number of patients who at any one time could reasonably be expected to be receiving or recovering from minor invasive investigations or procedures.

2.36 It is also strongly recommended that these premises are provided with a fire detection and alarm system that complies with the relevant guidance in the HTM 05-03 Part B.

• Psychiatric intensive care unit – a type of psychiatric ward. These wards are secure, meaning they are locked and entry and exit of patients is controlled. Staffing levels are higher, sometimes with 1:1 nursing staffing ratios. They usually receive patients who cannot be managed in an acute ward due to the level of risk the patient poses to themselves or others. In some cases patients may also be referred from prisons or rehabilitation wards. Patients will usually be detained under the Mental Health Act.

• Forensic services – this covers high, medium and low secure units, of which

[HTM 05-02 – PDF page 27]

2. Principles of fire safety in healthcare premises

only the last two are covered by HTM 05-02.

Further information on all of the above is provided in ‘Defining mental health services’, published in 2012 by the Mental Health Network of the NHS Confederation.

• Low secure services – are provided for those patients who have long-standing and complex problems who cannot be safely or successfully cared for in an acute ward. Patients will be detained under the Mental Health Act.

• In-patient facilities for people with learning disabilities – a learning disability affects the way a person understands information and how they communicate; it is not the same as a learning difficulty or mental illness. In- patient assessment and treatment beds are required for people with learning disabilities with complex mental health problems and/or challenging behaviours that cannot be managed in the community. The number of units across the NHS is small.

• Medium secure services – are specially designed to meet the needs of adults with a serious mental illness, who require care and treatment in a secure setting to ensure they are safely managed. In most cases patients in medium security will have committed an offence and present a serious risk to themselves and others, combined with a potential to escape.

Specific fire safety information relating to the above premises

• Recovery and rehabilitation services – rehabilitation units are provided for adults with severe and enduring mental health problems who have ongoing symptoms and functional impairments and cannot manage independent living, even with support.

2.41 Although the range of services provided varies considerably, there are common issues that must be considered to enable appropriate levels of fire safety to be achieved. The ultimate aim is to provide a safe and secure environment where patients can receive care and treatment; however, safety from the effects of fire and maintaining the required levels of security are equally important, and the design of fire precautions and evacuation strategies should not compromise security.

• Child and Adolescent Mental Health Services (CAMHS) Tier 4 in-patient services – these are defined as highly specialised provision that may be required for children and young people up to the age of 18, who may or may not be detained under the Mental Health Act.

2.42 Highly trained specialised nursing and clinical staff are always present when the premises are occupied and they will be trained to take the lead role in the evacuation of patients.

2.43 Should a fire start, it will be necessary to evacuate the sub-compartment of fire origin and the number of staff available will influence the speed of evacuation. Such evacuation may be progressive horizontal evacuation to other compartments or sub-compartments as described in Chapter 3.

• Dementia assessment – the term dementia is used to describe a syndrome that may be caused by a number of illnesses with progressive decline in multiple areas of function, including impairment of memory, reasoning, communication skills and the ability to carry out daily activities. As well as memory impairment, dementia might also include behavioural and psychological symptoms such as depression, psychosis, aggression and wandering.

2.44 Patients may exhibit behavioural problems that could impact on the fire and security

[HTM 05-02 – PDF page 28]

should be considered, with the additional caveat of any security measures required to ensure patient safety.

measures installed. Patients with an acute mental illness or learning disabilities have a history of generating unwanted fire signals. Tampering with fire doors is commonplace, and special attention must be paid to final exits.

Specific design requirements for the above premises

2.52 Sleeping accommodation should be in a separate compartment from day facilities.

2.45 The implications of this tampering are an increase in the number of false alarms and the potential for complacency amongst staff to the emergency signal. A security issue may also be created with regard to the control of patients and the possibility of unrestricted egress.

2.53 Accommodation in compartments providing sleeping accommodation should be limited to:

a. bedrooms;

b. bathrooms, WCs etc;

c. cleaners’ room;

d. a small office for staff on overnight duty

2.46 The potential to configure the alarm and detection system such that in the first instance only staff receive the alarm, can reduce adverse reactions from patients. A general alarm confined to the compartment or zone would only be activated as the evacuation strategy was implemented. Further guidance is provided in HTM 05-03 Part B.

(this may be an office or a recess off a circulation route);

e. linen stores.

2.47 Integration of the alarm and detection system with staff and patient monitoring and location systems can improve response times to alarm situations.

2.54 Where sleeping accommodation is segregated by sex, male and female bedrooms should be in separate sub-compartments.

2.55 The maximum number of beds in any sub-compartment, including swing beds, should be no more than 10.

2.56 Where “swing beds” are provided it should be possible to include the swing beds in either sub-compartment.

2.48 For security purposes, it is important that final exits do not release immediately on actuation of the alarm. The release mechanism should form part of the overall strategy for managing the evacuation. This gives control to the staff and increases the security of the facility. Some means of control should be provided such that these doors can be opened by staff, on confirmation of the fire signal, when it becomes necessary to evacuate to a designated (secure) assembly point.

2.57 Depending on the patients it may be necessary to maintain segregation during evacuation; where this is the case, the design of evacuation routes should ensure that this is always possible. This will also extend to secure places of safety away from the effects of fire, outside the building.

2.49 Should it become necessary to evacuate an entire facility or part thereof, adequate safe and secure external assembly points should be available.

2.58 Bedrooms:

a. All bedrooms should be classed as fire

2.50 Due to the intended occupancy, evacuation to an external assembly point would be a last resort only.

hazard rooms.

b. It may be necessary to provide the

2.51 When designing external escape routes that are intended for use by mental health patients, similar considerations to those above

potential for bedroom doors to be locked from the inside. However, if this is

[HTM 05-02 – PDF page 29]

2. Principles of fire safety in healthcare premises

access areas affecting the patient-access areas of healthcare premises.

2.61 Non-patient-access areas, for the purposes of this document only, are divided into the following:

required, they should be easy to open from the inside without recourse to a key. In addition, any locking device used should be easy to open from the outside of the room by means of a standard key issued to all staff.

a. Hazard departments: departments/

c. Where patients have restricted mobility,

are elderly or are suffering from dementia, moving the patients on their beds is likely to the most effective method of evacuation. Where this is the case, the design of evacuation routes should allow for bed evacuation and should be designed either:

management units that contain high fire loads and/or significant ignition sources. Hazard departments should be separated by distance from any patient- access areas and should not adjoin them, either horizontally or vertically, unless additional precautions are provided.

(i) to comply with Figure 1 below; or

b. Non-hazard departments: departments/

(ii) the architect or designer should

provide evidence to the client, fire officer and building control officer, that their design will permit bed evacuation; or

(iii) an alternative method of evacuation

management units that do not contain high fire load and/or significant ignition sources. Non-hazard departments may adjoin patient-access areas, either horizontally or vertically, provided they are separated from them by compartment walls and floors.

2.62 Patient-access areas should always be in different compartments from non-patient- access areas.

should be agreed that fully recognises the restricted mobility of the patients, the limitations of the proposed design and the availability of trained staff to safely manage the evacuation.

2.63 Areas and departments/management units should be located in accordance with Table 1 below.

2.59 Where communal bathrooms2 are provided, these should be designed as fire hazard rooms.

Staffing levels

Separation of patient-access areas from other parts of healthcare premises

2.60 In addition to the general requirement for progressive horizontal evacuation, healthcare premises should also be designed to minimise the possibility of fires from the non-patient-

2.64 The provision of an adequate number of staff who have received effective fire safety training is the best first line of defence against fire. This is particularly important when levels of activity in the building are reduced. The presence of trained staff who can respond quickly and effectively to any fire emergency is a vital factor in limiting the consequences of a fire, particularly where dependent patients are involved.

2.65 Article 15 of the Fire Safety Order requires the responsible person to:

a. produce an evacuation procedure;

2 Communal bathrooms allow unsupervised access and are distinct from bathrooms, which are normally kept locked, with patients only having access when supervised by staff. The former are generally provided in older premises where patient bedrooms are not provided with full en-suite facilities; the latter are generally provided in premises where patient bedrooms have full en-suite facilities (WC, washbasin and shower).

[HTM 05-02 – PDF page 30]

Door nib must allow

door leaf to open

substantially beyond

90 degrees if 1700 nominal doorset used

(1700)

ecw = 1550

1550 ecw required with clear corridor widths between 2150 and 2400.

1700 nominal doorset drawn

Door

nib

(650)

150 (100)

(2150) 150 (100)

2450 (2350)

Zone for handrail/ wall protection

Zone for handrail/ wall protection

Figure 1 Widths of doors and corridors to permit bed evacuation

Note: Further guidance is provided in Chapter 3 and Health Building Note 00-04 – ‘Circulation and

communication spaces’.

[HTM 05-02 – PDF page 31]

2. Principles of fire safety in healthcare premises

Separation from patient-access area

Normal dependency Very high dependency

Hazard area or department/ management unit

Atrium Refer to HTM 05-03 Part M Refer to HTM 05-03 Part M

Boilerhouse (main)1 60+ auto suppression Not allowed

Car park 60+ auto suppression Not allowed

Central staff change 60+ auto suppression

Commercial enterprises 60+ auto suppression Not allowed

Flammable store 60+ auto suppression Not allowed

Laundry 60+ auto suppression Not allowed

Local medical gas stores2 60+ ventilation Not allowed

Main electrical switchgear3 60+ auto suppression Not allowed

Main kitchens 60+ auto suppression Not allowed

Main stores 60+ auto suppression Not allowed

Medical records 60+ auto suppression

Pathology 60+ auto suppression

Pharmaceutical (manufacturing) 60+ auto suppression

Refuse collection/incineration 60+ auto suppression Not allowed

Sterile services department 60+ auto suppression

Works 60+ auto suppression Not allowed

Key:

“60” – May be adjacent but should always be separated by 60-minute fire-resisting construction. 60 minutes’ fire resistance may be reduced under certain circumstances (for example if sprinklers are fitted (see paragraphs 5.12–5.13)).

“60+ auto-suppression” – Preferably separate; however, if adjacent, it should be separated by 60-minute imperforate construction together with auto-suppression in the hazard department.

“Not allowed” – should not be located adjacent to very high dependency departments.

Notes:

1 Not applicable to small boilers/switchgear in plantrooms serving part of a building.

2 Main medical gas stores should always be located in separate buildings. Health Technical Memorandum 02-01 – ‘Medical gas pipeline systems’ gives guidance. Local medical gas stores should only contain sufficient quantity for daily use.

3 A medium or high voltage transformer, or switchgear room, or battery room serving a whole building or site.

Table 1 Requirements for the location and fire separation of fire hazard departments from patient-access areas

b. have sufficient staff to implement it; and

assumptions relating to patient evacuation can be realised by the available trained staff.

c. ensure that staff are adequately trained.

2.67 It is the responsibility of management to ensure that adequate numbers of staff will always be available and to devise suitable arrangements to provide for the safe evacuation of all relevant persons in accordance with the emergency evacuation plan. When requested they should be able to demonstrate that staffing levels are adequate to ensure the effective implementation of the emergency plan.

2.66 The emergency plan (see paragraphs 1.13–1.19) should detail the fire safety provisions to each patient area and the dependency of the patients within the area being considered. This information will enable the fire safety management procedures to detail the appropriate staffing levels required to undertake the evacuation of the area in the event of a fire; this information should be prepared as the design is being developed to ensure design

[HTM 05-02 – PDF page 32]

2.68 Staff should receive training in the methods of patient evacuation appropriate to the dependency of the patients and be familiar with the evacuation procedures at their place of work, and when requested, health service managers should be able to demonstrate that staffing levels are adequate at all times to ensure the safe evacuation of patients.