HTM 05-02: Appendix C: Doors and doorsets
[HTM 05-02 – PDF page 89]
Appendix C: Doors and doorsets
Fire doors should have the appropriate performance as indicated in Table C1. In
the table the doors are identified by their performance under BS 476-22 in terms of
Table C1 Location of fire doors
Location of door Minimum period of fire resistance in terms of integrity (minutes) when tested to BS 476-221
Minimum period of fire resistance in terms of integrity (minutes) when tested to European standards2
Sub-compartment wall FD30S E30 Sa
Fire hazard rooms FD30S E30 Sa
In a compartment wall FD30S – Single-storey healthcare buildings E30 Sa
E30 Sa
FD30S – Storeys above ground in healthcare buildings fitted with sprinklers
FD60S – elsewhere E60 Sa
To a protected shaft containing a stairway or escalator:
a. accessed from a hospital street FD30S E30 Sa
E30 Sa
b. elsewhere FD30S to each of the two sets of doors to the lobby
To a protected shaft containing a lift3:
a. accessed from a hospital street FD30 E30
E30 Sa
b. elsewhere FD30S to the doors from the circulation space to the lobby
FD30 from the lift car to the lobby E30
FD60S E60 Sa
To a protected shaft containing chutes, ducts and pipes
Within a cavity barrier FD30* E30
Notes:
1. To BS 476-22 (or BS 476-8 subject to paragraph 5 in Appendix A of Approved Document B).
2. The national classifications do not automatically equate with the equivalent classifications in the European column; therefore, products cannot typically assume a European class unless they have been tested accordingly.
Unless pressurisation techniques complying with BS EN 12101-6:2005 are used, all these doors (except those marked *) should also either:
(a) have a leakage rate not exceeding 3 m3/m/hour (head and jambs only) when tested at 25 Pa under BS 476-31.1; or
(b) meet the additional classification requirement of Sa when tested to BS EN 1634-3.
3. Lift doors to be tested to BS EN 81-58.
[HTM 05-02 – PDF page 90]
should be triggered by any of the following:
– the actuation of any automatic fire
detector within the compartment/ sub-compartment;
– the actuation of any manual
fire-alarm call point within the compartment/sub-compartment;
– any fault in the fire warning system
integrity for a period of minutes (for example FD30). A suffix (S) is added for doors where restricted smoke leakage at ambient temperatures is needed. Unless pressurisation techniques complying with BS EN 12101-6: 2005 are used, doors with the suffix “S” should also have a leakage rate not exceeding 3 m3/m/hour (head and jambs only) when tested at 25 Pa under BS 476-31.1. The method of test exposure is from each side of the doors separately, except in the case of lift doors, which are tested from the landing side only.
within the compartment/sub- compartment;
Door closers
– any loss of power to the fire warning
system;
Generally all fire doors should be fitted with an automatic self-closing device complying with BS EN 1154 or BS EN 1634-1, with the following exceptions:
• automatic door releases must be provided with a ready means of manual operation from a position at the door;
• fire doors to patients’ bedrooms in facilities providing in-patient mental health services;
• fire doors to bedrooms in in-patient accommodation for people with learning disabilities; and
• fire doors which are kept locked shut.
• each door fitted with an automatic door release should be closed at a predetermined time each night and remain closed throughout sleeping hours. If for reasons of management this is impracticable, it should be the specific responsibility of the fire warden (or other nominated member of staff) to operate the release mechanism at least once a week to ensure that:
– the mechanism is working
effectively;
With the exception of doors to stairways, it may be acceptable for fire doors to be held open on electrically operated door-release mechanisms provided that all of the following criteria can be satisfied:
– the doors close effectively onto their
frames.
Please note: the installation and operation of electro-magnetic hold open/swing free door closers should also satisfy similar criteria.
• the door-release mechanism should conform to BS 5839-3:1988 and BS 7273-4:2007 and be fail-safe (that is, in the event of a fault or loss of power, the release mechanism should be triggered automatically);
Identification
• all doors fitted with automatic door releases should be linked to the fire detection and alarm system;
• all automatic door releases within a compartment/sub-compartment
All fire doors, including each leaf of double doors, should be provided with an identification disc (except in mental health accommodation). The disc should be a minimum of 45 mm in diameter, clearly indicating the fire-resisting
[HTM 05-02 – PDF page 91]
Appendix C: Doors and doorsets
standard of the door (for example FD30s, FD60s etc).
Doors on escape routes
Door swings should not obstruct the circulation space or the designed width of the escape route. However, doors to cupboards etc that are normally locked may open onto circulation routes, but it is recommended that such doors should open through 180º to avoid obstruction.
Fire doors across escape routes providing alternative means of escape must be double- swing, and those across escape routes providing single direction of escape should open in the direction of escape.
Fire doors on escape routes should be side- hung or pivoted. Revolving doors should be avoided, but where they are used, they must easily convert to outward-opening doors; or there should be outward-opening doors adjacent to the revolving door, capable of allowing safe egress for the numbers of persons likely to use them. Turnstiles and shutters are not acceptable on escape routes and should not be used.
Fire-exit doors to rooms containing more than 60 people should open outwards from the room. Door swing direction for escape routes within mental health facilities should be reviewed on a risk assessment basis.
Fire doors across circulation routes should be fitted with glazed observation panels to a height of 500 mm above the threshold of the door.
Sliding doors are acceptable on escape routes provided they convert to outward-opening doors when subjected to reasonable pressure from any direction. In the case of powered sliding doors, they should in addition be provided with a monitoring system to ensure that they fail-safe to the fully open position in the event of a power failure.