HTM 03-01 A: _Hlk36670561 – General / _Hlk36670561 – Peripheral room type
[HTM 03-01 A – PDF page 178]
Appendix 8: Design of air- movement control schemes for operating theatres
General
an air-flow network be made (Figure A6) to collate all information. Flow rates, air- transfer devices etc should be entered as required. The remainder of this Appendix may be treated as reference data to assist in the various steps. The following symbols are used:
SS – supply air-flow rate for summer
temperature control;
A8.1 Standard operating suite design solutions are given in paragraphs 8.27–8.74 and Appendix 7. If these standard solutions cannot be used, the following procedure should be adopted, which will result in an acceptable design. Note that the method employed may equally be used to provide a design solution to a ventilated suite of rooms for any application.
SW – supply air-flow rate for winter
temperature control;
SD – supply air-flow rate for dilution of
bacterial contaminants;
SL – supply air-flow rate for heat loss;
SG – supply air-flow rate for heat gain;
ED – extract air-flow rate for dilution of
bacterial contaminants;
A8.2 The method is concerned with the calculation of air-flow rates to ensure that correct air movement occurs between rooms when any one door is open. Under most circumstances, the air quantities required for air-movement control will approximate to those for either temperature control or bacterial contaminant dilution. This flow rate is sufficient to control the effects of any slight reverse flows occurring when a door is opened.
SF – final supply air-flow rates
EF – final extract flow rates;
SAMC – air-supply flow rate for air-
movement control;
A8.3 The progression through the design procedure is shown in the air-flow design procedure chart (Figure A7) and is supported by worksheets WS1 to WS7 described in paragraph A8.4. It is recommended that a plan of the suite and
[HTM 03-01 A – PDF page 179]
Appendix 8: Design of air-movement control schemes for operating theatres
EAMC – air-extract flow for air- movement control;
(low pressure) (for example the Prep (lay- up) in standard layout 5 in Appendix 7).
LOUT – leakage air-flow rate outward;
Parallel/series multi-flow
LIN – leakage air-flow rate inward;
∑OUT – total air-flow rate outward;
∑IN – total air-flow rate inward.
A8.8 This is a room having a net surplus of supply or extract and with two or more doors. One or more doors will be to an area of equal cleanliness and need not be protected; hence, the flow may vary between inwards and outwards, the remaining door being to an area of greater or lesser cleanliness (for example the Prep (SPS) in standard layout 6 in Appendix 7).
Series multi-flow (unbalanced)
A8.4 To simplify the procedure, standard worksheets (WS1 to WS7) have been devised. For each operating suite, a set is required comprising one each of WS1, WS3, WS5, WS6a, WS6b and WS7, one WS4 for each corridor and one WS2 to cover each peripheral room. WS2 has five versions:
• WS2a single flow,
• WS2b parallel/series multi-flow,
A8.9 This is a room having a net surplus of supply or extract and with two or more doors. Air flows inwards through one or more doors and outwards through one or more doors.
• WS2c parallel multi-flow or series multi-flow (unbalanced);
Series multi-flow (balanced)
• WS2d series multi-flow (balanced); and
• WS2e bay (semi-open).
A8.10 This is a room as in paragraph A8.9 above, but having either no mechanical ventilation or no net surplus of supply or extract (for example an anaesthetic room).
Peripheral room type
Bay
A8.11 A room which has a permanent opening to the operating theatre may be considered as a bay off the latter (for example a scrub). Two categories exist:
A8.5 The rooms in the operating suite other than the operating theatre and corridor are referred to as peripheral rooms. Peripheral rooms have been classified according to the flows in and out. These room classifications are defined in paragraphs A8.6–A8.11.
Single flow
• open bay – the opening is larger than a normal single door opening. The bay may be considered as part of the main room;
A8.6 This is a room with only one door and a net surplus of supply or extract air.
Parallel multi-flow
• semi-open bay – the opening is no larger than a normal single door opening. In this case it is possible to protect the bay from the main room by provision of air supply or extract in the bay, or by passing air to or from another area.
A8.7 This is a room with two or more doors through each of which the air flows either outwards (high pressure) or inwards