HTM 03-01 A: _Hlk37000395 – Interventional imaging suites / _Hlk37000395 – Other application-specific design guidance
[HTM 03-01 A – PDF page 78]
anaesthetic room and the corridor but no transfer device between the anaesthetic room and the theatre.
Patients requiring full anaesthesia will normally be treated in a hybrid or conventional operating suite. The VSG should advise on the likely scope of use.
• The scrub should have an active extract as for a conventional operating suite but no pressure stabiliser between it and the corridor.
• The utility should be at negative pressure of not less than –5 Pa to the theatre and its corridor.
8.128 An interventional image suite may simply be a room containing the imaging equipment, an adjoining radiation protected control room or bay for staff and an equipment room for the imaging server. Support rooms for patient changing, sit recovery, toilets and a utility may also be needed.
• The corridor extract will be sized to cater for the air leakage from the preparation and anaesthetic rooms.
Overall, the ventilation scheme should ensure that all air supplied to the operating theatre is removed in the theatre. The theatre should be neutral (at the same pressure) to the corridor so that when the theatre exit door is open there is effectively no interchange of air between them. When the preparation or anaesthetic doors are opened, air flows from them into the theatre and not the other way.
8.129 Ventilation of the imaging room would be 10 ac/h with the room at a positive pressure to the corridor. Ceiling- mounted steelwork to support the imaging equipment may reduce the space available to install ventilation ductwork and compromise the supply terminal locations. This may mean that sidewall linear terminals are the only viable option. If fitted, their discharge velocity should not cause draughts and the direction vanes should be fixed or capable of being locked to prevent alteration during routine cleaning. Alternatively, a displacement ventilation scheme may be considered.
8.126 The theatre control panel, automatic control strategy and air handling unit will be as for a conventional operating suite.
Interventional imaging suites
8.130 A full “theatre style” control panel is not required, but a green light to show the ventilation is operational and a red one to show it is not should be provided.
8.131 Radiation shielding and warning notices may be required to ductwork where it penetrates ceilings, walls or floors to plantrooms or adjacent spaces to which staff may need access.
8.127 Interventional imaging refers to rooms in which surgical interventions are carried out guided by imaging equipment. The risk of infection by the airborne route is low as the surgical site is small, and sterile instruments tend to be unwrapped immediately before use. Anaesthetic gas or agents are used for pain relief or sedation.
[HTM 03-01 A – PDF page 79]
8.0 Specific healthcare department requirements
Other application-specific design guidance
Table 2 Treatment and procedure facilities
Application: Bronchoscopy, Endoscopy, Dental and General treatment facilities
Area/zone Reason for ventilation Typical design factors
Establish a clean airflow path – Supply terminal at high level at foot end of patient’s chair/couch and extract terminal at patient’s head level behind the chair/couch.
Bronchoscopy procedure room Control of exposure of staff to airborne pathogenic material discharged by the patient e.g. multi-drug-resistant tuberculosis (MDR-TB) during the procedure being undertaken. (COSHH Regs)
Control of exposure of staff to waste anaesthetic agents when used. (COSHH Regs)
Endoscopic procedure room As above and odour control
Design parameters Air change: 10 per hour Pressure regime: –5 Pa to corridor Noise level: 40 d(B)A Temp range: 20 to 25ºC BMS control Humidity: Floating; max 70%RH Air quality: BS EN 16798 - SUP2 Extract discharge – Discharge in safe position away from people or open windows. If no suitable position available treat the discharge in the same way as a LEV with a discharge stack 3 m above the roof line.
Establish a clean airflow path – Supply terminal at high level and extract terminal at low level near patient’s chair/ couch.
Dental treatment room Control of exposure of staff to airborne pathogenic material discharged by the patient during the procedure being undertaken. (COSHH Regs)
Control of exposure of staff to waste anaesthetic agents when used. (COSHH Regs)
As above
Emergency department resuscitation room
Design parameters Air change: 10 per hour Pressure regime: Neutral to corridor Noise level: 40 d(B)A Temp range: 20 to 25ºC BMS control Humidity: Floating; max 70%RH Air quality: BS EN 16798 - SUP2
General treatment room Comfort conditions only
All of the above rooms are suitable for aerosol-generating procedures (AGPs)
[HTM 03-01 A – PDF page 80]
Table 3 Airborne protective facilities
Applications: Level 2 and 3 critical care areas, bone marrow transplant (BMT), oncology, organ and tissue transplant units
Area/zone Reason for ventilation Typical design factors
Note: Level 2 & 3 Critical care areas should be treated identically in terms of service provision as their only difference is the staff- to-patient ratio.
Level 2 or 3 critical care individual room Protection of patients from airborne organisms and fungal spores
Level 2 or 3 critical care open bays As above
Supply only in patient’s room and cascade air out via door undercut, transfer grille or pressure stabiliser through rooms of a lower classification.
Design parameters Air change: ≥10 per hour Pressure regime: +5 Pa to general area Noise level: 35 d(B)A Temp range: 20 to 25ºC BMS control Humidity; Floating; max 60%RH Final filter; BS EN 1822 – EPA10
Bone Marrow Transplant (BMT) unit Protection of patients from airborne organisms and fungal spores
Supply only in room and cascade air out via door undercut, transfer grilles or pressure stabilisers through rooms of a lower classification.
Note: Patient(s) will have a very poor immune system (neutropenia) so will be particularly vulnerable to infection by the airborne route.
Haematology/Oncology ward As for BMT
Organ and Tissue Transplant unit As for BMT
Design parameters Air change: ≥10 per hour Pressure regime: +15 Pa to corridor Noise level: 35 d(B)A Temp range: 20 to 25ºC BMS control Humidity: Floating; max 60%RH Final filter: BS EN 1822 – EPA12
For individual room airborne protective isolation, see guidance on PPVL rooms given in Table 4.
See also Health Building 04-01 – 'Adult in-patient facilities' and Health Building 04-02 – 'Critical care units'.
[HTM 03-01 A – PDF page 81]
8.0 Specific healthcare department requirements
Table 4 Airborne isolation facilities
Applications: Isolation rooms category 2 & 3, Infectious disease units, Containment level 3 rooms
Area/zone Reason for ventilation Typical design factors
Category 3 isolation room
Category 2 isolation room Protection of staff and all other building occupants from airborne organisms dispersed by a patient with an infectious disease.
See Health Building Note 04-01 Supplement 1
Extract only in patient’s room and en-suite. Supply air from corridor passing into room via door undercut, transfer grille or pressure stabiliser. Alternatively the patient’s room may have a supply and extract provided they are interlocked to ensure that the room is always at –ve pressure with regard to the corridor.
Design parameters: Air change: ≥10 per hour Pressure regime: –5 Pa to general area Noise level: 35 d(B)A Temp range: 20 to 25ºC BMS control Humidity: Floating; max 60%RH Air quality: BS EN 16798 – SUP2
Positive pressure ventilated lobby (PPVL) isolation room Universal isolation facility
Supply in lobby flowing through a pressure stabiliser to patient’s room and on via a door undercut or transfer grille to an extract in the en-suite.
Protection of building occupants from patients who may be infected and protection of patients who may be immunocompromised and protection for patients with both conditions.
See Health Building Note 04-01 Supplement 1
Design parameters: Bedroom air change: ≥10 per hour Lobby pressure: +10 Pa to corridor Bedroom pressure: Neutral En-suite pressure: –ve Comfort parameters as above Air quality: BS EN 16798 – SUP2 With facility to fit BS EN 1822 – EPA12
Containment level 3 laboratory Protection of occupants in adjoining spaces from airborne bio-hazards
For design details see the Medical Research Council’s “Standards for containment level 3 facilities”
Category 4 facility Design advice will be provided by the client
See also Health Building 04-01 – 'Adult in-patient facilities' and Health Building 04-02 – 'Critical care units'.
[HTM 03-01 A – PDF page 82]
Table 5 Maternity facilities
Application: Obstetrics theatre, delivery rooms, nursery, neonatal intensive care and special care baby units
Area/zone Reason for ventilation Typical design factors
Obstetrics theatre Protection of patients from airborne organisms and fungal spores.
Control of exposure of staff to waste anaesthetic agents (COSHH Regs)
Ventilation design parameters as for a conventional operating suite. System should normally be at "set back” with a minimum temperature of 18ºC and be able to attain full operating conditions within 5 minutes of triggering the system
Delivery room Control of exposure of staff to waste anaesthetic agents. (COSHH Regs)
Establish a clean airflow path – Supply terminal at high level at foot end of bed and extract terminal at low level at head end of bed.
Delivery room with birthing pool As for standard delivery room above
Specials delivery room As for standard delivery room above
Design parameters: Air change: 10 per hour Pressure regime: Neutral to corridor Noise level: 35 d(B)A Temp range: 20 to 25ºC local control Humidity: Floating – max 70%RH Air quality: BS EN 16798 – SUP2
Nursery Comfort conditions only
Standard supply and extract
Protection of neonates from airborne organisms and fungal spores.
Neonatal intensive care unit or special baby care unit (SCBU)
Neonates are kept in incubators but may be removed for feeding, changing etc. so local temperature control and ensuring a draught-free environment is essential.
Design parameters: Air change: 10 per hour Pressure regime: +5 Pa to corridor Noise level: 45 d(B)A Temp range: 20 to 28ºC local control Humidity: Floating – max 70%RH Air quality: BS EN 16798 – SUP1 (Filter grade depends on ODA category – see the Specialised Ventilation for Healthcare Society’s (2018) SVHSoc.02)
N.B. This is a critical healthcare facility and consideration should be given to system resilience and/or how suitable alternative accommodation may be provided in the event of a ventilation system failure.
[HTM 03-01 A – PDF page 83]
8.0 Specific healthcare department requirements
Table 6 Pharmacy facilities
Applications: pharmacy aseptic suite, gene therapy, radiopharmacy, support rooms
Area/zone Reason for ventilation Typical design factors
Aseptic suite Clean room
Protection of product during and after processing.
Protection of the wider environment from cytotoxic agents and antibiotics.
EUGGMP standards (European Commission, 2011) apply and the Medicine Act if the facility is licensed.
Control of exposure by the airborne route to staff of substances during and after processing products. (COSHH Regs).
Note: While this application is a critical facility, it is usual to have a plan in place to decant to another site in the event of a ventilation system failure
Supply only in clean room and cascade air out via pressure stabilisers through rooms of a lower classification or where there are multiple clean rooms, a balanced supply and stable cascade out. Thimble extract may be provided for class 3 safety cabinets depending on the location of room within the building. Note: Advice from the client’s lead pharmacist should be sought prior to engaging in detailed design. Design parameters: Air change: ≥20 per hour Pressure regime: +15 Pa between unclassified rooms and +10 Pa between classified rooms Noise level: 45 d(B)A Temp range: 20–24ºC BMS control Humidity: Floating – max 60%RH Final filter: BS EN 1822 – HEPA14
Gene therapy clean room As above, plus protection of the wider environment from product
As per clean room above plus negative- pressure access lobby and controlled exhaust
As per clean room above
Radiopharmacy clean room As for standard clean room with additional requirements of the Ionising Radiation (Medical Exposure) Regulations
Non-sterile stores and support rooms Comfort conditions only
[HTM 03-01 A – PDF page 84]
Table 7 Sterile services
Application: Sterile services department, endoscope reprocessing unit
Area/zone Reason for ventilation Typical design factors
Sterile services department, Inspection, assembly and packing room (IAP)
Protection of instrument from gross contamination during packing.
Supply only in clean room and cascade air out via pressure stabilisers through rooms of a lower classification.
EUGGMP standards (European Commission, 2011) apply and the Medicine Act if the facility is licensed.
Note: While this application is a critical facility, it is usual to have a plan in place to decant to another site in the event of a ventilation system failure
Design parameters: Air change: ≥20 per hour Pressure regime: +15 Pa between unclassified rooms and +10 Pa between classified rooms Noise level: 45 d(B)A Temp range: 20–24ºC BMS control Humidity: Floating – max 60%RH Final filter: BS EN 1822 – EPA10
–5 Pa to corridor Air change: 10 ac/h General extract and extract located along the rear of the wash bench and sinks.
Wash room Control of exposure by the airborne route to staff of biological material liberated during the preliminary handling and washing of used surgical instruments (COSHH Regs)
6 ac/h supply ventilation only +5 Pa above surrounding rooms
Sterile pack store To prevent casual airborne contamination of the outside of sterile packs
Non-sterile stores and support rooms Comfort conditions only
–5 Pa to corridor Extract air 10 ac/h Extract location along the rear of the endoscope wash bench and sinks.
Used endoscope processing – wash room Control of exposure by the airborne route to staff of biological material liberated during the washing of used scopes (COSHH Regs)
+5 Pa to corridor Supply 10 ac/h
Clean endoscope storage To prevent casual airborne contamination of the outside of the scope
Pressure stabiliser located in wall above endoscope washer-disinfector discharging into wash room.
See Health Building Note 13 – 'Sterile services department' and Health Technical Memorandum 06-01 – 'Decontamination of flexible endoscopes'.
Alternatively, see Health Technical Memorandum 06-01 Part C – 'Operational management' for guidance on how to store flexible endoscopes.