[HTM 03-01 A – PDF page 53]

7.0 Environmental control

the event of a fire in the AHU or smoke being drawn into the system from an outside source, it should cause the AHU to shut down and the main supply-air damper and system fire damper(s) to close.

7.20 The selection of temperature set-point for each room or zone may be by a control facility in the room/zone or be carried out remotely at the control panel or BMS. Where the control device is mounted within the room/zone and is adjustable by the user, it should be marked either “raise” and “lower” or “+” and “–”. It should control within a specified temperature range to suit the user requirement with a control tolerance of ±1 K. All other control set- points should be selectable either on the control panel or at the BMS interface.

7.18 In critical areas a ventilation control panel should be mounted at the main entrance of the area that the ventilation serves (see Health Technical Memorandum 05-02 for more detailed guidance). Access to the panel should be restricted to the fire officer and appointed site AP(V). It should include independent on/off controls and an indication of the status of the supply and extract systems. A notice should be affixed to the control panel stressing the need to liaise with departmental staff before switching off fan units

7.21 Where local control is provided, an indication of temperature will be required locally or at a staff base (if appropriate) using an analogue or digital indicator. The indicator should be large enough to be read from the normal working position (for example at the operating table in a theatre). This may be mounted in a supervisory control panel, with the signal repeated on the main system control panel or BMS. It is important that this indicator displays the actual measured temperature and not the selected temperature.

Alarms and indication

7.22 Supply and extract systems should include indicator lamps on the control panels to confirm the operational status of each system. Where the usage is on a regular daily pattern, time control with a user-operated, timed manual override should be provided.

In certain critical care areas, it is preferable to maintain the supply ventilation in case of a fire within the area. For example, in an operating department, while undergoing surgery, the patient cannot always be easily moved without significant risk. In the event of a fire in a staff or support area of the department, or adjoining zone, the continued supply of air to a theatre will maintain it at a positive pressure and protect the patient and staff from the effects of smoke. This will allow time for the patient to be stabilised so that they can be safely evacuated if necessary.

User requirements

Room temperature control

7.23 Where a system is provided for a particular space, the indicator should be in, or immediately adjacent to, that space, and local controls should be provided with permanent labels clearly defining their function (for example isolation suites).

7.24 If room differential pressure gauges are required, they should be mounted directly adjacent to the entry door of the room to which they apply at a height of 1.5 m above floor level so that they are in

7.19 The limits for room temperature set- point are generally between 18ºC and 22ºC depending on the particular application. In some specialised applications (for example, operating departments), the user may require a wider range of adjustment (see Chapter 8).

[HTM 03-01 A – PDF page 54]

the eyeline of staff entering the room. If a mechanical gauge is fitted, it should have a green sector to indicate the acceptable normal pressure range. If electronic, it should have a permanent label affixed underneath it giving the normal acceptable pressure range.

For specific departmental control parameters, see Chapter 8. For plant controls see Chapter 9.