HBN 00-09: 3.0 Designing a healthcare facility: issues to consider – Examples of design principles / 3.0 Designing a healthcare facility: issues to consider – Sizing/space
[HBN 00-09 – PDF page 18]
3.0 Designing a healthcare facility: issues to consider
3.0 Designing a healthcare facility: issues to consider
Examples of design principles
Design to facilitate cleanliness & cleaning
• Use finishes that are impervious, smooth and seamless, as far as practicable.
• Run hard flooring up the walls for a short distance to provide an easy-to-clean coving.
• Eliminate or minimise dead-legs and blind ends in water systems, both in the original design and as the systems are modified.
• Consider hands-free operation of utilities (for example, sensor taps, automatic lights, movement sensors for toilet flushes etc).
• Consider hands-free operation of other facilities (for example, automatic doors, proximity-sensors etc).
• Consider integral blinds as an alternative to curtains at internal windows.
Encourage desired behaviour (for example, tidiness, hand hygiene)
• Provide sufficient space for activities to take place and to avoid cross-contamination between adjacent bed spaces.
• Provide sufficient storage for patients’ possessions and for all supplies to discourage clutter.
• Ensure proper segregation and management of waste, including clinical waste and linen.
• Provide sufficient domestic waste receptacles.
• Provide bedside waste disposal facilities for patient use.
• Design-out unnecessary horizontal surfaces (for example, window sills) in order to discourage clutter.
• Provide enough wash-hand basins and antimicrobial hand-rub dispensers.
• Plan for and deliver good separation of clean and dirty activities.
• Provide sufficient space for storage and preparation of cleaning equipment and materials.
• Provide suitable facilities for cleaning of equipment.
Design for easy cleaning
• It is always best practice to maintain a visibly clean environment that is free from dust and soilage, and acceptable to patients, their visitors and staff.
• Good design can make cleaning immeasurably easier, for example:
– Use finishes that are easy to clean.
– In clinical areas, flooring should be seamless and smooth, slip-resistant, easily cleaned and appropriately
wear-resistant.
– Use threshold matting on all external entrances. The type should allow for expected through traffic and easy
cleaning.
– Supply pipework should always be concealed.
• There may be pressure to choose the cheapest products/design. Attention to whole-life costs, including the costs of cleaning and maintenance, is important. Consult with the IPC team before purchase/on planning.
[HBN 00-09 – PDF page 19]
Important
The IPC team should be consulted throughout a building or renovation project and their advice and recommendations taken account of and documented.
c. En-suite single-bed room – as (b) but with
en-suite shower, WC and wash-hand basin.
d. Special ventilated isolation room – this is as
3.1 The recommendations in this section should be applied to the planning, design and maintenance of all healthcare buildings – both new build and refurbishments. They offer a planning checklist that can be used throughout the design and planning process. Not all items will need to be included in every project, but using the checklist will ensure areas with IPC implications are not missed. Timing will vary from project to project but refer to Chapter 2 for the sequence of the project process.
(c) but with a ventilation system that prevents uncontrolled escape of infectious aerosols from the room to adjacent areas. It can also provide a degree of dilution of infectious aerosols in the room for the safety of staff and visitors. The room should have extract ventilation that exceeds its supply, such that gaps in its fabric leak inwards not outwards.
e. Special ventilated isolation suite – as (d) but
3.2 The IPC team should have an integral role in ensuring other members of the project team are appropriately informed of any prevention and control-of-infection issues that may arise when:
with a lobby.
f. Isolation facilities – an umbrella term used
• an initial site is being considered for development;
in this document for room types (b)–(e).
• the healthcare facility is being designed;
• the healthcare facility is being constructed or undergoing refurbishment;
For design guidance on critical care areas, see Health Building Note 04-02 – ‘Critical care areas’.
• the healthcare facility is operational.
For guidance on mental health units, see Appendix 1.
3.3 The participation of the IPC team in all phases of planning and construction and renovation is essential.
3.4 For the purposes of this document, the following terminology is used:
a. Multi-bed room – this is a room that
contains more than one bed. It is best practice for multi-bed rooms to have both en-suite WC/shower and doors to the main ward area.
Sizing/space 3.5 The provision of sufficient space in clinical areas, particularly for each bed space, is one of the most important considerations in the planning and design of in-patient accommodation. A risk-based approach should be taken to ensure that the environment is appropriate for carrying out clinical activities and undertaking manual handling operations while maintaining a good standard of infection control.
b. Single-bed room – this is a room with space
for one patient and usually contains as a minimum: a bed; locker/wardrobe; and clinical wash-hand basin plus a small cupboard with worktop. (Note: single-bed rooms without en-suite sanitary facilities are not recommended.)
3.6 Spacing should take into account the amount of, and easy access to, equipment around the bed area and access for staff to clinical wash-hand basins. The principle should be to maintain sufficient space for activities to take place and to avoid cross- contamination between adjacent bed spaces. The exact space needed will vary according to numbers
[HBN 00-09 – PDF page 20]
3.0 Designing a healthcare facility: issues to consider
and activity of staff and type of patient (see ‘Recommendations’ after paragraph 3.12).
not have to sleep in the same room or share toilet and washing facilities. Patients should not have to pass through areas used by the opposite sex to reach their own facilities.
3.7 Mode of transmission of infection should also be taken into account. This includes:
3.12 Same-sex accommodation can be provided in:
• direct transmission;
• same-sex wards, where the whole ward is occupied by men or women only;
• single rooms;
• indirect transmission via fomites (for example, articles such as hoists, mobile X-ray units etc); and
• splash, droplet and airborne transmission.
• mixed wards, where men and women are in separate bays or rooms.
Recommendations
3.8 The route of spread of infection is a basic concept in preventing cross-infection, and spacing has direct implications for the prevention of infection.
Patient groups 3.9 Floor/bed space is influenced by the type of healthcare facility and the type of patient care. There are four distinct patient groups:
• The provision of sufficient space in clinical areas, particularly for each bed space, is one of the most important considerations in the planning and design of in-patient accommodation. A risk-based approach should be taken to ensure that the environment is appropriate for carrying out clinical activities and undertaking manual handling operations while maintaining a good standard of infection control. Health Building Note 04-01 – ‘Adult in-patient accommodation’ states:
• patients requiring acute care, which includes trauma, multi-organ failure, medical emergencies, planned major surgery and other life-threatening emergencies plus obstetric and neonatal care;
• patients with chronic conditions or sub- acute conditions;
“Ergonomic studies have established that most activities carried out at the bedside can be accommodated within the dimensions 3600 mm (width) × 3700 mm (depth). This represents the clear bed space and does not include space for fixed storage, preparation and worktops.”
• patients using mental health or learning disability in-patient services (note: this guidance does not apply to domiciliary care services that provide support in people’s own homes);
• patients requiring ambulatory care, which includes diagnostic services, day surgery, minor injuries and attendance at primary care facilities and walk-in centres.
• For IPC reasons, it is imperative that staff are able to attend to one patient without impinging on the bed space or equipment of a neighbouring patient. In the majority of cases, the dimensions in Health Building Note 04-01 should be adequate (although bed spaces for critical care areas need to be greater for reasons of circulation space and the equipment used in these areas).
3.10 The first three patient groups will require in- patient care. The volume of care and the degree of intervention, diagnostic equipment and movement of staff around the patient dictates the bed space needed.
• It is also important that the physical environment complies with disability access requirements and does not compromise the privacy and dignity of patients.
• Spacing should take into account the amount of and easy access to equipment around the bed area and access for staff to clinical wash-hand basins.
Privacy and dignity: same-sex accommodation 3.11 The need to deliver the highest standards of privacy and dignity applies equally to all areas of a healthcare facility. Achieving these high standards will usually mean ensuring that men and women do