[HBN 00-09 – PDF page 21]

Isolation facilities

• the storage of supplies retained in the room (for example, PPE);

See paragraph 3.4 for definitions.

• personal clothing and possessions (see also Appendix 1 on mental health settings).

3.21 In accident & emergency departments, a dedicated room should be provided for patients with a known or suspected infectious disease. If airborne isolation is required, this room should be at negative pressure to the corridor; a lobby is not required. This room should also be suitable for general use when not required for isolation (see Health Building Note 15-01 – ‘Accident & emergency departments’).

Note:

The role of isolation facilities in preventing cross-infection 3.13 The primary aim of IPC is to prevent the spread of infection between patients, visitors and staff by control or containment of potentially pathogenic organisms. Many of these organisms can be controlled by basic IPC practices such as hand hygiene and environmental cleanliness, and this can be facilitated by single-bed room isolation. A small proportion of patients requiring isolation will require special ventilated isolation facilities.

3.14 The key to effective isolation on general wards is the provision of sufficient en-suite single-bed rooms to prevent patients known to be a risk for spreading infections being cared for in open ward areas. Single rooms reduce the risk of cross-infection for non-airborne diseases. Most patients needing segregation/isolation on general wards can be isolated effectively in en-suite single rooms.

It may be necessary to cohort-nurse a group of infectious patients in a multi-bed room if insufficient single-bed rooms are available. This can be more easily achieved where wards are divided into two- or four-bedded rooms with en- suite sanitary facilities, which can be isolated further by closure of doors to the areas. When IPC guidelines are adhered to, research has demonstrated that cohort-nursing can successfully control and contain infection in hospital facilities.

3.15 A risk assessment should be used to inform decisions regarding which patients to nurse in single- bed rooms. Healthcare providers should audit the use of en-suite single-bed rooms to determine where further local requirements and adaptations are greatest.

Design 3.22 Health Building Note 04-01 provides guidance on en-suite single rooms.

3.16 Multi-bed rooms can also be used to cohort infectious patients if they have an en-suite WC and shower, and a door to the main ward area. The possible need for this should be considered at the design stage.

3.23 Health Building Note 04-01, Supplement A – ‘Isolation facilities for infectious patients in acute settings’ provides guidance on the facilities required for isolating infectious patients on acute general wards (source isolation). It also provides guidance on the ventilation parameters for a special ventilated isolation room/suite.

3.17 Clinical wash-hand basins should be provided in addition to the general wash-hand basin provided for patients.

3.18 Storage of, and ready access to, clean PPE is important to encourage its use plus appropriate waste receptacles for its disposal once worn.

Ceilings 3.24 Removable ceiling tiles are not advised for special ventilated isolation rooms/suites.

3.19 Gloves and aprons should be sited outside single-bed rooms, ideally in lobbies.

Doors 3.25 Doors are critical to the design of a special ventilated isolation room/suite. For specific guidance on source isolation, refer to Health Building Note 04-01, Supplement A.

3.20 Additional storage facilities will be required for the care and treatment of patients in isolation facilities, especially if the isolation is likely to last for some time:

[HBN 00-09 – PDF page 22]

3.0 Designing a healthcare facility: issues to consider

Wash-hand basin design

Lobbies 3.26 Lobbies facilitate staff compliance with hand- washing and use of PPE. They may also be essential with some types of special ventilated isolation rooms.

See also Health Building Note 00-10 Part C – ‘Sanitary assemblies’ and Health Building Note 00-02 – ‘Sanitary spaces’.

Clinical wash-hand basins 3.29 The dimensions of a clinical wash-hand basin should be large enough to contain most splashes and therefore enable the correct hand-wash technique to be performed without excessive splashing of the user. This can also occur if the water outlet is placed too high above the basin.

Engineering requirements for special ventilated isolation rooms/suites 3.27 Planned maintenance and revalidation – maintenance and revalidation programmes should be established for special ventilated isolation rooms to ensure the design criteria are maintained and met at all times. Although it is impossible to give specific maintenance frequencies, each unit should be included in a planned preventative maintenance that includes pressure/air flow monitoring equipment.

Recommendations

3.30 Clinical wash-hand basins should be wall- mounted using concealed brackets and fixings. They should also be sealed to a waterproof splash-back to allow effective cleaning of all surfaces.

• Single-bed rooms with en-suite sanitary facilities are optimum for infection prevention.

3.31 They should not have a plug or a recess capable of taking a plug. A plug allows the basin to be used to soak and reprocess equipment that should not be reprocessed in such an uncontrolled way.

3.32 Clinical wash-hand basins should not have overflows, as these are difficult to clean and become contaminated.

• There should be sufficient en-suite single-bed rooms to prevent patients known to be a risk for spreading infections being cared for in open ward areas. Healthcare providers should audit the use of en-suite single-bed rooms to determine where further local requirements and adaptations are greatest.

3.33 Taps should not be aligned to run directly into the drain aperture, as contamination from the waste outlet could be mobilised (see Health Building Note 00-10 Part C).

• The provision of additional isolation facilities should be considered when designing new healthcare buildings and renovating existing buildings.

Hand-hygiene facilities

Note:

3.34 Healthcare providers should have policies in place ensuring that clinical wash-hand basins are not used for other purposes such as emptying of patient bathing water, as this may transfer strains to the water supply system where they can colonise existing biofilms.

See also Appendix 1 on mental health settings.

This section should be read in conjunction with paragraphs 3.178–3.190 on safe hot and cold water systems.

General wash-hand basins 3.35 All en-suite facilities should have a wash-hand basin for use by patients and their visitors.

3.36 All toilet facilities should have a wash-hand basin.

3.37 Overflows should not be provided as these are difficult to clean and become contaminated.

3.28 Compliance with hand-hygiene guidelines can be improved by conveniently placed and well- designed hand-hygiene facilities. The importance of facilities to encourage and facilitate good hand- hygiene practices should be high on the list of priorities when designing and planning new healthcare premises or refurbishment of existing premises is being undertaken.

[HBN 00-09 – PDF page 23]

3.38 Taps should not be aligned to run directly into the drain aperture.

wash-hand basin for personal hygiene in the en-suite facility in addition to the clinical wash-hand basin in the patient’s bedroom.

3.39 All general wash-hand basins should be sealed to a waterproof splash-back.

See also Appendix 1 on mental health settings.

• In intensive care and high dependency units (critical care areas), a clinical wash- hand basin should be available by each bed space. It should be noted, however, that under-usage of basins encourages colonisation with Legionella and other microorganisms. Designers should be aware of this and, accordingly, should balance ease of staff hand-washing with the avoidance of under-used wash-hand basins (see also Health Technical Memorandum 04-01 – ‘Addendum: Pseudomonas aeruginosa – advice for augmented care units’).

Clinical wash-hand basin provision 3.40 All clinical wash-hand basins should be accessible and should not be situated behind curtain rails. Inconveniently located or insufficient clinical wash-hand basins are two of the main reasons that healthcare staff do not comply with hand-hygiene protocols. There is a need to review the numbers and placement of clinical wash-hand basins as well as their dimensions (see Health Building Note 00-10 Part C; Health Building Note 00-02; and Health Technical Memorandum 04-01 – ‘Addendum: Pseudomonas aeruginosa – advice for augmented care units’).

• Two clinical wash-hand basins in multi-bed rooms (note that there should be no more than four beds in a multi-bed room in line with Health Building Note 04-01).

For guidance on mental health settings, see Appendix 1.

3.41 Hand-hygiene facilities should be readily available in all clinical areas. There should be sufficient numbers and appropriate sizes of clinical wash-hand basins to encourage and assist staff to readily conform to hand-hygiene protocols.

3.44 In primary care and out-patient settings, where clinical procedures or examination of patients/clients is undertaken, a clinical wash-hand basin should be close to where the procedure is carried out (see Health Building Note 00-03 –‘Clinical, clinical support and specialist spaces’).

3.45 Health Building Note 00-10 Part C also gives details of sanitary assemblies for other areas such as kitchens and patient wash areas.

3.42 The location and provision of clinical wash- hand basins should ensure that they are all readily available and convenient for use. Having a clinical wash-hand basin easily available at all times is more important than compliance to a precise bed-to-basin ratio. For example, in a multi-bed room, if two clinical wash-hand basins are placed side-by-side, both on the same side of the entrance, only the one closest to the entrance will get significant use – the other will form a dead-leg in the water distribution system. While it may be marginally more complex in terms of plumbing, there should be one clinical wash-hand basin on each side of the entrance or at opposite sides of the room.

Water/taps 3.46 Health and safety regulations (The Workplace (Health, Safety and Welfare) Regulations, 1992) require that both hot and cold running water should be available in areas where employees are expected to wash their hands.

3.43 Guidelines for the appropriate numbers of clinical wash-hand basins in clinical areas are given in Health Building Note 04-01 and Health Building Note 11-01 – ‘Facilities for primary and community care services’. To encourage good practice and to give reasonable access, it is recommended that:

3.47 Hands should always be washed under running water; mixer taps allow this to be practised in safety in healthcare settings where hot water temperatures may be high to control Legionella (see Health Technical Memorandum 04-01).

• A minimum of one clinical wash-hand basin in each single-bed room is required. En- suite single-bed rooms should have a general

[HBN 00-09 – PDF page 24]

3.0 Designing a healthcare facility: issues to consider

and advise on the position of these units in clinical areas.

3.48 Taps can be lever- or sensor-operated and should be easy to turn on and off without contaminating the hands.

Hand drying 3.57 Paper hand-towel dispensers should be conveniently placed by all wash-hand basins (clinical and non-clinical).

3.49 Taps discharging directly into a drain hole can cause splashing, which could disperse contaminated droplets. The tap outlet flow should not discharge directly into the waste aperture.

3.58 The use of paper towels in rolls should be discouraged; they are difficult to tear off without contaminating the remaining roll.

3.50 Non-TMV taps (commonly used in kitchens and on sinks in cleaners’ rooms/dirty utilities) allow the user free rein to determine the temperature of the water delivered at the point of use; however, a risk assessment should be undertaken first.

3.59 Fabric towels are a source of cross- contamination and are not recommended in clinical areas.

3.51 Swan-neck tap outlets are not recommended, as they do not empty after use. Similarly, strainers, aerators and flow restrictors should not be used as they become colonised with bacteria.

3.60 Hot-air hand dryers reduce paper waste and may be considered for use in public areas of healthcare facilities, but should not be installed in clinical areas as they are noisy and could disturb patients.

3.61 Hands-free waste bins, with appropriate colour- coded waste bags, should be provided by each wash- hand basin.

Taps in augmented care settings 3.52 For the augmented care setting, the choice and type of water outlets is important and should be based on a risk assessment of infection-control and scalding issues. There is some evidence that the more complex the design of the outlet assembly (for example, some sensor-operated taps), the more prone to P. aeruginosa colonisation the outlet may be (see Berthelot et al. 2006).

Sinks and disposal facilities 3.62 Using sinks for both hand-washing and the cleaning of equipment should be discouraged as this will significantly increase the risk of hand and environmental contamination. Dirty utility rooms should contain a:

• sluice for disposing of body fluids and patients’ wash-water;

• separate sink for cleaning equipment;

3.53 In intensive care and other critical care areas, where patients are unlikely to be able to use the wash-hand basins, the installation of non-TMV mixing taps may be the preferred control option following a risk assessment (see Health Technical Memorandum 04-01 ‘Addendum – Pseudomonas aeruginosa: advice for augmented care units’).

• clinical wash-hand basin.

3.63 Contaminated fluids such as patients’ wash- water should not be emptied down clinical wash- hand basins in adjacent ward areas.

Soap dispensers 3.54 Liquid soap dispensers should be wall-mounted at all wash-hand basins and be designed to be operated without contamination from the user’s hands coming into direct contact with the dispensing mechanism.

3.55 Dispensers should not be refillable but be of a disposable single-cartridge design (see also Appendix 1 for guidance on mental health units).

3.64 Disposal facilities should be provided in areas where dirty wastewater is disposed (for example, dirty utility rooms and cleaners’ rooms/areas for cleaning equipment). See Health Building Note 00- 10 Part C – ‘Sanitary assemblies’ for further guidance.

3.56 Antimicrobial hand-rub dispensers should be available at the point of patient care, subject to local risk assessment. Users and IPC teams should liaise