HBN 00-04: 8 Doors
[HBN 00-04 – PDF page 46]
8 Doors
Introduction
Threshold
8.9 A step or threshold should be avoided at doorways.
8.1 This chapter provides guidance on the design of internal doorsets in circulation and communication spaces.
8.10 Where a threshold is unavoidable on internal doors (for example doors with acoustic seals), its maximum height should be 10–13 mm.
8.2 See Health Building Note 00-01 – ‘General design principles’ for guidance on doors and frames.
8.11 A threshold in excess of 5 mm should be chamfered or rounded.
Approach
8.12 Rubber thresholds are the most easily traversed by wheelchairs and pushchairs.
8.3 A level area is required in front of doors to allow people to stand/park a wheelchair/pushchair whilst manoeuvring the door.
Door opening width
8.13 The key issue with regard to access through a door is the effective clear opening width (ecw) of the door(s) rather than the doorset size.
8.4 Generally, doors should open away from areas with high traffic flow towards areas with a lower traffic flow. However, this will be influenced by the requirements of means of escape (see paragraph 3.4).
8.5 Clear space should be provided at the latch side of each door to provide access to the door handle and allow a person to wait whilst someone comes through the door in the opposite direction.
8.14 The ecw for a swing door is the available width measured at 90 degrees to the plane of the doorway clear of all obstructions (such as protruding ironmongery) when the door is opened through 90 degrees or more. See Approved Document M (2013), Diagram 9.
8.6 Where there is high usage it will be necessary to provide a waiting space on both sides of the door.
8.7 The following clear spaces should be provided:
8.15 The ability of the door to open through greater than 90 degrees will depend upon the size of the door nib and the extent of any protruding ironmongery.
• 600 (450) mm to the latch side of the door, when the door opens towards a person using it;
Note
• 450 (300) mm to the latch side of the door, when the door opens away from a person using it;
The door nib is the length of wall between the edge of the structural door opening and a wall running, generally, perpendicular to the one incorporating the door. See Figures 32–36.
• 600 (450) mm to the latch side, on both sides of the door, where doors swing in both directions.
Single doors
8.8 Doors in the corner of spaces/rooms should be hung with the hinges nearest to the corner of the room so that the door rests alongside the wall when open. This assists people with wheelchairs/ pushchairs and/or mobility difficulties to manoeuvre effectively and pass through the door.
8.16 For internal single doors, an ecw of 850 mm (minimum 800 mm) is generally recommended. This can be achieved with a standard 1000 mm doorset where the door can open beyond 90 degrees (see Figure 32). This will allow:
• general traffic access;
[HBN 00-04 – PDF page 47]
• limited hoist access including standing/raising aide.
Note
leaves are open and the clear corridor width is a minimum of 2900 mm opposite the door. The ecw of 1370 mm may be achieved with a standard 1700 mm doorset with the doors opening just greater than 90 degrees (see Figures 17 and 35);
Standing/raising aide is a type of hoist used where patient has weight-bearing capability in their legs. See website www.arjo.com/int/Products.asp? PageNumber=243&ProductCategory_Id=13
8.17 The use of a sling hoist with legs closed or multipurpose hygiene chair will require a minimum clear corridor width of 1350 mm (see Figure 32).
Leaf and a half doors
8.18 With a leaf and a half door, the leaves are divided asymmetrically.
• for bed access when turning 90 degrees from a corridor into a room with a recessed door, with two attendants passing through the door with the bed (one at the front and one at the back), a minimum ecw of 1200 mm is considered acceptable when both leaves are open and the clear corridor width is a minimum of 2900 mm opposite the door (see Figure 17). The ecw of 1200 mm may be achieved with a 1500 mm doorset with standard ironmongery when the door leaves opens beyond 90 degrees (see Figure 34).
8.19 Suitable access will be possible when the following conditions are met:
Note
• for general traffic access, the larger of the two doors must provide an ecw of 850 mm (minimum 800 mm subject to minimum clear approach space of 1500 mm) when only the larger leaf is open. This can be achieved with a 1300 mm doorset (see Figure 33);
The recommended ecws for bed access are based on the assumption that bed-mounted equipment will not project significantly beyond the bed width of 1000– 1080 mm (see paragraph 1.16). Where mobile equipment needs to be moved with the bed and/or larger beds are to be used, a risk assessment should be carried out on the space requirements for access. See Appendix 1.
8.20 To avoid confusion, wherever an asymmetrical door arrangement occurs, if possible, the handing of asymmetrical doors should be consistent throughout the building.
• for hoist access (including shower trolleys and sling hoists with legs open and two attendants), an ecw of 1150 mm (minimum 1050 mm) is recommended when both leaves are open. The minimum ecw can be achieved with a 1300 mm doorset (see Figure 33). However, a 1500 mm doorset is recommended as this provides the recommended ecw without opening the doors significantly beyond 90 degrees (see Figure 34);
Double doors
8.21 Suitable access will be possible when the following conditions are met:
• for general traffic access, in heavily trafficked areas, it is recommended that both leaves provide an ecw of 850 mm (minimum 800 mm) when only one leaf is open. This can be achieved with a 1900 mm doorset (see Figure 36);
• for bed access when turning 90 degrees from a corridor into a room, with four attendants passing through the door with the bed (two at the front and two at the back), an ecw of 1550 mm is recommended when both leaves are open and the clear corridor width is between 2150 and 2400 mm. The ecw of 1550 mm may be achieved with a standard 1700 mm doorset with at least one door leaf opening significantly greater than 90 degrees (see Figure 16);
• for beds access, heavily trafficked areas, a minimum ecw of 1740 mm is recommended when both leaves are open. This can be achieved with a standard 1900 mm doorset (see Figure 36).
• for bed access when turning 90 degrees from a corridor into a room with a recessed door, with four attendants passing through the door with the bed (two at the front and two at the back), an ecw of 1370 mm is recommended when both
[HBN 00-04 – PDF page 48]
8 Doors
Figure 32 1000 mm single doorset
ecw approx 850
door stop, or wall, required to stop door opening 180 degrees and to assist access
approx 450
distance to wall or door stop to allow door to open sufficiently to provide the ecw where door has horizontal pull bar
Typical door providing access for people with poor manoeuvring ability and wheelchairs
ecw approx 800 (achieved with 60 door nib, 926 leaf); ecw approx 850 (achieved with 150 mm door nib, 926 leaf)
minimum clear
wheelchair turning
space for 850 ecw
door
minimum clear wheel-
chair turning space for
825 ecw door
minimum clear hoist
turning space for 850 ecw
door (standing/raising aid,
sling hoist – legs closed,
multi-purpose hygiene
chair)
minimum clear wheelchair
turning space for 800 ecw door
ecw 850 (800)
door nib
[HBN 00-04 – PDF page 49]
Figure 33 1300 mm leaf & half doorset Figure 34 1500 mm leaf & half doorset
door nib door nib
870 ecw achieved (large leaf only open) with 150 door nib on large leaf (926 leaf) 800 ecw achieved (large leaf only open) with 60 door nib on large leaf (926 leaf)
ecw 850 (800)
door nib door nib
870 ecw achieved (large leaf only open) with 150 door nib on large leaf (926 leaf) 800 ecw achieved (large leaf only open) with 60 door nib on large leaf (926 leaf)
minimum clear shower trolley turning
space for 1050 ecw door
ecw 850 (800)
achieves ecw of approx 1300 with both leaves open, 150 door nib on large leaf and 100 door nib on small leaf achieves ecw of approx 1230 with both leaves open, 60 door nib on large leaf and 100 door nib on small leaf
achieves ecw of approx 1140 with both leaves open, 150 door nib on large leaf and 270 door nib on small leaf achieves ecw of approx 1040 with both leaves open, 60 door nib on large leaf and 270 door nib on small leaf
Figure 36 1900 mm double doorset
door nib door nib
Figure 35 1700 mm leaf & half doorset
door nib door nib
870 ecw achieved (larger leaf only open) with 150 door nib on larger leaf (926 leaf) 800 ecw achieved (larger leaf only open) with 60 door nib on larger leaf (926 leaf)
ecw 850 (800)
870 ecw achieved (larger leaf only open) with 150 door nib on larger leaf (926 leaf) 800 ecw achieved (larger leaf only open) with 60 door nib on larger leaf (926 leaf)
ecw 850 (800)
achieves ecw of approx 1500 with both leaves open, 150 door on large leaf and 100 door nib small leaf achieves ecw of approx 1430 with both leaves open, 60 door nib on large leaf and 100 door nib small leaf
achieves ecw of approx 1740 with 2 x 150 door nib and protruding ironmongery achieves ecw of approx 1600 with 2 x 60 door nib and protruding ironmongery achieves ecw of approx 1740 with 2 x 60 door nibs and push plates on opening side of door
[HBN 00-04 – PDF page 50]
8 Doors
Force to open door/door closers
8.22 The force required to push or pull doors should be kept to a minimum.
8.33 Doors to be closed by wheelchair users without assistance should be fitted, along the width of the closing side of the door, with a horizontal pull bar handle. The handle should be mounted at a height of 900–1100 mm, preferably 1000 mm (see Figure 37).
8.23 Door closers should meet the requirements of both Approved Document B and Approved Document M, as appropriate. See BS 8300 and Approved Document M in relation to door closers.
8.34 Horizontal bars reduce the ecw of the door, and this must be considered when selecting the doorset (see Figure 32).
8.24 Automatic closers on double swing doors should have a check mechanism to prevent them swinging beyond the closed position.
8.35 Vertical pull handles enable people of different heights to grasp them at a height that gives them the best mechanical advantage, enabling doors to be opened more easily (see Figure 37).
Handles for latching doors
8.25 Strong floor spring closers (often fitted to external heavy doors) should be avoided unless used in conjunction with automatic opening and closing devices.
Fire doors
8.36 Door handles that unlatch should be easy to grasp and open with one hand.
8.26 Fire doors fitted with door closers are heavy and awkward to open and hamper easy circulation. Fire doors on circulation routes, and those not needing to be closed for security reasons, should be fitted with electromagnetic stays or swingfree door closers, which will close in the event of a fire alarm.
8.37 Lever handles are recommended because they can be elbow-operated by a person with impaired hand function. The design of the lever handle should minimise the risk of catching clothing or causing injury, for example by curving the end of the lever towards the door.
8.38 Minimal force should be required to operate the lever.
Sliding doors
8.27 On doors that are designed to remain open, the edges should be recessed when open in order to avoid creating an obstruction. Alternatively, the edges should contrast visually with the background against which they will be viewed.
8.39 Sliding doors are economical in terms of space requirements.
Door handles
8.40 Automatic sliding doors are easy to use.
8.28 Door handles should be easy to use. Their section should be circular or similar (see Figure 17 in BS 8300).
8.41 Heavy sliding doors must be automatically controlled.
8.42 Automatic sliding doors should allow manual operation in the event of a power failure.
8.29 Door handles should allow a firm grip for the hand, and be fixed at a height of 900–1100 mm, preferably 1000 mm (see Figure 37).
8.43 Sliding doors should:
• allow for rapid evacuation;
8.30 Consistent positioning will allow people to find the handle more easily.
Pull handles
• be clearly marked to avoid confusion with conventional push/pull side-hung doors;
• be well-maintained to ensure that the tracks allow smooth movement;
8.31 Knobs and round pull handles should be avoided, since people with impaired hand function find these difficult (if not impossible) to use.
8.32 Pull handles should be D-shaped to reduce the risk of catching clothing or causing injury.
• incorporate a safety device (that is, a guard), either along the length of the sliding sections or between the doors and walls.
[HBN 00-04 – PDF page 51]
Figure 37 Recommended zones for vision panels and location of ironmongery
10º
30º
minimum zone of visibility
minimum zone of visibility
minimum zone of visibility
zone for handle
minimum zone of visibility
900–1100
zone for door protection
min. zone of visibility
min. zone of visibility
900–1100
zone for door protection
Shaded area = possible zone of visibility
[HBN 00-04 – PDF page 52]
8 Doors
Automatic doors
8.44 The provision of automatic doors is recommended in areas of high use.
8.56 All doors in corridors on circulation routes, and any which swing in both directions, should contain a glazed portion to allow people to see others approaching from the opposite direction (see Figure 37).
Kick plates
8.45 Automatic sliding doors are preferable to automatic swing doors, and should open automatically in the event of a power failure or the need for rapid evacuation of a building (see BS 7036:1996).
8.46 Automatic doors should be provided with suitable warnings. See paragraph 4.13.
8.57 Doors should be fitted with kick plates, which should be mounted to a minimum height of 400 mm to protect them from damage from pushchairs and wheelchairs.
Visual contrast
8.47 For automatic swing doors, it is desirable that the depth of the door swing, when fully open, and an additional 1570 mm is marked on the floor in contrasting colour/tone (see paragraph 4.9).
8.58 Door frames should contrast visually with the walls/ surrounding surfaces.
8.48 Automatic double sliding doors should have a minimum clear width of 1200 mm for wheelchair traffic and 1740 mm for bed/trolley traffic.
8.59 See BS 8300 (paragraph 9.1.1) for guidance on the visual characteristics of doorsets to assist people with impaired vision.
8.49 Automatic doors may be triggered by photoelectric sensors, pressure pads or push buttons.
Privacy curtains
8.50 Sensors should detect all users, including children and guide dogs, and the sensor should not allow the door to close if the doorway is not clear.
8.60 Where staff need to enter and exit rooms whilst patients are being examined or treated, and it is not possible to avoid potential views into the room, for patient privacy and dignity, consideration should be given to the use of privacy curtains inside the doors.
8.51 If floor sensors are used, they should be sensitive to uneven pressure, for example that exerted by people using crutches.
8.61 Local infection control advice should be sought on the use of privacy curtains. Consideration should be given to the design of the privacy curtains and provision of a suitable cleaning regime.
8.52 Push buttons to activate automatic doors should be sited clear of the fully open door swing, at a height of 750–1000 mm, should contrast visually with the surrounding background, and should measure approximately 50 mm by 50 mm.
8.62 If wipeable curtains are used, they must be regularly wiped, they should not become discoloured (particularly with fungal growth), and they will need to be replaced regularly. If linen curtains are used, they must be changed frequently.
8.53 The use of power-operated revolving doors requires careful consideration and a risk assessment. If a revolving door is used, an additional accessible side- hung door must be available for use, without the need to call for assistance (see BS 8300 and BS 7036-5 for details).
Glazing
8.63 Figures 38–40 illustrate the minimum space required for a person to open, pass through and close different doors behind a privacy curtain. The precise required layout of a curtain track will depend upon the door size and room configuration.
8.54 Door glazing should be easily identifiable as such.
8.55 Frameless glass doors should be easily identifiable to prevent people colliding with them (see Approved Document M for details).
[HBN 00-04 – PDF page 53]
Figure 38 Privacy curtain options for 1000 mm
Figure 39 Privacy curtain options for 1500 mm
doorset
doorset
1725–1775
150–200
See Chapter 8, Doors
See Chapter 8, Doors
Parked curtain zone
approx 930
Clearance for parked curtain zone
Space to open and close door
Alternative parked curtain zone
Clearance for parked curtain zone Minimum overlap of curtain
Clearance to centre line of curtain track from leading edge of door
See Chapter 8, Doors
See Chapter 8, Doors
Parked curtain zone
Clearance for parked curtain zone
Space to open and close door
approx 930
Alternative parked curtain zone
1500 Nominal
Clearance for parked curtain zone
Clearance to centre line of curtain track from leading edge of door
See Chapter 8, Doors
See Chapter 8, Doors
Parked curtain zone
Parked curtain zone
Space to open and close door
Clearance for parked curtain zone
Alternative parked curtain zone
approx 930
Alternative parked curtain zone
Clearance for parked curtain zone
Note: Shaded area = area required for someone to open and close the door behind the curtain
[HBN 00-04 – PDF page 54]
8 Doors
Figure 40 Privacy curtain options for 1500 mm outward opening doorset
See Chapter 8, Doors
Parked curtain zone
Clearance for parked curtain zone
Alternative parked curtain zone
See Chapter 8, Doors
Parked curtain zone
Clearance for parked curtain zone
Alternative parked curtain zone
Door signage
8.64 Signs on or adjacent to doors should be at a height of 800–1500 mm and tactile so that they can be easily read by touch. See ‘Wayfinding: effective wayfinding and signing systems guidance for healthcare facilities’ for further details.