Home › England (NHS England estates) › HBN 00-04 › 7 Handrails

HBN 00-04: 7 Handrails

Circulation and communication spaces · PDF pages 43–45 of 59 · Source file: Health_Building_Note_00-04_-_Circulation_and_communication_spaces_-_updated_April_2013.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HBN 00-04 – PDF page 43]

7 Handrails

Introduction

7.9 Recessed handrails are not recommended, as they cannot be leant on for support.

Height

7.1 This chapter provides guidance on the design of handrails in circulation and communication spaces. See also paragraphs 3.29–3.31.

7.10 The top of the handrail should be:

• 900–1000 mm above the surface of a ramp, ramp landing or pitch line of a flight of steps or along a corridor;

7.2 Where handrails and wall protectors are required, they may be combined or kept separate (see paragraph 7.20). For further details on wall protection see Health Building Note 00-10 Part B: ‘Walls and ceilings’.

• 900–1100 mm from the surface of a stair landing.

Shape and size

7.3 Handrails should be easy to grasp; the size and shape should allow a firm but comfortable grip with the whole hand.

7.11 A second lower rail at a height of 600 mm should be provided in corridors, stairs and landings in children’s healthcare facilities and on ramps (for wheelchair users). They should also be provided on stairs and landings in healthcare premises where there are likely to be a significant number of semi- ambulant users.

7.4 Handrails that are too small are uncomfortable and provide an unsatisfactory grip, whereas handrails that are too large are difficult to grip for people with weak or arthritic hands.

Withstandable force

7.12 Handrails should be rigid, securely fixed and able to support the weight of a person leaning on them.

7.13 They should be sufficiently secure to support a person grasping them to prevent or arrest a fall:

7.5 A handrail that is round in cross-section with a diameter of 40–45 mm (differing from Approved Document M requirement of 32–50 mm) is recommended. Oval handrails with dimensions of 38 mm × 50 mm wide (that is, 1mm narrower than the 39 mm required by Approved Document M) are acceptable. In both cases, the longer dimension should be horizontal.

• vertically, they should support 95% of people plus a margin of 50% (that is, 88 kg + 44 kg) = 132 kg;

7.6 Handrails with a large square or rectangular cross- section should be avoided.

• horizontally, they should support a force from an adult of 155 N + 50% = 233 N.

Clearance

Provision on stairs, ramps and landings

7.14 Continuous handrails on stairways, ramps and landings help people to negotiate changes in direction.

7.7 Handrails should allow enough space between the rail and the adjacent wall (or any other obstacle) for hands to pass without scraping knuckles and to aid those who want to use the rail as a support for the whole forearm.

7.15 Vertical handrail risers or interruptions of handrails to accommodate newel posts and supports should be avoided.

7.8 A clearance of 60–75 mm (10 mm less than Approved Document M states) is recommended, as this allows the forearm to be rested on the rail without any danger of it getting trapped.

7.16 Handrails should extend horizontally for 300 mm past each end of the change in level and, where they

[HBN 00-04 – PDF page 44]

7 Handrails

Figure 29 Handrail on low wall, suitable for

ramped access

do not interrupt pedestrian routes, an extension of 450 mm is recommended.

7.17 They should return to a wall or at least 100 mm down towards the floor, and should terminate in a way that reduces the risk of clothing being caught.

50 max = furthest distance a handrail can be set back from the edge of a ramp

7.18 Handrails on ramps may be provided on low walls (see Figure 29), but the handrail must not be located more than 50 mm back from the edge of the ramp.

Provision in corridors

60–75 40–45 50 max

40–45

7.19 Handrails should return into recessed doorways and openings, but otherwise be continuous to aid navigation.

Handrails in association with wall protection

7.20 Where handrails and wall protectors are provided:

• a minimum vertical clearance of 50 mm must be maintained between the handrail and wall protector (see Figures 30 and 31);

Ramp

• where the wall protector protrudes in front of the handrail, the clear width of the corridor will be to the wall protector (see Figure 31).

900–1000

Balustrades

7.21 Balustrades should be provided around landings at a height of 1100 mm above the floor. The space between the balusters should be no wider than 100 mm. They should not provide toeholds for climbing.

Appearance/finishes

7.22 Handrails should be:

• easily visible, that is, contrast visually with the surface to which they are fixed;

• smooth and free of any abrasive elements;

• neither too cold nor too hot to the touch.

7.23 Handrails may have raised indicators built in to convey information such as floor level.

[HBN 00-04 – PDF page 45]

Figure 30 Handrails and separate wall protection

Figure 31 Handrails and combined wall protection

alternative handrail section

60–75 40–45

40–45

40–45

60–75

40–45

possible lower handrail

900–1000

possible lower handrail

900–1000

possible wall protection

wall protection 200–1000

wall protection 200–1000

approx 30 wall protection projects in front of handrail; this will reduce clear corridor width