HBN 00-04: 6 Lifts
[HBN 00-04 – PDF page 38]
6 Lifts
Introduction
Lift size
6.1 This chapter provides guidance on the design of lifts for general traffic, patient trolleys/stretchers and beds.
6.8 All lifts in healthcare buildings should have minimum internal dimensions of 1100 mm (wide) × 1400 mm (deep); that is, be capable of accommodating at least eight people (or 630 kg).
6.2 It does not cover goods traffic lifts.
General traffic lifts
6.3 The following guidance is for planning purposes only. For detailed technical information see:
• Health Technical Memorandum 00 – ‘Policies and principles of healthcare engineering’;
6.9 General traffic lifts should have minimum internal dimensions of 1600 mm (wide) × 1400 mm (deep). See Figure 26.
• Health Technical Memorandum 05-03 Part E – ‘Escape lifts in healthcare premises’;
6.10 Handrails should be provided on both the side and rear walls of lift cars for general traffic. See Chapter 7 for further details on handrails.
• BS 8300:2009+A1:2010/Approved Document M (2013) for information on landing indicators, landing calls, lift car controls and emergency communication etc in relation to disabled access;
6.11 Consideration should be given to the provision of larger general traffic lifts, of 2000 mm (wide) × 1400 mm (deep). This size can accommodate any type of wheelchair together with wheelchair attendants and other passengers.
• BS 5655-6:2011;
Lifts for trolley/stretcher movement
• CIBSE Guide D;
• BS EN 81-70:2003.
Selection of lifts
6.12 The recommended minimum lift size for patient trolley/stretcher movement is 1400 mm × 2400 mm (this will accommodate trolleys up to 800 mm × 2375 mm). See Figure 27.
6.4 Lifts should be versatile to accommodate as many types of load as possible.
6.13 A lift of this size will just accommodate an extended standard hospital bed (1000–1050 mm × 2370 mm). However, it is not recommended for moving patients in beds.
6.5 The number, type, size and speed of lifts should be determined from a traffic analysis specific to the proposed building development, and should allow adequate flexibility of the lift solution to accommodate future changes.
6.6 At least one wheelchair-accessible lift should be in operation between each floor of a healthcare facility.
6.14 Where trolley/stretcher lifts are to be used for general traffic, the lift car will require handrails (see paragraph 6.10); the internal dimensions of the lift (that is, 1400 mm × 2400 mm) will need to be clear of handrails.
6.7 Where planning allows, lift cars may be provided with doors on opposing sides to allow wheelchair users to exit without reversing out.
6.15 Where provided, handrails should be limited to one sidewall of the lift car to minimise the potential risk to patients on trolleys; while patient trolleys may fit underneath side handrails, the rail overhang may inconvenience or pose a hazard risk to a patient on a trolley.
[HBN 00-04 – PDF page 39]
Lifts for bed movement
Lift finishes
6.16 The recommended minimum lift size for the movement of patients on beds is 1800 mm × 2700 mm.
6.24 The lift car should be fitted with a slip-resistant floor covering with similar frictional qualities to the floor of the lift landing.
6.17 In order to segregate traffic, for operational and infection control reasons, it is not anticipated that lifts for bed movement will be used for general traffic.
6.25 The floor covering should provide good grip but minimum resistance to the movement of wheelchairs and wheeled trolleys (studded flooring is not recommended).
6.18 Where bed lifts are also to be used for general traffic, the lift car will require handrails (see paragraphs 6.10 and 6.15). See Figure 28.
6.26 The floor should have a high luminance to reassure people that they are not stepping into an open lift shaft.
Lift landings and lobbies
6.27 Mirrors and reflective glass should be avoided in lifts, as they can cause confusion and disorientation.
Lighting
6.19 Each lift should open onto a landing of adequate depth, in order not to restrict traffic flow in front of the lift entrance, or onto a protected lobby. Lifts should not open directly onto corridors.
6.28 Wall-wash lighting, uplighting or perimeter lighting rather than direct downlighting should be used in bed and trolley/stretcher lifts to avoid dazzling patients being transported.
Doors
6.20 A protected lobby should be provided where a lift does not open off a hospital street (see paragraphs 6.25–6.27 of Health Technical Memorandum 05-02 for details). See also Health Technical Memorandum 08-02 – ‘Lifts’ for details of current best practice.
6.29 Lift doors for general traffic lifts should provide a clear opening width of 1100 mm and height of 2000 mm (see BS ISO 4190-1:1999).
6.21 Figures 26–28 illustrate the minimum space requirements outside lifts.
6.22 The lift landing/lobby walls and lift door should contrast visually, as should the landing floor and lift floor.
6.30 Lift doors for movement of patient trolleys/ stretchers and beds should provide a minimum clear opening width of 1370 mm and height of 2100 mm.
6.23 Additionally, a visually contrasting floor surface measuring at least 1500 mm × 1500 mm should be provided outside the lift door area. See the latest version of LG2 for detailed guidance on lighting.
[HBN 00-04 – PDF page 40]
6 Lifts
Figure 26 General traffic lift
1900 landing/manoeuvring space assisted use, 2100 between lifts if two lifts face each other
landing/manoeuvring space independent use
possible position of landing controls
location of controls
minimum
manoevring
space beyond
door opening
for independent
use
handrails @ 900 as Building Regulations 2000
manoeuvring space for assisted approach
possible position of
landing controls
[HBN 00-04 – PDF page 41]
Figure 27 Lift for trolley/stretcher movement
car size
car size
most types of trolley length accommodated
100 door recess
width of space for attendant(s) to turn patient trolley 180 degree
CL
length of space for attendant(s) to turn patient trolley 180 degrees
[HBN 00-04 – PDF page 42]
6 Lifts
Figure 28 Lift for bed movement
car size
handrail
1000–1080
trolley/ equipment
clear car size
approx 2440 with pump attached to end of bed
width of space for attendants to turn bed 180 degrees
CL
length of space for attendants to turn bed 180 degrees