[HBN 00-04 – PDF page 34]

5 Internal stairs

Introduction

Risers and goings

5.1 This chapter provides guidance on the design of internal stairs suitable for general traffic, and for mattress evacuation.

5.11 Risers and goings should be uniform throughout the flight, as any irregularities may cause people to stumble. The recommended riser height for healthcare buildings is 150–170 mm.

5.2 Single steps may be difficult to negotiate, are not visually obvious and should be avoided.

Approach and landings

5.12 Risers should not be of the open type, as they are a trip hazard (especially for semi-ambulant people with leg braces and prostheses), disorientating, and may transmit distracting sounds.

5.3 Stairs should be designed so that they are not in the direct line of normal pedestrian travel or access routes.

5.13 The minimum recommended length of an internal going in healthcare buildings is 280 mm, preferably 300 mm.

Nosings

5.4 A landing should be provided at the top and bottom of each flight of stairs. The minimum clear landing depth is 1200 mm but must equal the clear stair width between handrails (see paragraph 5.27).

5.5 Figure 24 shows the clear landing depth as 1500 mm to equal the example clear stair width between handrails.

5.14 Nosings should contrast visually with the stairs, extend the full width of the step, and reach a depth of 50–60 mm on both tread and riser to allow visually-impaired people to detect the edge of each step.

5.6 The top and bottom steps of a flight should not encroach onto the landing area. Doors must open clear of the unobstructed clear landing.

5.15 Although rounded nosings may cause slipping, sharp projecting nosings and abrupt angles should be avoided.

5.16 A tread should not overlap the one below. Where there is an overlap, the nosing should not project by more than 25 mm.

Edge protection

5.7 To indicate that there are descending steps ahead, consideration should be given to providing a hazard-warning zone on each landing. The zone should use a floor finish that contrasts visually with the general floor finish, but has the same slip resistance.

5.8 The warning zone should be at least 400 mm from the nosing and a minimum of 800 mm deep and 1200 mm wide (see Figure 24). See Appendix 2.

5.17 For steps not adjacent to a wall, a barrier, with a minimum height of 100 mm above the level of the treads, should be provided, for safety reasons (to prevent feet, crutches and sticks from accidentally slipping off the edge of steps).

Height

Step finishes and type

5.9 The maximum recommended number of risers between landings for a flight of internal stairs is 12–14 (see Appendix 2).

5.18 Stair finishes should not have patterns that may cause step edges to be indistinguishable or cause visual confusion of any kind.

5.10 Where possible, the number of risers in successive flights should be equal.

5.19 Helical and spiral steps, the treads of which are often too narrow, should be avoided.

[HBN 00-04 – PDF page 35]

Areas under stairs

5.30 The lighting should be designed so that it highlights the differences between risers and treads, the top and bottom steps, and any changes in direction.

5.20 Open areas on the underside of stairs should be avoided to eliminate the possibility of anyone walking into the overhang created.

5.31 Lighting that causes glare (for example poorly located spotlights, floodlights or low-level light sources) should be avoided.

5.21 If enclosure is not possible, two rails – one at 1000 mm and one at 200 mm above floor level – or some other, strategically placed, permanent barrier should be provided.

Ramps

Handrails

5.22 Handrails should be provided on both sides of steps.

5.23 Handrails should be located within the width of the tread of the stairs.

5.32 Ramps may be provided in place of steps in some situations, in particular to facilitate egress of wheelchair users or those with pushchairs in an emergency, and should be provided to bypass all short flights of steps. (See Approved Document M (2013) and BS 8300:2009+A1:2010 for detailed guidance on ramps.)

5.24 See Chapter 7 for further details on handrails.

Clear width of steps

5.33 However, ramps are generally not considered appropriate for any significant changes in internal level within a healthcare building.

Mattress evacuation

5.25 Steps should be wide enough to allow people to negotiate them comfortably by holding onto one or both handrails or by being assisted.

5.26 The width of the steps should reflect the amount of pedestrian traffic.

5.34 Figure 25 illustrates an example staircase design for mattress evacuation. Table 1 provides optional/ alternative dimensions for the clear width of stairs and landings. Dimensions in Table 1 are supported by Figure A3 in Appendix 4.

5.27 A minimum unobstructed, clear stair width between handrails of 1000 mm for one person, or 1500 mm for two-way traffic, is necessary. The minimum 1000 mm wide channel ensures that people can use both handrails if they wish.

5.35 For mattress evacuation, the number of turning manoeuvres in descending a staircase should be as few as possible.

5.28 Figure 24 illustrates an example design of internal stairs for healthcare buildings.

5.36 See Health Technical Memorandum 05-02 for further details of staircase design for mattress evacuation.

Lighting

5.29 Stairs and landings should be well illuminated; see the latest version of LG2 for detailed guidance on lighting.

[HBN 00-04 – PDF page 36]

5 Internal stairs

Figure 24 Internal stairs

BS 8300 = 250–300 B Regs = (250)

BS 8300 = 250–300 B Regs = (250)

max 25

preferred profile

150–170

150–170

Example stair profiles

handrail extension

900–1100

edge protection

handrail extension

900–1000

height of handrail above

stair tread

permanent barrier to stop people walking into exposed landing

900–1100

if less than 2100

200 + 1000

unobstructed distance between handrails to be maintained on landings

Example landing depth

Zone for

possible zone

of visual warning at top of flight

Example stair width

handrail Zone for

handrail

[HBN 00-04 – PDF page 37]

Table 1 Alternative stair and landing dimensions to facilitate mattress evacuation

A Minimum clear landing

B Minimum clear stair

C Minimum clear landing

width

width

depth

 allows mattress evacuation only

allows mattress evacuation and restricted ambulant passing

1600* 1800* allows mattress evacuation plus ambulant passing

* Stair width is not determined by the number of people expected to use the stairs in a fire emergency, but principally by the requirements of mattress manoeuvrability.

For a clear landing width of 3400 mm, the minimum clear landing depth for mattress evacuation is 1450 mm. 1600 mm is recommended to enable ambulant passing and to equal the clear stair width. See BS 8300.

For a clear landing width of 3800 mm, the minimum clear landing depth for mattress evacuation is 1350 mm. 1800 mm is recommended to equal the clear stair width. See BS 8300.

Figure 25 Mattress evacuation down stairway

Example landing depth for 1500 clear stair width. Alternative dimensions see Table 1

C (1550)

B (1500)

Example stair width, see table

DOWN

for 1500 clear stair width. Alternative dimensions see Table 1

Example landing width to facilitate “U-turn” dragging mattress,

A (3220)