HBN 00-04: 4 Internal lobbies
[HBN 00-04 – PDF page 27]
4 Internal lobbies
Lobby length
Introduction
4.9 Where swing doors are used, a minimum clear length (that is, clear of the furthest point that any door(s) will swing into) of:
4.1 This chapter provides guidance on the design and appropriate length and width of internal lobbies (that is, lobbies connecting internal spaces, for example at staircases).
• 1570 mm should be provided for general traffic access (see Figures 18, 20 and 21).
4.2 See also Health Technical Memorandum 05-02.
Lobby size
• 4100 mm should be provided for bed/trolley access.
Note
4.3 The type of traffic expected to pass through a lobby will influence the size of the lobby and the decision to provide double- or single-leaf doors.
4.4 Lobbies should be wide enough to allow two users to pass and to negotiate doorways. The actual width will depend upon:
A single swing door hinges from the corner of the door so that a 926 mm leaf swings approximately 930 mm into the lobby at its further point, depending on the hinge design. A double swing door generally hinges from part way along the door so that the leaf does not project as far when swinging.
• whether handrails are provided within the lobby;
• the type of door ironmongery used and consequent nib size (see paragraphs 8.13–8.15).
Lobby width
4.10 For lobbies where both sets of doors are automatic sliding doors, the length can be reduced as no door swings are involved, nor is space required for manual operation. See Figures 22 and 23.
Doors
4.5 For lobbies with single doors for general traffic, a minimum clear width of 1500 mm is recommended (see Figure 18). This allows for varying users passing and for the positioning of a 1000 mm doorset for access/egress. (See also Figures A1 and A2 in Appendix 4 and paragraphs 3.7–3.8 and 8.16.)
4.11 Automatic sliding doors are preferred to swing doors. However, where swing doors are used, the two sets of doors at either end of the lobby should swing in the same direction, particularly for escape purposes (see Figure 21).
4.12 Doors may swing towards each other, or in both directions, but the lobby must be larger and ideally the doors should be offset (see Figure 18).
4.6 For lobbies with double doors for general traffic, a minimum clear width of 2020 mm is recommended (that is, 1900 mm doorset plus 60 mm door nib on either side – see Figures 19– 21). See also paragraph 8.21 for an explanation of door width requirements.
4.7 For lobbies with automatic double sliding doors for general traffic, a minimum clear width of 1500 mm is recommended (see Figure 22).
4.13 Where automatic swinging doors project more than 100 mm into access routes where users approach the door from the side (that is, not head on), the zone into which the doors open should be guarded by a barrier to protect users (see Figures 18, 20 and 21). See also paragraph 3.17.
4.8 For lobbies with double doors (sliding or swing) for patient trolley/bed access, a minimum clear width of 2150 mm is recommended (see Figure 23). See also paragraph 3.9.
4.14 In reception areas, lobby doors should be visible from the reception desk to enable assistance to be given to anyone having difficulty negotiating the entrance.
[HBN 00-04 – PDF page 28]
4 Internal lobbies
Lighting
4.15 For guidance on the appropriate width of door leaves and required effective clear opening widths see paragraphs 8.13–8.21.
4.17 Internal lobbies should be well and evenly lit. See also paragraph 3.26.
Surfaces
4.16 Floor surfaces in lobbies should be level without thresholds at doorways.
Figure 18 Lobbies with single doors for general traffic
Zone for
handrail/
wall
protection
See Chapter 8, Doors
See Chapter 8, Doors
Alternative door position
(1570) clear to alternative
door swing
door leaf ~930
(1570) clear to door swing
Clear space in front of doors Clear space in front of doors
(1570) clear to alternative door swing
Zone for
handrail/
wall
protection
Alternative door position
See Chapter 8, Doors See Chapter 8, Doors
Handrail stops before door swing
door leaf ~930
500 of the rail to be knurled or patterned
Visually contrasting guard with cane detection at ground level. See paragraph 4.14
Clear space in front of doors, visually contrasting floor if door is automatic. See paragraph 8.47
Clear space in front of doors
Lobby length = 1570 plus the length of the door swing into the lobby
[HBN 00-04 – PDF page 29]
Figure 19 L-shaped lobby with double doors opening inwards for general traffic
500 of the rail to be knurled or patterned Handrail stops before door swing
See Chapter 8, Doors
~930
Clear space in front of doors
See Chapter 8, Doors
Zone for handrail/ wall protection
Zone for handrail/ wall protection
Clear space in front of doors
[HBN 00-04 – PDF page 30]
4 Internal lobbies
Zone for handrail/ wall protection
door leaf ~830 door leaf ~830
double swing double swing
Lobby length = 1570 plus the length of the two door swings into the
500 of the rail to be knurled or patterned Handrail stops
before door swing
See Chapter 8, Doors See Chapter 8, Doors
Visually contrasting guard with
cane detection at ground level.
See paragraph 4.14
lobby Clear space in front of doors Clear space in front of doors
Figure 20 Lobby with double doors for general traffic
[HBN 00-04 – PDF page 31]
Zone for handrail/ wall protection
Clear space in front of doors
door leaf ~930
Handrail stops
before door swing
500 of the rail to be knurled or patterned
Lobby length = 1570 plus the length of the door swing
into the lobby
See Chapter 8, Doors See Chapter 8, Doors
Visually contrasting guard
with cane detection at
ground level.
See paragraph 4.14
Clear space in front of doors,
visually contrasting floor if door is
automatic. See paragraph 8.47
Figure 21 Lobby with double doors opening in same direction for general traffic
[HBN 00-04 – PDF page 32]
4 Internal lobbies
Zone for handrail/ wall protection
clear space in front of doors
opening beam
See Chapter 8, Doors
opening beam zone for automatic door
opening beam zone for automatic door
zone for automatic door
opening beam zone for automatic door
where side
approach is possible, a
minimum of 700 to each
side of the doorway opening
where side
approach is possible, a
minimum of 700 to each
side of the doorway opening
clear space in front of doors
Figure 22 Lobby with automatic double sliding doors for general traffic
[HBN 00-04 – PDF page 33]
Figure 23 Lobby with automatic double sliding doors for patient trolley/bed access
Zone for handrail/ wall protection
opening beam
See Chapter 8, Doors
space for walking
and pulling
patient trolley
opening beam zone for automatic door
bed or patient trolley length
2100–2370
opening beam zone for automatic door
space for
walking and
pushing
patient trolley
zone for automatic door
opening beam zone for automatic door
where side
approach is possible, a
minimum of 700 to each
side of the doorway opening
where side
approach is possible, a
minimum of 700 to each
side of the doorway opening