Home › England (NHS England estates) › HBN 00-04 › 3 Corridors

HBN 00-04: 3 Corridors

Circulation and communication spaces · PDF pages 16–26 of 59 · Source file: Health_Building_Note_00-04_-_Circulation_and_communication_spaces_-_updated_April_2013.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HBN 00-04 – PDF page 16]

3 Corridors

Introduction

3.1 This chapter provides guidance on the design and appropriate width of corridors.

3.8 Where there is a higher volume of traffic, a constant clear corridor width of 1800–2100 mm will allow most users to pass comfortably (see Figures 5, 6 and 7).

Corridor width for bed/patient trolley traffic

3.2 Corridors connect spaces and, in emergencies, form part of escape routes. They must be simple and safe to negotiate, and aid navigation around the building.

3.9 The recommended minimum clear corridor width for circulation of beds/trolleys is 2150 mm if passing spaces are provided (see Figures 8 and 9).

Corridor width

3.3 Corridors should be wide enough to allow two users to pass each other and negotiate doorways.

3.10 Where two beds need to pass regularly, the recommended minimum clear corridor width should be 2960 mm (see Figure 10).

3.11 Consideration should be given to providing spaces where beds can be turned through 180 degrees particularly along long stretches of corridor and/or outside primary entrance doors or lifts (see Figure 11).

Figure 3 Space for independent wheelchair user

and ambulant person to pass

3.4 Where the requirements for means of escape are greater than that for circulation, for example the corridor is intended as a hospital street (see Health Technical Memorandum 05-02 – ‘Guidance in support of functional provisions for healthcare premises’), the requirements for means of escape should become the minimum requirements for the space.

3.5 Where passing spaces are provided, the distance between them should be determined by the frequency of activity along the corridor.

3.6 Potential waiting times at passing spaces (measured in seconds or number of paces) should be kept to a minimum. The average person walks at approximately 1000 mm per second, therefore a distance of 10–20 m between passing spaces is recommended.

Corridor width for general traffic

Note

Figure 11 is based on bed dimensions shown in Figures 8–10.

3.7 The recommended minimum clear corridor width for general traffic, where there is a low volume of traffic and passing spaces are provided, should be 1500 mm (see Figures 3 and 4). This width allows for varying users to pass in between the defined passing spaces (see also Figures A1 and A2 in Appendix 4) and for the approximate positioning of a 1000 mm door across the corridor (see Figure 32).

[HBN 00-04 – PDF page 17]

Figure 4 Corridor with passing space and

90 degree corner for general traffic Figure 5 Space for two independent wheelchair

users to pass

Wheelchair turning space with attendant and 180 degree turn

Figure 6 Space for independent wheelchair user

and semi-ambulant person with walking frame to pass

Passing space 1800 x 2200

allows passing wheelchairs

and turning

2200 allows attendant to turn wheelchair 180 degrees

10–20 m

Figure 7 Space for wheelchair user and semi-

10–20 m = recommended distance

ambulant user with crutches to pass

between passing spaces

Zone for handrail/wall protection

Zone for handrail/wall protection

[HBN 00-04 – PDF page 18]

3 Corridors

space to

stand

waiting for

bed to

pass

space for

waiting and

pulling

patient

bed/trolley

out of

recess

clearance to

2330–2370

any obstruction 1000–1080

1000–1080

space for

walking

and push-

ing patient

bed/trolley

space for

walking

and pulling

patient

bed/trolley

Figure 9 Bed passing space

space for

walking

and pulling

patient

bed/trolley

space for

walking and

pushing

patient

bed/trolley

2330–2370

1000–1080

Figure 8 Space for straight bed movement

[HBN 00-04 – PDF page 19]

Figure 10 Space for two beds passing

space for walking and pulling patient bed/trolley

space for walking and pushing patient bed/trolley

space for walking and pulling patient bed/trolley

2330–2370

space for walking and pushing patient bed/trolley

1000–1080 1000–1080

860 if attendants need to stay at side of bed when passing

[HBN 00-04 – PDF page 20]

3 Corridors

Figure 11 Corridor with recess for turning bed through 180 degrees

Minimum dimension allows extended standard bed only

Recess at lift lobby or other assembly point, allows bed to turn through 180 degrees

Pump at foot of bed adds 70 mm to length but does not affect turning space

Zone for handrail/wall protection

Zone for handrail/wall protection

[HBN 00-04 – PDF page 21]

Obstructions

3.12 Sharp angles and overhead obstructions, such as staircases that jut out, should be avoided. If these exist, and cannot be removed, they should be emphasised by painting them in a bright, contrasting colour or, preferably by erecting a physical barrier (see paragraphs 5.20–5.21).

3.16 Where doors are located within circulation routes, to help prevent partially-sighted users colliding with the door edge when the door is open or being opened, consideration should be given to stopping the handrail before it reaches the door swing area and making the last 500 mm knurled or patterned to indicate the approach of a potential hazard. See Figures 13–15 and 18–21.

3.13 Corners should be carefully detailed. Splayed or rounded angles are helpful, as wall surfaces are likely to be touched by people who require a tactile knowledge of the building or use handrails for support.

3.17 Outward-opening doors into main circulation routes and corridors are not recommended. Where it cannot be avoided that a door opens into the corridor, the door should be recessed so that when fully open it does not restrict the clear corridor width (see Figure 14).

3.14 Corridor widths should be unobstructed by projections. However, where obstructions are unavoidable (for example in existing buildings), a local reduction in clear width to 1200 mm is acceptable for general traffic corridors provided that hazard protection is installed (see Figure 12).

3.18 It may be acceptable to have a non-recessed door opening into a corridor provided the door gives access to a switchcupboard/service duct that is kept locked and only opened occasionally and the corrridor is not on a major access or escape route (see Appendix 2).

Doors

3.19 Figures 15–17 illustrate the minimum recommended corridor widths and door sizes for bed movement and turning into and out of a corridor.

3.15 Figures 13 and 14 illustrate the minimum recommended corridor widths and single door sizes for general traffic, including turning into and out of a corridor.

Figure 12 Corridor with section of

restricted clear width for general traffic

Handrail at angle for hazard protection

Reduced clear width at localised obstructions for short distances. See paragraph 3.14

Handrail at angle for hazard protection

approx maximum length of reduced clear width

Zone for handrail/wall protection

Zone for handrail/wall protection

[HBN 00-04 – PDF page 22]

3 Corridors

Space for approach/manoeuvre for assisted use

See Chapter 8,

Doors

Zone for

handrail/

wall

protection

wheelchair

for turning assisted

Minimum clear space

500 of the rail to be knurled or patterned

before door

swing

Space for approach/manoeuvre for assisted use

Zone for

handrail/

wall

protection

Recess must be

as deep as door

leaf

Doors Handrail stops

See Chapter 8,

Figure 14 Corridor with single side door for general traffic

Zone for

handrail/

wall

protection

See Chapter 8,

Doors

Zone for

handrail/

wall

protection

traffic

Clear space in front of door

500 of the rail to be knurled or patterned Handrail stops before door swing

Figure 13 Straight corridor with single door for general

Space in front of door to allow assisted withdrawal

[HBN 00-04 – PDF page 23]

Figure 15 Straight corridor with double doors for bed movement

withdrawal

ecw = (1740)

before door swing

See Chapter 8, Doors

500 of the rail to be knurled or patterned Handrail stops

space in front of door to allow

withdrawal space in front of door to allow

Zone for handrail/ wall protection

Zone for handrail/ wall protection

[HBN 00-04 – PDF page 24]

3 Corridors

Figure 16 Turning a bed through a door off a straight corridor

Door nib must allow

door leaf to open

substantially beyond

90 degrees if 1700 nominal doorset used

See Chapter 8, Doors

ecw = 1550

1550 ecw required with clear corridor widths between 2150 and 2400.

1700 nominal doorset drawn

Door

nib

Zone for handrail/ wall protection

Zone for handrail/ wall protection

[HBN 00-04 – PDF page 25]

Figure 17 Turning a bed through a recessed door off a corridor

Further increase in recess depth has no further effect on reducing required door effective clear width (ecw)

Clear space beyond

ecw to allow turning

ecw = 1370 (1200)

see paragraph 8.19

See Chapter 8, Doors

Door nib

Zone for handrail/wall protection

Zone for handrail/wall protection

[HBN 00-04 – PDF page 26]

3 Corridors

3.20 For guidance on the appropriate width of door leaves and required effective clear opening widths see paragraphs 8.13–8.21.

Note

Figures 15–17 are based on bed dimensions shown in Figures 8–10.

3.27 Where specified, tubular fluorescent lamps and fittings should always be fitted with diffusers to minimise glare and reflection. Tubes should be positioned longitudinally down corridors to aid orientation. See the latest version of the Chartered Institution of Building Services Engineers (CIBSE) Lighting Guide 2 (LG2) – ‘Hospitals and health care buildings’ for detailed guidance on lighting.

Security

Lighting

3.21 Corridors should be well and evenly lit.

3.28 Corridors should be as straight as possible with limited recesses and chamfered corners to aid surveillance and security.

3.22 The position, size and shape of windows should maximise the use of natural light.

Handrails

3.23 Windows should not be situated at the ends of corridors as this may produce glare.

3.24 Low windows can aid lighting of floor areas but should not cause glare or disorientation and should be designed to prevent people falling against or through them.

3.29 Handrails should be fitted in main communication routes (that is, main corridors between departments) and in departmental corridors as required. See specific departmental guidance for further information.

3.25 Glare may be minimised by using light-coloured walls and solar shading or fitting blinds or curtains.

3.30 All corridors should have a clear width that allows for the fitting of handrails without reducing the required clear space for access.

3.26 Windows should open outwards and have restricted openings. Tilt-and-turn windows that protrude into corridors should be avoided.

3.31 See Chapter 7 for detailed information on handrails.