[HBN 00-04 – PDF page 55]

Appendix 1 – Bed movement study

The bed movement study was conducted at Leicester General Hospital during 2005. The study investigated space requirements for movement of:

The anthropometric dimensions and skill of the handlers who carried out the study were analysed/considered. The recommendations for space requirements take into account that:

• all handlers carrying out the study were fairly skilled;

• a standard hospital bed, with or without orthopaedic or other attachments (2190 mm × 1050 mm, or 2370 mm × 1050 mm with bed extended) and;

• a bariatric bed for a 450 kg patient (2330 mm × 1080 mm).

• people with deep trunks need more space when turning sideways, that is, facing the side of the bed, as when going through “pinch” points;

The study was based on the following assumptions/ qualifications:

• tall people’s elbows stick out more when pushing and pulling on bed frames;

• attendants grasp the bed frame at the foot and head when manoeuvring beds – even when there are orthopaedic attachments present;

• those who are of “large” build, for example have broad shoulders, require more space as they walk alongside the bed.

• four attendants are frequently used to manoeuvre beds;

• when pushing beds along corridors, attendants are usually positioned at the side of the bed but move to the end when required, for example at pinch points;

The space requirements illustrated in Figures 8–11, 16 and 17 and associated text generally represent the findings of the study. However, it should be noted that the minimum ecw of 1200 mm in Figure 17 and noted in paragraph 8.19 is an agreed acceptable DH minimum, based on the recorded data during the study and professional opinion, but was not recommended in the report associated with the study.

• attendants generally do not have to stay at the side of the bed during movement unless “bagging” a patient (for example providing artificial respiration to a patient on a ventilator);

• orthopaedic attachments require a minimum height of 1950 mm to ensure clearance under door frames or door closer mechanisms where present.

[HBN 00-04 – PDF page 56]

Appendix 2 – Variations from Approved

Document M and BS 8300

Corridor widths for general traffic

premises is 4200 mm. Therefore, 14 risers are considered appropriate.

Visual warnings, change in level

Rising steps are readily detected by cane users, and the use of contrast nosings and handrails assists other visually impaired users; this Health Building Note therefore recommends that over and above recommendations in Approved Document M and BS 8300, for the safety of visually-impaired people a visual warning zone, using finishes that contrast visually with the surrounding floor, be applied at the top landing of all changes in level.

Approved Document M requires a minimum unobstructed corridor width of 1200 mm, if passing spaces are provided. However, BS 8300 states a preferred clear corridor width of 1800 mm in buildings with a significant number of wheelchair users. Due to the nature of the users/visitors in healthcare premises (that is, increased semi-ambulant and wheelchair users) and having considered the space requirements for circulation, this guidance recommends a minimum unobstructed width of 1500 mm but recognises that 1800 mm will allow most users to pass comfortably.

Lobby length/size

Approved Document M (2013) states: “Where a lift is provided, as a minimum a utility stair should be designed to be suitable for people with impaired sight. The lift should be suitable for an unaccompanied wheelchair user. Suitable provision should also be made for people with sensory impairments. Measures should also be adopted which give a disabled person sufficient time to enter the lift to reduce the risk of contact with closing doors.”

BS 8300 allows for a reduction in lobby length if doors feature vision panels, on the basis that a sighted person would be able to see a user immediately in front of the door and not open the door into them. However, vision panels will not assist visually impaired people to negotiate a lobby and are therefore not used as an argument for reducing lobby length in healthcare premises.

Lifts

Approved Document M allows for a reduction in lobby length of 100 mm for every 100 mm added to the lobby width. Research for this Health Building Note indicates there is no clear evidence to support this argument. This guide does not, therefore, recommend applying this argument to justify reducing lobby lengths in healthcare premises.

Internal stair tread

Approved Document M and BS 8300 recommend a minimum lift car size of 1100 mm × 1400 mm for wheelchair access with a handrail fitted on the back wall of the lift car. However, both documents acknowledge that the minimum car size has access limitations. In healthcare premises, for flexibility of access, handrails are recommended on both side walls as well as the back wall. Additionally, to allow for more than one attendant with a wheelchair user, a minimum lift car size of 1600 mm × 1400 mm is recommended.

Handrails

Approved Document M requires internal staircase tread goings to be a minimum of 250 mm whilst BS 8300 recommends 250–300 mm with a preference for 300 mm. This Health Building Note aligns closely with BS 8300 and recommends a minimum of 280 mm and a preference for 300 mm.

Internal stairs, number of risers in flights

The Department of Communities and Local Government (DCLG) has clarified its recommendations in relation to handrail sizes. In this clarification, the required cross- section size of circular handrails is 40–50 mm. However for healthcare premises, in accordance with (unpublished) research commissioned by the Department of Environment and carried out by Robert Feeney Associates, 40–45 mm is recommended.

Approved Document M states that “normally a flight between landings should contain no more than 12 risers”. However, the floor-to-floor height in many healthcare

[HBN 00-04 – PDF page 57]

Doors opening into corridors

The required clear space around handrails is 50–60 mm. However for healthcare premises, in accordance with research cited earlier, 60–75 mm is recommended.

Door access space

Approved Document M defines the minimum clear width to the latch side of a manually operated door as 300 mm. However, BS 8300 states: “Increasing this space to 450 mm will improve manoeuvrability, reduce the risk of wheelchairs colliding with the wall, and speed up completion of the task.”

This view is supported by this guidance, which recommends 450 mm as a minimum clear width to the latch side of the door, to allow for less experienced users, with a preference for 600 mm.

Approved Document M states: “Corridors and passageways will satisfy Requirement M1 or M2 if: . . . (g) any door opening towards a corridor, which is a major access route or an escape route, [is] recessed so that, when fully open, it does not project into the corridor space, except where the doors are to minor utility facilities, such as small store rooms and locked duct cupboards; (h) any door from a unisex wheelchair-accessible toilet projects when open into a corrridor that is not a major access route or an escape route, provided the corridor is at least 1800 mm wide at that point.” However, this guidance recommends that non-recessed outward-opening doors (other than doors to locked service cupboards) are not allowed on any corrridor in patient areas in healthcare premises based on a sensory impairment risk assessment.