SHTM 03-01 Part A: Appendix 2: Summary of design conditions

Ventilation for Healthcare - Design and validation (SHTM 03-01 Part A) · PDF pages 169–170 of 227 · Source file: shtm-03-01-part-a-v30-feb-2022.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[SHTM 03-01 Part A – PDF page 169]

Appendix 2: Summary of design conditions

Pressure

Temp

Comments (for

Table A1 Design conditions for miscellaneous rooms Application Ventilation Air- change

(Pascal

Supply filter grade

Noise (dB(A))

(°C)

Pa)

rate (ac/h)

further information see Chapter 8)

(BS EN 16798 or BS EN 1822-1)

S/N 6 – SUP2 35 18–28

General ward (level 0 and 1 care)

E 6 –ve – 45 –

Communal ward toilet

Single room S/E/N 6 0 or –ve SUP2 35 18–28 Single room WC E >10 –ve – 45 – Clean utility S 6 +ve SUP3 45 18–22 Dirty utility E 6 –ve – 45 – Ward isolation room (PPVL)

S 10 Lobby +10 Room 0

E 10 –5 SUP2 35 – See Table 4

SUP2 35 – See Scottish Health Planning Note 4 (Supplement 1) Infectious diseases isolation room

S 10 +10 E12 35 – See Table 3

Neutropaenic patient ward

Critical care areas (Level 2 and 3 care)

S & E 15 0 SUP2 45 18–25 Provide clean airflow path

S 10 +10 SUP1 35 – Isolation room may be –ve pressure or PPVL. See Table 3 Birthing room S & E 10 0 SUP2 45 20–25 See Table 5 NICU/SCBU S & E 10 +ve SUP1 35 20–28 Isolation room may be –ve pressure Operating department recovery room

S & E 10 +ve SUP2 45 18–22

Catheterisation room

Interventional or non- interventional Imaging room of any type

S & E 15 S/E SUP2 45 18–28

S & E 10 +ve SUP2 48 – Stable conditions as specified for the imaging equipment Sedation recovery room as in paragraph

S & E 15 -5 SUP2 40 20–25 See Table 2

Endoscopic procedure room

E 10 –ve – 45 –

Endoscope reprocessing wash room

S & E 10 Neutral SUP2 45 20–25 See Table 2

General treatment room

S & E 6 – SUP2 – 18–25 See Table 2

Emergency department waiting area

[SHTM 03-01 Part A – PDF page 170]

Pressure

Temp

Comments (for

Application Ventilation Air- change

(Pascal

Supply filter grade

Noise (dB(A))

(°C)

Pa)

rate (ac/h)

further information see Chapter 8)

(BS EN 16798 or BS EN 1822-1)

Containment level 3 laboratory

# >20 # H14* – 18–22 # See ACDP guide; *Filter in extract See Table 4 Post-mortem room

S & E S = 10 E = 12

–ve SUP2 45 18–22 Provide clean airflow path Specimen store E – –ve – – – Fan accessible from outside of store Notes:

For general and UCV operating suites and associated rooms, see specific guidance in Chapter 8 and typical design solutions in Appendix 7

Waiting and circulation areas should be directly or indirectly ventilated to provide a comfortable environment and control airborne contamination and odours.

18–22°C indicates the range over which the temperature may float.

18-22°C indicates the range over which the temperature should be capable of being controlled at any point within that range.

S = Supply

E = Extract

N = Natural ventilation where possible where natural ventilation is used the design must reflect clauses 5.2 to 5.9

SUP refers to the supply air quality as defined in BS EN 16798