SHTM 03-01 Part A: Appendix 2: Summary of design conditions
[SHTM 03-01 Part A – PDF page 169]
Appendix 2: Summary of design conditions
Pressure
Temp
Comments (for
Table A1 Design conditions for miscellaneous rooms Application Ventilation Air- change
(Pascal
Supply filter grade
Noise (dB(A))
(°C)
Pa)
rate (ac/h)
further information see Chapter 8)
(BS EN 16798 or BS EN 1822-1)
S/N 6 – SUP2 35 18–28
General ward (level 0 and 1 care)
E 6 –ve – 45 –
Communal ward toilet
Single room S/E/N 6 0 or –ve SUP2 35 18–28 Single room WC E >10 –ve – 45 – Clean utility S 6 +ve SUP3 45 18–22 Dirty utility E 6 –ve – 45 – Ward isolation room (PPVL)
S 10 Lobby +10 Room 0
E 10 –5 SUP2 35 – See Table 4
SUP2 35 – See Scottish Health Planning Note 4 (Supplement 1) Infectious diseases isolation room
S 10 +10 E12 35 – See Table 3
Neutropaenic patient ward
Critical care areas (Level 2 and 3 care)
S & E 15 0 SUP2 45 18–25 Provide clean airflow path
S 10 +10 SUP1 35 – Isolation room may be –ve pressure or PPVL. See Table 3 Birthing room S & E 10 0 SUP2 45 20–25 See Table 5 NICU/SCBU S & E 10 +ve SUP1 35 20–28 Isolation room may be –ve pressure Operating department recovery room
S & E 10 +ve SUP2 45 18–22
Catheterisation room
Interventional or non- interventional Imaging room of any type
S & E 15 S/E SUP2 45 18–28
S & E 10 +ve SUP2 48 – Stable conditions as specified for the imaging equipment Sedation recovery room as in paragraph
S & E 15 -5 SUP2 40 20–25 See Table 2
Endoscopic procedure room
E 10 –ve – 45 –
Endoscope reprocessing wash room
S & E 10 Neutral SUP2 45 20–25 See Table 2
General treatment room
S & E 6 – SUP2 – 18–25 See Table 2
Emergency department waiting area
[SHTM 03-01 Part A – PDF page 170]
Pressure
Temp
Comments (for
Application Ventilation Air- change
(Pascal
Supply filter grade
Noise (dB(A))
(°C)
Pa)
rate (ac/h)
further information see Chapter 8)
(BS EN 16798 or BS EN 1822-1)
Containment level 3 laboratory
# >20 # H14* – 18–22 # See ACDP guide; *Filter in extract See Table 4 Post-mortem room
S & E S = 10 E = 12
–ve SUP2 45 18–22 Provide clean airflow path Specimen store E – –ve – – – Fan accessible from outside of store Notes:
For general and UCV operating suites and associated rooms, see specific guidance in Chapter 8 and typical design solutions in Appendix 7
Waiting and circulation areas should be directly or indirectly ventilated to provide a comfortable environment and control airborne contamination and odours.
18–22°C indicates the range over which the temperature may float.
18-22°C indicates the range over which the temperature should be capable of being controlled at any point within that range.
S = Supply
E = Extract
N = Natural ventilation where possible where natural ventilation is used the design must reflect clauses 5.2 to 5.9
SUP refers to the supply air quality as defined in BS EN 16798