SHTM 03-01 Part A: Executive Summary
[SHTM 03-01 Part A – PDF page 6]
Executive Summary
Scottish Health Technical Memorandum 03-01 – ‘Specialised ventilation in healthcare premises’ is published in two parts:
Part A: The concept, design, specification, installation and acceptance testing of healthcare ventilation systems.
Part B: The management, operation, maintenance and routine testing of existing healthcare ventilation systems.
The documents give comprehensive advice and guidance on the legal requirements, design implications, maintenance and operation of specialised ventilation in healthcare premises providing acute care. The use of these premises is very intense, the occupancy level high and the patients may be particularly susceptible to airborne infection risks. Their condition may also require close control of the environment.
The ventilation of non-healthcare facilities within the hospital curtilage should be designed to suit the application and specific guidance relating to the activity should be followed, for example pharmacy, central decontamination unit, etc. However, as they are on the hospital site, the means of providing ventilation should not adversely impact upon the hospital (for example, evaporative cooling towers should not be installed, sound levels should be appropriate and if the facility is within or attached to an area accessed by patients, their needs and the risk of airborne contamination should be considered).
In other types of healthcare facility that are outside of the hospital curtilage, for example GP practices, health centres, minor injuries units, dental, ophthalmic and podiatry clinics, mental health facilities, respite and long stay care homes and hospices, a risk assessment of the nature of the treatment being delivered, condition of the patients and intensity of use needs to be undertaken by those responsible for the facility in order to determine the extent to which this guidance will be applicable.
The guidance contained in Part A of this Scottish Health Technical Memorandum applies to new installations and major refurbishments of existing installations and should be considered as the standard to be achieved.
The guidance contained in Part B of this Scottish Health Technical Memorandum applies to all ventilation systems installed in healthcare premises irrespective of the age of the installation and should be considered as the standard to be achieved.
Scottish Health Technical Memorandum 03-01 (2022) supersedes all previous versions of Scottish Health Technical Memorandum 03-01 – ‘Specialised ventilation in healthcare premises’ (2014). It also supersedes SHTM 2025 (1994) and DV4 (1983).
Who should use this guidance?
This document is aimed at specifiers, designers, suppliers, installers, estates and facilities managers and operations. Elements of the document will also be relevant to
[SHTM 03-01 Part A – PDF page 7]
managers concerned with the day-to-day management of healthcare facilities and senior healthcare management.
Main changes since the 2014 edition
design information for specific healthcare applications has been revised and information on the reason for ventilation given. For example, endoscopy rooms may now be either negative (to contain and remove odours and manage airborne risks to staff) or positive pressure (to maintain a higher level of cleanliness where it is intended to puncture body membranes with the endoscope). These endoscopy-specific risks (i.e. waste anaesthetic gases and pathogenic material (for example, multi-drug- resistant tuberculosis) discharged by the patient during the procedure being undertaken) were identified prior to the SARS-CoV-2 pandemic. As with other elements in Part A, the application of this change is not retrospective but applies to new installations and major refurbishments (see Preamble above);
the client’s needs and legal requirements are more clearly explained;
this edition of Scottish Health Technical Memorandum 03-01 introduces the concept of the Ventilation Safety Group in healthcare organisations (similar to the Water Safety Group in Scottish Health Technical Memorandum 04-01 and the Electrical Safety Group in Scottish Health Technical Memorandum 06-01). This is a multidisciplinary group whose remit will be to assess all aspects of ventilation safety and resilience required for the safe development and operation of healthcare premises;
the SHTM introduces a standard method of identifying and labelling ventilation systems and the creation of an inventory of installed systems;
the issues of resilience and diversity are addressed;
guidance is provided on refurbishments or when changing the use of an existing installation;
guidance is given on lifecycle and the updating of mid-life plant;
design information for specific healthcare application has been extensively revised;
issues around rooms where anaesthetic agents are used are addressed;
airflow rates are more tailored to the applications to take advantage of new fan and control technology and so reduce energy consumption;
revised air quality and filter standards are given;
new and emerging technologies are catered for;
advice is given on installation standards and the appointment of an independent validator;
more detailed information is given on the commissioning process;
validation acceptance standards and methodology has been completely revised;
routine inspection and maintenance guidance has been revised and updated.
[SHTM 03-01 Part A – PDF page 8]
Net Zero Carbon
Scottish Health Technical Memorandum 03-01 supports UK legislation to bring all greenhouse gas emissions to net zero by 2045, and promotes sustainable methods of ventilation in healthcare facilities.
SHTM’s core principle is that the default method of ventilation should as far as possible be natural ventilation followed by mixed mode (natural with mechanical ventilation), with mechanical ventilation being the last option.
The energy consumption of ventilation systems should be further minimised by specifying solutions with the lowest lifecycle environmental cost. The basic objective of energy-saving strategies in this SHTM is to provide the required ventilation service using the minimum energy. To this end, Scottish Health Technical Memorandum 03- 01 recommends switching a system “off” when not required to be the most energy- efficient policy. If the system is needed to maintain a minimum background condition, reducing its output by “setting back” to the minimum necessary to achieve and maintain the desired condition is the next best option.
Fans represent an enormous potential for energy savings to reduce carbon emissions, as they are among the largest single users of energy (they use approximately 40% of all electricity in ventilation systems). The European Regulation 1253/2014, implementing the Energy-related Products (ErP) Directive, has significantly reduced the power to drive fans. Accordingly, Scottish Health Technical Memorandum 03-01 recommends using electronically commutated fans, as these have been proven to be the most energy-efficient, while also advising that belt-driven fans should no longer be installed.
There have been many legislative changes aimed at reducing energy consumption and technical advances that have increased operational efficiency. This revised SHTM incorporates those changes and has amended many of the design parameters for healthcare ventilation. Designs that are simply repeated from previous installations designed to superseded standards and guidance will not meet the revised energy or operational standards and will not produce a compliant result.