Home › Scotland (NHS Scotland Assure / HFS) › HBN 00-03 › Health Building Note 00-03 – 11 Generic clinical support spaces: Miscellaneous

HBN 00-03: Health Building Note 00-03 – 11 Generic clinical support spaces: Miscellaneous

Core guidance - Clinical and clinical support spaces (HBN 00-03) · PDF pages 131–136 of 166 · Source file: hbn-00-03-oct-2014.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[HBN 00-03 – PDF page 131]

11 Generic clinical support spaces: Miscellaneous

Near patient testing room

11.6 Two room layouts have been provided (see Figures 102 and 103).

Room description and layout

11.1 This room is used to carry out tests on body fluids (for example urea, electrolytes, blood sugar, blood gases etc) that require instant results.

11.7 Both layouts show an outward opening door. The need to include a door depends on the location and security of the space. Where an outward opening door is provided, it must not open onto a circulation route.

11.8 Both layouts also include zones for blood sample testing, computer access and clinical hand washing.

11.2 The sink will be required if demineralised water is needed. Requirements for demineralised water will depend on the type of equipment used.

11.9 A sharps bin should be located on the laboratory bench. A stool may be provided in place of the laboratory chair.

11.3 A dedicated pneumatic tube link to the main pathology laboratory may be provided to allow specimens to be sent for more complex analysis.

11.4 A specimen fridge will be required where samples have to be stored before sending to the main pathology laboratories.

11.10 The illustrated space requirements for accessing modular base and upper cabinets is based on space to access standard cupboards, not using baskets or trays. However, adequate space is available for side access to baskets or trays.

11.5 Specialist advice should be sought to ensure compliance with CoSHH Regulations.

[HBN 00-03 – PDF page 132]

11 Generic clinical support spaces: Miscellaneous

Optional

lab sink

Glove

and apron

dispenser

Optional

laboratory

fridge

Clinical

wash-hand

basin

Supplies trolley

under lab bench

Blood gas

analyser

Paper towel

dispenser

Lab chair

Display board

Computer

and printer

Mobile

under-bench

storage

Wall

cupboard

Engineering services outlet zone

Engineering services outlet zone

Sack

holder

Glove

and apron

dispenser

Optional

lab sink

Lab chair

Clinical

wash-hand

basin

Optional

laboratory

fridge

under lab bench

Paper towel

dispenser

Sack

holder

Blood gas

analyser

Display board

Computer

and printer

Wall

cupboard

Mobile

under-bench

storage

Engineering services outlet zone Supplies trolley

Engineering services outlet zone

Figure 102 Near patient testing room (option 1) Figure 103 Near patient testing room (option 2)

[HBN 00-03 – PDF page 133]

Figure 104 Space requirements for standing use of a clinical wash-hand basin

Ergonomic drawings

assembly

Clinical wash-hand basin

Space to use basin at high level, ie above 600 mm from floor level

11.11 These ergonomic drawings (see Figure 104) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

11.12 The basin should be fitted with non- touch taps.

Glove & apron dispenser

high level

Space to use basin at

Space to use

11.13 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

from floor level

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

11.14 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

Concealed waste

Minimum distance to side wall

~120 service duct

11.15 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

11.16 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

Comfortable reach to side of basin

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

Flush concealed services duct

11.17 Lever taps are not illustrated.

11.18 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 134]

11 Generic clinical support spaces: Miscellaneous

Standard base and wall cupboards

500 mm, the reach dimensions illustrated relate to the front edge of the wall cupboard (that is, reaching into the cupboard would proved difficult).

11.19 This ergonomic drawing (see Figure 105) shows the space requirements to access standard, floor mounted, base and wall cupboards. Where worktops or other obstructions project more than

Figure 105 Space requirements for access to standard, floor mounted base and wall cupboards

Recommended depth of cupboard depends upon depth of worktop

Distance between front of worktop and front of wall cupboard Depth of wall cupboard

Sloping top to wall cupboards will assist with cleaning/ infection control

Maximum height of wall cupboard

Maximum height that allows all users access

Clear space between worktop

and bottom of wall cupboard

Maximum height that allows full forward reach onto shelf etc

Space for working and ambulant passing, 1600 preferred for frequent passing

Space for ambulant passing

Standing close for infrequent passing

ambulant passing when someone is working at the worktop

Space for working. (900) to access base cupboard

[HBN 00-03 – PDF page 135]

Parking bay

Relatives’ overnight stay

Room description

Room description and layout

11.24 This room is for sleeping only. It should be able to accommodate two people.

11.25 Access is required to beverage-making facilities.

11.20 Parking bays are used to hold mobile equipment when not in use. The bays should be easily accessible and close to areas served. Their location should not disrupt circulation routes.

11.26 It should be combined with an en-suite shower and toilet.

11.21 Generally a bay of 2 m² with a power supply for recharging equipment is sufficient.

11.27 The room layout provided (see Figure 106) includes a single divan bed and a separate single sofa bed, for a maximum of two adults, including one wheelchair user.

11.22 The design of the bay should reflect the area in which it is located. It may be painted in a different colour to the surrounding area if it needs to be quickly identifiable. Alternatively, its ceiling height may be raised to that of the surrounding area in order to blend in.

11.23 No room layout has been provided.

Figure 106 Space requirements for relatives’ overnight stay, single divan bed and separate single sofa bed

Table

Settee bed

Access to room or en-suite

Bedside table B d id Bedside dside Bedside Be table t bl t bl table

Mirror

Divan bed

Access to room or en-suite

[HBN 00-03 – PDF page 136]

11 Generic clinical support spaces: Miscellaneous

Ergonomic drawings

Space to access a divan bed

11.28 This ergonomic drawing (see Figure 107) shows the space requirements for wheelchair and ambulant access to a divan bed.

Figure 107 Space requirements to access a divan bed

Wheelchair turning

Bedside table

Ambulant access to bed

Divan bed