HBN 00-03: Health Building Note 00-03 – 11 Generic clinical support spaces: Miscellaneous
[HBN 00-03 – PDF page 131]
11 Generic clinical support spaces: Miscellaneous
Near patient testing room
11.6 Two room layouts have been provided (see Figures 102 and 103).
Room description and layout
11.1 This room is used to carry out tests on body fluids (for example urea, electrolytes, blood sugar, blood gases etc) that require instant results.
11.7 Both layouts show an outward opening door. The need to include a door depends on the location and security of the space. Where an outward opening door is provided, it must not open onto a circulation route.
11.8 Both layouts also include zones for blood sample testing, computer access and clinical hand washing.
11.2 The sink will be required if demineralised water is needed. Requirements for demineralised water will depend on the type of equipment used.
11.9 A sharps bin should be located on the laboratory bench. A stool may be provided in place of the laboratory chair.
11.3 A dedicated pneumatic tube link to the main pathology laboratory may be provided to allow specimens to be sent for more complex analysis.
11.4 A specimen fridge will be required where samples have to be stored before sending to the main pathology laboratories.
11.10 The illustrated space requirements for accessing modular base and upper cabinets is based on space to access standard cupboards, not using baskets or trays. However, adequate space is available for side access to baskets or trays.
11.5 Specialist advice should be sought to ensure compliance with CoSHH Regulations.
[HBN 00-03 – PDF page 132]
11 Generic clinical support spaces: Miscellaneous
Optional
lab sink
Glove
and apron
dispenser
Optional
laboratory
fridge
Clinical
wash-hand
basin
Supplies trolley
under lab bench
Blood gas
analyser
Paper towel
dispenser
Lab chair
Display board
Computer
and printer
Mobile
under-bench
storage
Wall
cupboard
Engineering services outlet zone
Engineering services outlet zone
Sack
holder
Glove
and apron
dispenser
Optional
lab sink
Lab chair
Clinical
wash-hand
basin
Optional
laboratory
fridge
under lab bench
Paper towel
dispenser
Sack
holder
Blood gas
analyser
Display board
Computer
and printer
Wall
cupboard
Mobile
under-bench
storage
Engineering services outlet zone Supplies trolley
Engineering services outlet zone
Figure 102 Near patient testing room (option 1) Figure 103 Near patient testing room (option 2)
[HBN 00-03 – PDF page 133]
Figure 104 Space requirements for standing use of a clinical wash-hand basin
Ergonomic drawings
assembly
Clinical wash-hand basin
Space to use basin at high level, ie above 600 mm from floor level
11.11 These ergonomic drawings (see Figure 104) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.
Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser
11.12 The basin should be fitted with non- touch taps.
Glove & apron dispenser
high level
Space to use basin at
Space to use
11.13 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.
from floor level
ie up to 600 mm
basin at low level,
Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)
Concealed waste
~120 service duct
Minimum distance to side wall
Paper towel dispenser
11.14 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.
(50) Minimum clearance between paper towel dispenser and duct
Projecting concealed services duct
Concealed waste
Minimum distance to side wall
~120 service duct
11.15 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.
11.16 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:
Space to use
from floor level
Space to use
ie up to 600 mm
basin at low level,
from floor level
ie above 600 mm
basin at high level,
passing
ambulant
Comfortable reach to side of basin
“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”
Flush concealed services duct
11.17 Lever taps are not illustrated.
11.18 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.
[HBN 00-03 – PDF page 134]
11 Generic clinical support spaces: Miscellaneous
Standard base and wall cupboards
500 mm, the reach dimensions illustrated relate to the front edge of the wall cupboard (that is, reaching into the cupboard would proved difficult).
11.19 This ergonomic drawing (see Figure 105) shows the space requirements to access standard, floor mounted, base and wall cupboards. Where worktops or other obstructions project more than
Figure 105 Space requirements for access to standard, floor mounted base and wall cupboards
Recommended depth of cupboard depends upon depth of worktop
Distance between front of worktop and front of wall cupboard Depth of wall cupboard
Sloping top to wall cupboards will assist with cleaning/ infection control
Maximum height of wall cupboard
Maximum height that allows all users access
Clear space between worktop
and bottom of wall cupboard
Maximum height that allows full forward reach onto shelf etc
Space for working and ambulant passing, 1600 preferred for frequent passing
Space for ambulant passing
Standing close for infrequent passing
ambulant passing when someone is working at the worktop
Space for working. (900) to access base cupboard
[HBN 00-03 – PDF page 135]
Parking bay
Relatives’ overnight stay
Room description
Room description and layout
11.24 This room is for sleeping only. It should be able to accommodate two people.
11.25 Access is required to beverage-making facilities.
11.20 Parking bays are used to hold mobile equipment when not in use. The bays should be easily accessible and close to areas served. Their location should not disrupt circulation routes.
11.26 It should be combined with an en-suite shower and toilet.
11.21 Generally a bay of 2 m² with a power supply for recharging equipment is sufficient.
11.27 The room layout provided (see Figure 106) includes a single divan bed and a separate single sofa bed, for a maximum of two adults, including one wheelchair user.
11.22 The design of the bay should reflect the area in which it is located. It may be painted in a different colour to the surrounding area if it needs to be quickly identifiable. Alternatively, its ceiling height may be raised to that of the surrounding area in order to blend in.
11.23 No room layout has been provided.
Figure 106 Space requirements for relatives’ overnight stay, single divan bed and separate single sofa bed
Table
Settee bed
Access to room or en-suite
Bedside table B d id Bedside dside Bedside Be table t bl t bl table
Mirror
Divan bed
Access to room or en-suite
[HBN 00-03 – PDF page 136]
11 Generic clinical support spaces: Miscellaneous
Ergonomic drawings
Space to access a divan bed
11.28 This ergonomic drawing (see Figure 107) shows the space requirements for wheelchair and ambulant access to a divan bed.
Figure 107 Space requirements to access a divan bed
Wheelchair turning
Bedside table
Ambulant access to bed
Divan bed