[HBN 00-03 – PDF page 66]

6 Generic clinical spaces: Treatment rooms

Treatment room: all-round couch access

6.6 The following procedures require a treatment room (that is, with mechanical ventilation):

Room description and layout

• invasive procedures, that is, procedures that cut the superficial layers of the skin, for example removal of moles, warts, corns, biopsies etc;

6.1 This room is intended as a flexible clinical space to be used by a wide range of specialties.

• use of certain rigid endoscopes including laryngoscopes (used during resuscitation procedures), otoscopes and ophthalmoscopes.

6.2 The room has been sized to accommodate mobile diagnostic equipment, for example mobile ultrasound equipment.

6.7 Blackout blinds and dimmable lighting are recommended for flexibility in use, for example sessional ultrasound, ENT or eye care use.

6.3 It is assumed that sterile instruments and dressings will be held within the treatment room on an instruments/dressings trolley. The trolley may be prepared in the treatment room or an associated clean utility room.

6.8 The room layout provided (see Figure 47) shows a standard three-section couch.

6.4 Medical oxygen and vacuum will generally be required. Medical air, nitrous oxide and gas scavenging may also be required. See Health Technical Memorandum 02-01 for specific requirements.

6.9 The alternative door location (that is, to match the layout of option 1 of the double-sided couch access consulting/examination) implies that the window would be located behind the couch. This would require privacy control, which is not good, psychologically, for patients. However, it would provide better trolley access to the couch in an emergency.

6.5 Treatment rooms should be mechanically ventilated, with 10 air changes per hour supply and extract.

[HBN 00-03 – PDF page 67]

Figure 47 Treatment room: all-round couch access

Engineering services outlet zone

Possible window location

Stool

Chair

Supplies trolley

Dressing/ instrument trolley

Engineering services outlet zone

Ceiling- mounted examination light

Clinical workstation

Pendant services

Couch with paper roll attached

Clinical wash-hand basin

Optional privacy curtain

Sack holder

Sack holder

Alternative door location

Glove and apron dispenser

Paper towel dispenser

[HBN 00-03 – PDF page 68]

6 Generic clinical spaces: Treatment rooms

Figure 48 Space requirements for standing use of a clinical wash-hand basin

Ergonomic drawings

assembly

Clinical wash-hand basin

Space to use basin at high level, ie above 600 mm from floor level

6.10 These ergonomic drawings (see Figure 48) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

6.11 The basin should be fitted with non- touch taps.

Glove & apron dispenser

high level

Space to use basin at

Space to use

from floor level

6.12 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

6.13 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

Concealed waste

Minimum distance to side wall

~120 service duct

6.14 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

6.15 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

Comfortable reach to side of basin

Flush concealed services duct

6.16 Lever taps are not illustrated.

6.17 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 69]

Clinical workstation

6.18 This ergonomic drawing (see Figure 49) shows the space requirements for a clinical workstation.

6.19 The clinical workstation is intended for accessing and updating patient records within a clinical environment. It should only be used for short periods of time.

Figure 49 Space requirements for a clinical workstation

Approximate

Approximate

sitting height

standing height

Chair

standing at

clinical

workstation

workstation

sitting at clinical

[HBN 00-03 – PDF page 70]

6 Generic clinical spaces: Treatment rooms

Couch with all-round access

6.20 This ergonomic drawing (see Figure 50) shows the space requirements for all-round access to a three- section couch.

6.22 The type of pendant required will vary depending upon the level of services being provided (for example fixed power and data only, power data and medical gas with vertical adjustment, or with vertical and horizontal adjustment etc). However, this document assumes that in a generic treatment room only simple services are anticipated.

6.21 Pendant services should be provided where all- round couch access is required. The type of pendant will vary depending on the services being provided.

Figure 50 Space requirements for all-round access to three-section couch

Pendant services

height range

Approx adjustable

changing

examination/

examination/

treatment

treatment

Pendant services

treatment

examination/

Couch with paper roll attached

Ceiling- mounted examination light

treatment

examination/

[HBN 00-03 – PDF page 71]

Dressing and undressing: ambulant

6.23 These ergonomic drawings (see Figure 51) show the space requirements for ambulant dressing and undressing.

6.24 An identical space provision is suitable for semi- ambulant users though it should be located adjacent to a seating area.

Figure 51 Space requirements for ambulant dressing and undressing

Maximum height

of permissible

low-level

obstructions

Space for full arm movements

when dressing and undressing

Space for arm movements when dressing and undressing

Space at floor/low level for dressing and undressing

Space at floor/low

level for dressing

and undressing

Space for arm movements

when dressing and undressing

[HBN 00-03 – PDF page 72]

6 Generic clinical spaces: Treatment rooms

Treatment room: double-sided couch access

6.31 Blackout blinds and dimmable lighting are recommended for flexibility in use, for example sessional ultrasound, ENT or eye care use.

Room description and layout

6.32 Two room layouts have been provided (see Figures 52 and 53).

6.25 This room is intended as a flexible clinical space to be used by a wide range of specialties.

6.26 The room has been sized to accommodate mobile diagnostic equipment, for example mobile ultrasound equipment.

6.33 Both layouts include a standard three-section couch and a privacy curtain separating the couch end of the room. Alternatively, a privacy curtain may be included inside the door. See Health Building Note 00-04 for further details.

6.34 Option 1 may accommodate an island couch if engineering services are provided using a pendant and the privacy curtain is located just inside the door.

6.27 It is assumed that sterile instruments and dressings will be held within the treatment room on an instruments/dressings trolley. The trolley may be prepared in the treatment room or an associated clean utility room.

6.28 Medical oxygen and vacuum will generally be required. Medical air, nitrous oxide and gas scavenging may also be required. See Health Technical Memorandum 02-01 for specific requirements.

6.29 Treatment rooms should be mechanically ventilated, with 10 air changes per hour supply and extract.

6.35 The alternative door location on option 1 (that is, to match the layout of option 1 of the double-sided couch access consulting/examination room) implies that the window would be located behind the couch. This would require privacy control within the curtained area, which is not good, psychologically, for patients. However, the alternative door location would provide better patient trolley access to the couch in an emergency.

6.30 The following procedures require a treatment room (that is, with mechanical ventilation):

• invasive procedures, that is, procedures that cut the superficial layers of the skin, for example removal of moles, warts, corns, biopsies etc;

• use of certain rigid endoscopes including laryngoscopes (used during resuscitation procedures), otoscopes and ophthalmoscopes.

6.36 Option 2 is effectively identical to the consulting/ examination room double-sided couch access, option 2. The clinical administration space is on the inside wall of the room (that is, away from the natural light) and the examination space is on the outside wall (that is, requiring privacy control due to the proximity of the window). The room layout cannot comfortably accommodate an island couch layout.

[HBN 00-03 – PDF page 73]

Engineering services outlet zone

Chair

Dressing/

instrument

trolley

Couch with

paper roll

attached

Ceiling-

mounted

examination

light

Supplies

trolley

Possible window location

Chair

Clinical

wash-hand

basin

Sack

holder

Sack

Clinical

workstation

Engineering services outlet zone

Paper

towel

dispenser

holder Glove

and apron

dispenser

Engineering services outlet zone

Engineering services outlet zone

Alternative door location

Chair

Engineering services outlet zone

Clinical

workstation

Stool

Optional privacy curtain

Dressing/

instrument

trolley

Clinical

wash-hand

basin

Ceiling-

mounted

examination

light

Paper

towel

dispenser

Possible window location

Sack

holder

Supplies

trolley

Couch with

paper roll

attached

Glove

and apron

dispenser

Sack

holder

Figure 52 Treatment room: double-sided couch access (option 1) Figure 53 Treatment room: double-sided couch access (option 2)

Engineering services outlet zone

[HBN 00-03 – PDF page 74]

6 Generic clinical spaces: Treatment rooms

Figure 54 Space requirements for standing use of a clinical wash-hand basin

Ergonomic drawings

assembly

Clinical wash-hand basin

Space to use basin at high level, ie above 600 mm from floor level

6.37 These ergonomic drawings (see Figure 54) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

6.38 The basin should be fitted with non- touch taps.

Glove & apron dispenser

high level

Space to use basin at

Space to use

from floor level

6.39 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

6.40 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

Concealed waste

Minimum distance to side wall

~120 service duct

6.41 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

6.42 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

Comfortable reach to side of basin

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

Flush concealed services duct

6.43 Lever taps are not illustrated.

6.44 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 75]

Clinical workstation

6.45 This ergonomic drawing (see Figure 55) shows the space requirements for a clinical workstation.

6.46 The clinical workstation is intended for accessing and updating patient records within a clinical environment. It should only be used for short periods of time.

Figure 55 Space requirements for a clinical workstation

Approximate

Approximate

sitting height

standing height

Chair

standing at

clinical

workstation

workstation

sitting at clinical

[HBN 00-03 – PDF page 76]

6 Generic clinical spaces: Treatment rooms

Couch: double-sided access

6.48 Ceiling-mounted examination lights should be provided where double-sided couch access is required.

6.47 These ergonomic drawings (see Figure 56) show the space requirements for double-sided access to a three-section couch. The overall general space requirements for a three-section couch are the same as for a two-section couch.

Figure 56 Space requirements for double-sided access to a three-section couch

Approximate

Suction bottle bracket to be below patient’s chest

Engineering services outlets requirements

see HTM 02-01 and HTM 08-03

height range of couch

Space for changing

examination/

examination/

treatment

treatment

Couch with paper roll attached

Ceiling- mounted examination light

examination/treatment

[HBN 00-03 – PDF page 77]

Treatment chairs (various): double-sided access

including stirrups, leg supports or footrests. The use of the various methods is subject to local clinical and/or patient/client preferences.

6.49 These ergonomic drawings (see Figure 57) show the space requirements for double-sided access to a variety of treatment chairs.

6.52 The podiatry treatment chair incorporates separate leg supports, which may be adjusted independently of one another.

6.50 The reclining treatment/therapy chair provides the most flexible option for general examinations and treatments.

6.53 The activity space for the podiatry treatment chair assumes the examination light is attached to the podiatry trolley. The illustrated chair is mobile. Floor-mounted chairs are also available although these may reduce flexibility in room use.

6.51 The reclining gynaecology chair may be used for general examinations and treatments or female internal examinations. A variety of attachments are available to assist internal examinations of females

Figure 57 Space requirements for double-sided access to a variety of treatment chairs

changing

Space for changing

examination/ treatment

Reclining gynaecology chair

Reclining treatment chair

Ceiling- mounted examination light

reclining position

reclining position

Approx length of chair in

Approx length of chair in

Stool

approx 1050

Stool

treatment

access

examination/

access

Space for changing

access side of treatment chair

access

Podiatry treatment chair

reclining position

Approx length of chair in

chair in sitting position

Approximate length of

Stool

examination

access

for treatment/

Approximate space

[HBN 00-03 – PDF page 78]

6 Generic clinical spaces: Treatment rooms

Dressing and undressing: ambulant

6.54 These ergonomic drawings (see Figure 58) show the space requirements for ambulant dressing and undressing.

6.55 An identical space provision is suitable for semi- ambulant users though it should be located adjacent to a seating area.

Figure 58 Space requirements for ambulant dressing and undressing

Maximum height

of permissible

low-level

obstructions

Space for full arm movements

when dressing and undressing

Space for arm movements when dressing and undressing

Space at floor/low level for dressing and undressing

Space at floor/low

level for dressing

and undressing

Space for arm movements

when dressing and undressing