HBN 00-03: Health Building Note 00-03 – 6 Generic clinical spaces: Treatment rooms
[HBN 00-03 – PDF page 66]
6 Generic clinical spaces: Treatment rooms
Treatment room: all-round couch access
6.6 The following procedures require a treatment room (that is, with mechanical ventilation):
Room description and layout
• invasive procedures, that is, procedures that cut the superficial layers of the skin, for example removal of moles, warts, corns, biopsies etc;
6.1 This room is intended as a flexible clinical space to be used by a wide range of specialties.
• use of certain rigid endoscopes including laryngoscopes (used during resuscitation procedures), otoscopes and ophthalmoscopes.
6.2 The room has been sized to accommodate mobile diagnostic equipment, for example mobile ultrasound equipment.
6.7 Blackout blinds and dimmable lighting are recommended for flexibility in use, for example sessional ultrasound, ENT or eye care use.
6.3 It is assumed that sterile instruments and dressings will be held within the treatment room on an instruments/dressings trolley. The trolley may be prepared in the treatment room or an associated clean utility room.
6.8 The room layout provided (see Figure 47) shows a standard three-section couch.
6.4 Medical oxygen and vacuum will generally be required. Medical air, nitrous oxide and gas scavenging may also be required. See Health Technical Memorandum 02-01 for specific requirements.
6.9 The alternative door location (that is, to match the layout of option 1 of the double-sided couch access consulting/examination) implies that the window would be located behind the couch. This would require privacy control, which is not good, psychologically, for patients. However, it would provide better trolley access to the couch in an emergency.
6.5 Treatment rooms should be mechanically ventilated, with 10 air changes per hour supply and extract.
[HBN 00-03 – PDF page 67]
Figure 47 Treatment room: all-round couch access
Engineering services outlet zone
Possible window location
Stool
Chair
Supplies trolley
Dressing/ instrument trolley
Engineering services outlet zone
Ceiling- mounted examination light
Clinical workstation
Pendant services
Couch with paper roll attached
Clinical wash-hand basin
Optional privacy curtain
Sack holder
Sack holder
Alternative door location
Glove and apron dispenser
Paper towel dispenser
[HBN 00-03 – PDF page 68]
6 Generic clinical spaces: Treatment rooms
Figure 48 Space requirements for standing use of a clinical wash-hand basin
Ergonomic drawings
assembly
Clinical wash-hand basin
Space to use basin at high level, ie above 600 mm from floor level
6.10 These ergonomic drawings (see Figure 48) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.
Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser
6.11 The basin should be fitted with non- touch taps.
Glove & apron dispenser
high level
Space to use basin at
Space to use
from floor level
6.12 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.
ie up to 600 mm
basin at low level,
Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)
Concealed waste
~120 service duct
Minimum distance to side wall
Paper towel dispenser
6.13 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.
(50) Minimum clearance between paper towel dispenser and duct
Projecting concealed services duct
Concealed waste
Minimum distance to side wall
~120 service duct
6.14 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.
6.15 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:
Space to use
from floor level
Space to use
ie up to 600 mm
basin at low level,
from floor level
ie above 600 mm
basin at high level,
passing
ambulant
“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”
Comfortable reach to side of basin
Flush concealed services duct
6.16 Lever taps are not illustrated.
6.17 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.
[HBN 00-03 – PDF page 69]
Clinical workstation
6.18 This ergonomic drawing (see Figure 49) shows the space requirements for a clinical workstation.
6.19 The clinical workstation is intended for accessing and updating patient records within a clinical environment. It should only be used for short periods of time.
Figure 49 Space requirements for a clinical workstation
Approximate
Approximate
sitting height
standing height
Chair
standing at
clinical
workstation
workstation
sitting at clinical
[HBN 00-03 – PDF page 70]
6 Generic clinical spaces: Treatment rooms
Couch with all-round access
6.20 This ergonomic drawing (see Figure 50) shows the space requirements for all-round access to a three- section couch.
6.22 The type of pendant required will vary depending upon the level of services being provided (for example fixed power and data only, power data and medical gas with vertical adjustment, or with vertical and horizontal adjustment etc). However, this document assumes that in a generic treatment room only simple services are anticipated.
6.21 Pendant services should be provided where all- round couch access is required. The type of pendant will vary depending on the services being provided.
Figure 50 Space requirements for all-round access to three-section couch
Pendant services
height range
Approx adjustable
changing
examination/
examination/
treatment
treatment
Pendant services
treatment
examination/
Couch with paper roll attached
Ceiling- mounted examination light
treatment
examination/
[HBN 00-03 – PDF page 71]
Dressing and undressing: ambulant
6.23 These ergonomic drawings (see Figure 51) show the space requirements for ambulant dressing and undressing.
6.24 An identical space provision is suitable for semi- ambulant users though it should be located adjacent to a seating area.
Figure 51 Space requirements for ambulant dressing and undressing
Maximum height
of permissible
low-level
obstructions
Space for full arm movements
when dressing and undressing
Space for arm movements when dressing and undressing
Space at floor/low level for dressing and undressing
Space at floor/low
level for dressing
and undressing
Space for arm movements
when dressing and undressing
[HBN 00-03 – PDF page 72]
6 Generic clinical spaces: Treatment rooms
Treatment room: double-sided couch access
6.31 Blackout blinds and dimmable lighting are recommended for flexibility in use, for example sessional ultrasound, ENT or eye care use.
Room description and layout
6.32 Two room layouts have been provided (see Figures 52 and 53).
6.25 This room is intended as a flexible clinical space to be used by a wide range of specialties.
6.26 The room has been sized to accommodate mobile diagnostic equipment, for example mobile ultrasound equipment.
6.33 Both layouts include a standard three-section couch and a privacy curtain separating the couch end of the room. Alternatively, a privacy curtain may be included inside the door. See Health Building Note 00-04 for further details.
6.34 Option 1 may accommodate an island couch if engineering services are provided using a pendant and the privacy curtain is located just inside the door.
6.27 It is assumed that sterile instruments and dressings will be held within the treatment room on an instruments/dressings trolley. The trolley may be prepared in the treatment room or an associated clean utility room.
6.28 Medical oxygen and vacuum will generally be required. Medical air, nitrous oxide and gas scavenging may also be required. See Health Technical Memorandum 02-01 for specific requirements.
6.29 Treatment rooms should be mechanically ventilated, with 10 air changes per hour supply and extract.
6.35 The alternative door location on option 1 (that is, to match the layout of option 1 of the double-sided couch access consulting/examination room) implies that the window would be located behind the couch. This would require privacy control within the curtained area, which is not good, psychologically, for patients. However, the alternative door location would provide better patient trolley access to the couch in an emergency.
6.30 The following procedures require a treatment room (that is, with mechanical ventilation):
• invasive procedures, that is, procedures that cut the superficial layers of the skin, for example removal of moles, warts, corns, biopsies etc;
• use of certain rigid endoscopes including laryngoscopes (used during resuscitation procedures), otoscopes and ophthalmoscopes.
6.36 Option 2 is effectively identical to the consulting/ examination room double-sided couch access, option 2. The clinical administration space is on the inside wall of the room (that is, away from the natural light) and the examination space is on the outside wall (that is, requiring privacy control due to the proximity of the window). The room layout cannot comfortably accommodate an island couch layout.
[HBN 00-03 – PDF page 73]
Engineering services outlet zone
Chair
Dressing/
instrument
trolley
Couch with
paper roll
attached
Ceiling-
mounted
examination
light
Supplies
trolley
Possible window location
Chair
Clinical
wash-hand
basin
Sack
holder
Sack
Clinical
workstation
Engineering services outlet zone
Paper
towel
dispenser
holder Glove
and apron
dispenser
Engineering services outlet zone
Engineering services outlet zone
Alternative door location
Chair
Engineering services outlet zone
Clinical
workstation
Stool
Optional privacy curtain
Dressing/
instrument
trolley
Clinical
wash-hand
basin
Ceiling-
mounted
examination
light
Paper
towel
dispenser
Possible window location
Sack
holder
Supplies
trolley
Couch with
paper roll
attached
Glove
and apron
dispenser
Sack
holder
Figure 52 Treatment room: double-sided couch access (option 1) Figure 53 Treatment room: double-sided couch access (option 2)
Engineering services outlet zone
[HBN 00-03 – PDF page 74]
6 Generic clinical spaces: Treatment rooms
Figure 54 Space requirements for standing use of a clinical wash-hand basin
Ergonomic drawings
assembly
Clinical wash-hand basin
Space to use basin at high level, ie above 600 mm from floor level
6.37 These ergonomic drawings (see Figure 54) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.
Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser
6.38 The basin should be fitted with non- touch taps.
Glove & apron dispenser
high level
Space to use basin at
Space to use
from floor level
6.39 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.
ie up to 600 mm
basin at low level,
Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)
Concealed waste
~120 service duct
Minimum distance to side wall
Paper towel dispenser
6.40 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.
(50) Minimum clearance between paper towel dispenser and duct
Projecting concealed services duct
Concealed waste
Minimum distance to side wall
~120 service duct
6.41 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.
6.42 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:
Space to use
from floor level
Space to use
ie up to 600 mm
basin at low level,
from floor level
ie above 600 mm
basin at high level,
passing
ambulant
Comfortable reach to side of basin
“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”
Flush concealed services duct
6.43 Lever taps are not illustrated.
6.44 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.
[HBN 00-03 – PDF page 75]
Clinical workstation
6.45 This ergonomic drawing (see Figure 55) shows the space requirements for a clinical workstation.
6.46 The clinical workstation is intended for accessing and updating patient records within a clinical environment. It should only be used for short periods of time.
Figure 55 Space requirements for a clinical workstation
Approximate
Approximate
sitting height
standing height
Chair
standing at
clinical
workstation
workstation
sitting at clinical
[HBN 00-03 – PDF page 76]
6 Generic clinical spaces: Treatment rooms
Couch: double-sided access
6.48 Ceiling-mounted examination lights should be provided where double-sided couch access is required.
6.47 These ergonomic drawings (see Figure 56) show the space requirements for double-sided access to a three-section couch. The overall general space requirements for a three-section couch are the same as for a two-section couch.
Figure 56 Space requirements for double-sided access to a three-section couch
Approximate
Suction bottle bracket to be below patient’s chest
Engineering services outlets requirements
see HTM 02-01 and HTM 08-03
height range of couch
Space for changing
examination/
examination/
treatment
treatment
Couch with paper roll attached
Ceiling- mounted examination light
examination/treatment
[HBN 00-03 – PDF page 77]
Treatment chairs (various): double-sided access
including stirrups, leg supports or footrests. The use of the various methods is subject to local clinical and/or patient/client preferences.
6.49 These ergonomic drawings (see Figure 57) show the space requirements for double-sided access to a variety of treatment chairs.
6.52 The podiatry treatment chair incorporates separate leg supports, which may be adjusted independently of one another.
6.50 The reclining treatment/therapy chair provides the most flexible option for general examinations and treatments.
6.53 The activity space for the podiatry treatment chair assumes the examination light is attached to the podiatry trolley. The illustrated chair is mobile. Floor-mounted chairs are also available although these may reduce flexibility in room use.
6.51 The reclining gynaecology chair may be used for general examinations and treatments or female internal examinations. A variety of attachments are available to assist internal examinations of females
Figure 57 Space requirements for double-sided access to a variety of treatment chairs
changing
Space for changing
examination/ treatment
Reclining gynaecology chair
Reclining treatment chair
Ceiling- mounted examination light
reclining position
reclining position
Approx length of chair in
Approx length of chair in
Stool
approx 1050
Stool
treatment
access
examination/
access
Space for changing
access side of treatment chair
access
Podiatry treatment chair
reclining position
Approx length of chair in
chair in sitting position
Approximate length of
Stool
examination
access
for treatment/
Approximate space
[HBN 00-03 – PDF page 78]
6 Generic clinical spaces: Treatment rooms
Dressing and undressing: ambulant
6.54 These ergonomic drawings (see Figure 58) show the space requirements for ambulant dressing and undressing.
6.55 An identical space provision is suitable for semi- ambulant users though it should be located adjacent to a seating area.
Figure 58 Space requirements for ambulant dressing and undressing
Maximum height
of permissible
low-level
obstructions
Space for full arm movements
when dressing and undressing
Space for arm movements when dressing and undressing
Space at floor/low level for dressing and undressing
Space at floor/low
level for dressing
and undressing
Space for arm movements
when dressing and undressing