[HBN 00-03 – PDF page 60]

5 Generic clinical spaces: Recovery spaces

5.5 Natural light should be provided.

Recovery/assessment room (2 places)

Room description and layout

5.6 See Health Technical Memorandum 02-01 – ‘Medical gas pipeline systems’ and Health Technical Memorandum 08-03 – ‘Bedhead services’ for specific requirements on the use of medical gases.

5.1 A recovery/assessment space is intended as a generic space where patient recovery following a procedure requiring local anaesthetic or sedation (not general anaesthetic) and a variety of assessments (for example maternity) and treatments (for example dialysis) may be undertaken. Patients may also be transferred here from a post-anaesthetic recovery area.

5.7 The room layout provided (see Figure 42) includes two couches. It is assumed there will be one practitioner for every two patients/clients. When this space is used, consideration must be given to the ‘Delivering Same Sex Accommodation’ programme (DSSA), including the attendance of partners/carers.

5.2 It may be co-located with a seated recovery area and/or post-anaesthetic recovery area.

5.8 For sizing recovery/assessment rooms generally, the following allowances may be used:

• 9 m² per couch/reclining treatment chair;

5.3 Immediate access is required to a resuscitation trolley. If this is not held within the room, it should be located conveniently nearby.

• 4–6 m² for clinical support (for example clinical workstation, clinical wash-hand basin etc).

5.4 An overall width of 3350 mm is required for mobile hoist transfer. Therefore, 600 mm of the adjacent space will be required for this purpose.

[HBN 00-03 – PDF page 61]

Figure 42 Recovery/assessment room

Engineering services outlet zone

Engineering services outlet zone

Bedside locker

Bedside locker

Stool

Reassurance light

Reassurance light

Clinical workstation

Clinical wash-hand basin

Supplies trolley

Sack holder Sack holder

Paper towel dispenser

Engineering services outlet zone

Glove and apron dispenser

Engineering services outlet zone

[HBN 00-03 – PDF page 62]

5 Generic clinical spaces: Recovery spaces

Figure 43 Space requirements for standing use of a clinical wash-hand basin

Ergonomic drawings

assembly

Clinical wash-hand basin

Space to use basin at high level, ie above 600 mm from floor level

5.9 These ergonomic drawings (see Figure 43) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

5.10 The basin should be fitted with non- touch taps.

Glove & apron dispenser

high level

Space to use basin at

Space to use

5.11 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

from floor level

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

5.12 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

Concealed waste

Minimum distance to side wall

~120 service duct

5.13 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

5.14 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

Comfortable reach to side of basin

Flush concealed services duct

5.15 Lever taps are not illustrated.

5.16 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 63]

Clinical workstation

5.17 This ergonomic drawing (see Figure 44) shows the space requirements for a clinical workstation.

5.18 The clinical workstation is intended for accessing and updating patient records within a clinical environment. It should only be used for short periods of time.

Figure 44 Space requirements for a clinical workstation

Approximate

Approximate

sitting height

standing height

Chair

standing at

clinical

workstation

workstation

sitting at clinical

[HBN 00-03 – PDF page 64]

5 Generic clinical spaces: Recovery spaces

Treatment chairs (various): double-sided access

including stirrups, leg supports or footrests. The use of the various methods is subject to local clinical and/or patient/client preferences.

5.19 These ergonomic drawings (see Figure 45) show the space requirements for double-sided access to a variety of treatment chairs.

5.22 The podiatry treatment chair incorporates separate leg supports, which may be adjusted independently of one another.

5.20 The reclining treatment/therapy chair provides the most flexible option for general examinations and treatments.

5.23 The activity space for the podiatry treatment chair assumes the examination light is attached to the podiatry trolley. The illustrated chair is mobile. Floor-mounted chairs are also available although these may reduce flexibility in room use.

5.21 The reclining gynaecology chair may be used for general examinations and treatments or female internal examinations. A variety of attachments are available to assist internal examinations of females

Figure 45 Space requirements for double-sided access to a variety of treatment chairs

changing

Space for changing

examination/ treatment

Reclining gynaecology chair

Reclining treatment chair

Ceiling- mounted examination light

reclining position

reclining position

Approx length of chair in

Approx length of chair in

Stool

approx 1050

Stool

treatment

access

examination/

access

Space for changing

access side of treatment chair

access

Podiatry treatment chair

reclining position

Approx length of chair in

chair in sitting position

Approximate length of

Stool

examination

access

for treatment/

Approximate space

[HBN 00-03 – PDF page 65]

Health Building Note 00-03 – Clinical, clinical support and specialist spaces

Dressing and undressing: ambulant

Seated recovery area

Room description

5.24 These ergonomic drawings (see Figure 46) show the space requirements for ambulant dressing and undressing.

5.26 This is an open-plan area with easy chairs. It will be used for patients with low clinical needs to sit and recover following a procedure (which may have required a local anaesthetic).

5.25 An identical space provision is suitable for semi- ambulant users though it should be located adjacent to a seating area.

Figure 46 Space requirements for ambulant dressing and undressing

5.27 It should be an open-plan lounge-type space with comfortable upholstered, easily cleanable, chairs and may simply form a discrete part of a waiting area.

5.28 The area should contain a separate zone for clinical hand-washing.

5.29 Natural light should be provided.

5.30 Beverage facilities should be available nearby.

5.31 No room layout has been provided. For sizing seated recovery areas, the following allowances may be used:

• 1.5 m² per easy chair;

Maximum height

of permissible

low-level

obstructions

Space for full arm movements

when dressing and undressing

• 3 m² per wheelchair space.

Space for arm movements when dressing and undressing

Space at floor/low level for dressing and undressing

Space at floor/low

level for dressing

and undressing

Space for arm movements

when dressing and undressing