Home › Scotland (NHS Scotland Assure / HFS) › HBN 00-03 › Health Building Note 00-03 – 3 Generic clinical spaces: Consulting, examination and interview spaces (pages 37–44)

HBN 00-03: Health Building Note 00-03 – 3 Generic clinical spaces: Consulting, examination and interview spaces (pages 37–44)

Core guidance - Clinical and clinical support spaces (HBN 00-03) · PDF pages 37–44 of 166 · Source file: hbn-00-03-oct-2014.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS National Services Scotland.

[HBN 00-03 – PDF page 37]

Dressing and undressing: ambulant

3.80 These ergonomic drawings (see Figure 19) show the space requirements for ambulant dressing and undressing.

3.81 An identical space provision is suitable for semi- ambulant users though it should be located adjacent to a seating area.

Figure 19 Space requirements for ambulant dressing and undressing

Maximum height

of permissible

low-level

obstructions

Space for full arm movements

when dressing and undressing

Space for arm movements when dressing and undressing

Space at floor/low level for dressing and undressing

Space at floor/low

level for dressing

and undressing

Space for arm movements

when dressing and undressing

[HBN 00-03 – PDF page 38]

3 Generic clinical spaces: Consulting, examination and interview spaces

Examination/physical therapy room

Room description and layout

3.85 The room layout provided (see Figure 20) includes a standard three-section couch. However, for maximum flexibility, of general use, a reclining treatment/therapy chair that supports patient/client in sitting or supine position is recommended.

3.82 An examination/physical therapy space is intended as a generic space where a variety of examinations, tests and therapies (for example physiotherapy, acupuncture and massage) may be undertaken.

3.83 The following procedures may take place in this room:

3.86 Alternatively, the room can accommodate a reclining gynaecology chair or bobath plinth (for physiotherapy treatments) although the clinical workstation would conflict fractionally with the space required around the plinth.

3.87 A touchdown base may be located nearby in place of the clinical workstation in the room.

• non-invasive procedures, i.e. procedures that do not break the skin, for example changing a dressing;

3.88 Where trolley access is required, a door and a half in a 1500 mm aperture will be required.

• minimally invasive procedures, i.e. procedures that break or puncture the skin, for example injections, taking blood etc.

3.89 Locating the privacy curtain across the width of the room will allow an attendant to wait outside the examination area.

3.84 It has been sized to accommodate mobile diagnostic equipment, for example mobile ultrasound equipment.

Figure 20 Examination/physical therapy room

Supplies trolley

Chair

Sack holder

Couch

Clinical wash-hand basin

Sack holder

Paper towel dispenser

Ceiling- mounted examination light

Glove and apron dispenser

Optional chair

Possible location of privacy curtain

Optional clinical workstation

Possible location of privacy curtain

Possible location of door & half

Engineering services outlet zone Engineering services outlet zone

Engineering services outlet zone

Possible location of door & half

[HBN 00-03 – PDF page 39]

Separate versus combined consulting and examination rooms

3.90 Separate consulting and examination rooms may be justified for some clinics. However, they do not provide the flexibility of combined consulting/ examination rooms. See Figure 21.

3.91 Where separate consulting and examination rooms are provided, there should not be adjoining doors between the rooms for reasons of patient privacy.

3.92 A comparison of the space requirements and utilisation of four combined consulting/ examination rooms against two consulting rooms and four examination rooms shows the combined rooms require less space and offer greater utilisation.

Figure 21 Combined versus separate consulting and examination rooms

Example 1: 4 Consulting/examination rooms (@ 16 m2) Range of uses: 1–4 doctors 1–4 clinic sessions

Example 2: 2 Consulting and 4 examination rooms (@ 12 m2) Range of uses: 1–2 doctors 1–2 clinic sessions

[HBN 00-03 – PDF page 40]

3 Generic clinical spaces: Consulting, examination and interview spaces

Ergonomic drawings

Clinical workstation

3.94 The clinical workstation is intended for accessing and updating patient records within a clinical environment. It should only be used for short periods of time.

3.93 This ergonomic drawing (see Figure 22) shows the space requirements for a clinical workstation.

Figure 22 Space requirements for a clinical workstation

Approximate

Approximate

sitting height

standing height

Chair

standing at

clinical

workstation

workstation

sitting at clinical

[HBN 00-03 – PDF page 41]

Figure 23 Space requirements for standing use of a clinical wash-hand basin

Clinical wash-hand basin

assembly

Space to use basin at high level, ie above 600 mm from floor level

3.95 These ergonomic drawings (see Figure 23) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

3.96 The basin should be fitted with non- touch taps.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

Glove & apron dispenser

high level

Space to use basin at

3.97 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

Space to use

from floor level

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

3.98 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

3.99 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

Concealed waste

Minimum distance to side wall

~120 service duct

3.100 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

“Elbow height for shod, slightly bent

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

Comfortable reach to side of basin

3.101 Lever taps are not illustrated.

Flush concealed services duct

3.102 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 42]

3 Generic clinical spaces: Consulting, examination and interview spaces

Couch: double-sided access

3.104 Ceiling-mounted examination lights should be provided where double-sided couch access is required.

3.103 These ergonomic drawings (see Figure 24) show the space requirements for double-sided access to a three-section couch. The overall general space requirements for a three-section couch are the same as for a two-section couch.

Figure 24 Space requirements for double-sided access to a three-section couch

Approximate

Suction bottle bracket to be below patient’s chest

Engineering services outlets requirements

see HTM 02-01 and HTM 08-03

height range of couch

Space for changing

examination/

examination/

treatment

treatment

Couch with paper roll attached

Ceiling- mounted examination light

examination/treatment

[HBN 00-03 – PDF page 43]

Treatment chairs (various): double-sided access

including stirrups, leg supports or footrests. The use of the various methods is subject to local clinical and/or patient/client preferences.

3.105 These ergonomic drawings (see Figure 25) show the space requirements for double-sided access to a variety of treatment chairs.

3.108 The podiatry treatment chair incorporates separate leg supports, which may be adjusted independently of one another.

3.106 The reclining treatment/therapy chair provides the most flexible option for general examinations and treatments.

3.109 The activity space for the podiatry treatment chair assumes the examination light is attached to the podiatry trolley. The illustrated chair is mobile. Floor-mounted chairs are also available although these may reduce flexibility in room use.

3.107 The reclining gynaecology chair may be used for general examinations and treatments or female internal examinations. A variety of attachments are available to assist internal examinations of females

Figure 25 Space requirements for double-sided access to a variety of treatment chairs

changing

Space for changing

examination/ treatment

Reclining gynaecology chair

Reclining treatment chair

Ceiling- mounted examination light

reclining position

reclining position

Approx length of chair in

Approx length of chair in

Stool

approx 1050

Stool

treatment

access

examination/

access

Space for changing

access side of treatment chair

access

Podiatry treatment chair

reclining position

Approx length of chair in

chair in sitting position

Approximate length of

Stool

examination

access

for treatment/

Approximate space

[HBN 00-03 – PDF page 44]

3 Generic clinical spaces: Consulting, examination and interview spaces

Bobath plinth

3.110 The ergonomic drawing (see Figure 26) shows the space requirements for doublesided access to a two-section bobath plinth.

Figure 26 Bobath plinth: double-sided access

Engineering services outlets requirements

see HTM 02-01 and HTM 08-03

Approx adjustable height

range

changing

examination/ treatment

examination/ treatment

Mirror

Optional harness traction

Bobath plinth

Approximate

Stool

length of plinth

access