[HBN 00-03 – PDF page 29]

Figure 11 Space requirements for standing use of a clinical wash-hand basin

Clinical wash-hand basin

assembly

Space to use basin at high level, ie above 600 mm from floor level

3.38 These ergonomic drawings (see Figure 11) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

3.39 The basin should be fitted with non- touch taps.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

Glove & apron dispenser

high level

Space to use basin at

3.40 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

Space to use

from floor level

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

3.41 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

3.42 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

Concealed waste

Minimum distance to side wall

~120 service duct

3.43 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

3.44 Lever taps are not illustrated.

Comfortable reach to side of basin

Flush concealed services duct

3.45 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 30]

3 Generic clinical spaces: Consulting, examination and interview spaces

Couch: double-sided access

3.48 Ceiling-mounted examination lights should be provided where double-sided couch access is required.

3.47 These ergonomic drawings (see Figure 12) show the space requirements for double-sided access to a three-section couch. The overall general space requirements for a three-section couch are the same as for a two-section couch.

Figure 12 Space requirements for double-sided access to a three-section couch

Approximate

Suction bottle bracket to be below patient’s chest

Engineering services outlets requirements

see HTM 02-01 and HTM 08-03

height range of couch

Space for changing

examination/

examination/

treatment

treatment

Couch with paper roll attached

Ceiling- mounted examination light

examination/treatment

[HBN 00-03 – PDF page 31]

Treatment chairs (various): double-sided access

use of the various methods is subject to local clinical and/or patient/ client preferences.

3.49 These ergonomic drawings (see Figure 13) show the space requirements for double-sided access to a variety of treatment chairs.

3.52 The podiatry treatment chair incorporates separate leg supports, which may be adjusted independently of one another.

3.50 The reclining treatment/therapy chair provides the most flexible option for general examinations and treatments.

3.53 The activity space for the podiatry treatment chair assumes the examination light is attached to the podiatry trolley. The illustrated chair is mobile. Floor-mounted chairs are also available although these may reduce flexibility in room use.

3.51 The reclining gynaecology chair may be used for general examinations and treatments or female internal examinations. A variety of attachments are available to assist internal examinations of females including stirrups, leg supports or footrests. The

Figure 13 Space requirements for double-sided access to a variety of treatment chairs

changing

Space for changing

examination/ treatment

Reclining gynaecology chair

Reclining treatment chair

Ceiling- mounted examination light

reclining position

reclining position

Approx length of chair in

Approx length of chair in

Stool

approx 1050

Stool

treatment

access

examination/

access

Space for changing

access side of treatment chair

access

Podiatry treatment chair

reclining position

Approx length of chair in

chair in sitting position

Approximate length of

Stool

examination

access

for treatment/

Approximate space

[HBN 00-03 – PDF page 32]

3 Generic clinical spaces: Consulting, examination and interview spaces

Dressing and undressing: ambulant

3.55 An identical space provision is suitable for semi- ambulant users though it should be located adjacent to a seating area.

3.54 These ergonomic drawings (see Figure 14) show the space requirements for ambulant dressing and undressing.

Figure 14 Space requirements for ambulant dressing and undressing

Maximum height

of permissible

low-level

obstructions

Space for full arm movements

when dressing and undressing

Space for arm movements when dressing and undressing

Space at floor/low level for dressing and undressing

Space at floor/low

level for dressing

and undressing

Space for arm movements

when dressing and undressing

[HBN 00-03 – PDF page 33]

Consulting/examination room: single- sided couch access

Room description and layout

3.56 This room is intended as a flexible space for consultations and examinations for use by a wide range of specialties.

3.60 The layout shows the clinical wash-hand basin within the curtained examination area. However, its location should be subject to local policy and infection control advice. It must be easily accessible from both the consultation and examination areas. The curtain should be located to prevent it becoming contaminated from use of the clinical wash-hand basin.

3.57 The following procedures may take place in this room:

3.61 Piped medical gases are generally not required. In emergency situations it is anticipated that bottled oxygen and mobile suction equipment will be readily available.

• non-invasive procedures, that is, procedures that do not break the skin, for example changing a dressing;

• minimally invasive procedures, that is, procedures that break or puncture the skin, for example injections, taking blood etc.

3.62 The room layout provided mean the patient/client will be positioned between the practitioner and the door during consultation. Consideration may be given to altering the layout to position the practitioner between the patient/client and the door for staff safety.

3.58 The room layout provided (see Figure 15) includes a two-section couch.

3.59 Where it is not necessary to access both sides of the couch, the single-sided room layout may be used but to maximise flexibility and adaptability double- sided couch access is generally recommended.

3.63 The layout has the disadvantage of the consultation area being located on the inside wall (that is, generally away from natural light) and the examination area being located on the outside wall (that is, requiring privacy control due to the likely proximity of a window).

Figure 15 Consulting/examination room, single-sided couch access

Sack holder

Wall-mounted examination light

Couch with paper roll attached

Clinical wash-hand basin

Supplies trolley

Sack holder

Paper towel dispenser

Glove and apron dispenser

Chair

Consultation workstation

Chair

Engineering services outlet zone Engineering services outlet zone

Engineering services outlet zone

[HBN 00-03 – PDF page 34]

3 Generic clinical spaces: Consulting, examination and interview spaces

Ergonomic drawings

3.66 It should be possible to rotate the computer monitor to allow the patient/client to view it.

Consultation workstation

3.67 The consultation desk should be positioned so that:

• the practitioner can acknowledge a patient/ client on entry to the room;

• the practitioner is not be silhouetted against a window when in consultation with the patient/ client.

3.64 This ergonomic drawing (see Figure 16) shows a nominal space requirement for a consultation workstation. The actual space requirement will depend upon the design and location of the chairs and the design of the desk. The illustrated desk is the recommended minimum dimension for using a flat screen computer.

3.68 A small lockable drawer should be available to store prescription pads if electronic prescriptions are not being used.

3.69 A small local printer may be provided.

3.65 The activity space is based on the practitioner sitting at the desk with the patient/client seated diagonally opposite. The desk should not be located between the practitioner and patient/client.

Figure 16 Nominal space requirement for a consultation workstation

Space for wheelchair access/withdrawal

Space to withdraw

chair from desk

withdrawn

Space for occupied upright chair with person’s legs extended, (1050) for legs

Chair

Consultation

workstation

Chair

chair from desk

Space to withdraw

Chair

Space for wheelchair access/withdrawal

upright chair

Space for occupied

Space for occupied

upright chair

[HBN 00-03 – PDF page 35]

Figure 17 Space requirements for standing use of a clinical wash-hand basin

Clinical wash-hand basin

assembly

Space to use basin at high level, ie above 600 mm from floor level

3.70 These ergonomic drawings (see Figure 17) show the space requirements for standing use of a clinical wash-hand basin assembly. For seated use, the basin will need to be lowered.

3.71 The basin should be fitted with non- touch taps.

Soap dispenser Hand cream dispenser Optional scrub solution dispenser Paper towel dispenser

Glove & apron dispenser

high level

Space to use basin at

3.72 The recommended fixing height of a lever tap on a clinical wash-hand basin is 1095 mm. Where a lever tap is used, the fixing height of the dispensers should be chosen to reduce any possible conflicts in use.

Space to use

from floor level

ie up to 600 mm

basin at low level,

Space to use basin at low level, ie up to 600 mm from floor level Elevation (showing sensor tap)

Concealed waste

~120 service duct

Minimum distance to side wall

Paper towel dispenser

3.73 The illustrated clinical wash-hand basin projects 400 mm from the back panel or wall. However, clinical wash-hand basins may vary from 350 to 500 mm projection. Where basins deeper than 400 mm are used, the impact on/from other components and/or activities undertaken within any space should be considered when evaluating any room layout.

(50) Minimum clearance between paper towel dispenser and duct

Projecting concealed services duct

3.74 The glove and apron dispenser illustrated is a combined unit; this is considered the most compact solution although separate units may also be used. Even the most compact unit cannot practically be located within comfortable reach of the basin; it should, however, be conveniently located within the room.

Concealed waste

Minimum distance to side wall

~120 service duct

3.75 The ergonomic advice for the height of horizontal elbow operated lever taps is based on the following data:

Space to use

from floor level

Space to use

ie up to 600 mm

basin at low level,

from floor level

ie above 600 mm

basin at high level,

passing

ambulant

“Elbow height for shod, slightly bent posture (as when leaning forward) for 50%ile UK male = 1134 mm, for female 1049 mm. 1090 mm is considered the best compromise for an elbow height for both male and female use. The ergonomic advice for the height of a lever tap is 75 mm below elbow height giving a figure height of approx 1015 mm.”

3.76 Lever taps are not illustrated.

Comfortable reach to side of basin

Flush concealed services duct

3.77 For detailed information on basins, see Health Building Note 00-10 Part C – ‘Sanitary assemblies’.

[HBN 00-03 – PDF page 36]

3 Generic clinical spaces: Consulting, examination and interview spaces

Couch: single-sided access

3.79 Wall-mounted examination lights should be provided where single-sided couch access is required. The light may be mounted on a horizontal rail to enable its position to be altered in the horizontal plane.

3.78 This ergonomic drawing (see Figure 18) shows the space requirements for single-sided access to a couch. It illustrates a two-section couch simply as the most likely scenario. The generic access space is believed to be the same for other types of couch.

Figure 18 Space requirements for single-sided access to a couch

height range

Approx adjustable

Engineering services outlets requirements

see HTM 02-01 and HTM 08-03

examination/ treatment

Couch with paper roll attached

Wall- mounted examination light

examination/

treatment