HTM 05-02: Appendix L: Summary of changes to the April 2014 edition

Firecode - Guidance in support of functional provisions (Fire safety in the design of healthcare premises) · PDF pages 110–112 of 112 · Source file: HTM_05-02_2015.pdf
Unofficial text extract. Tables and figures may be incomplete. Authoritative version: official PDF from NHS England.

[HTM 05-02 – PDF page 110]

Appendix L: Summary of changes to the April 2014 edition

Page 10 – paragraph 2.36, last line: “HTM 05-03 series” replaced with “HTM 05-03: Part B”.

Page 12 – first line: “Acute mental patients” replaced with “Patients with an acute mental illness or learning disabilities”.

Page 27 – paragraph 3.43 final sentence amended to read: “Therefore all stairways, other than those contained within and only serving an atrium, should be designed as escape stairways to permit vertical evacuation by the most appropriate method, see paragraphs 3.53 to 3.55.”

Page 28 – paragraph 3.55: “dependent” replaced with “independent”.

Page 31 – paragraph 3.64, fourth line: “a intensive” replaced with “an intensive”.

Page 32 – paragraph 3.69: add after last sentence, “See paragraphs 3.70 to 3.73”.

Page 36 – paragraph 4.6, first line; paragraph 4.8, third line; and paragraph 4.9, third line: “(see Appendix C)” replaced with “(see Appendix D)”

Page 41 – paragraph 5.19: “Appendix B” replaced with “Appendix A”.

Page 44 – Table 6 deleted and replaced with the following Table:

Chemical stores Store rooms

Cleaners’ room Relatives’ overnight stay room

Clothes storage Ward kitchens

Disposal rooms Communal bathrooms in mental health premises (see paragraph 2.52)

Hub rooms Linen stores

Lift motor rooms Staff on-call rooms

Main staff changing and locker rooms

Patient bedrooms provided specifically for:

• people with mental health needs

• people with learning disabilities

Key

Doors to these rooms to be kept locked shut

[HTM 05-02 – PDF page 111]

Appendix L: Summary of changes to the April 2014 edition

Door to be fitted with appropriately designed free-swing self-closing devices

Doors to be fitted with self-closing devices

Self-closing devices not required.

Table 6 Examples of fire hazard rooms

Table 6 Example of fire hazard rooms

Page 48 – paragraph 5.62, third line: “6.48” replaced with “5.66”.

Page 50 – paragraph 5.65(d): after “smoke damper”, “ – see Table 7” has been inserted.

Page 51 – paragraph 5.78: sub-paragraph (c) has been deleted.

Page 60 – paragraph 7.4, line 2: “Table 7” replaced with “Table 10”.

Page 73 – Table C1 deleted and replaced with the following table:

Table C1 Location of fire doors

Location of door Minimum period of fire resistance in terms of integrity (minutes) when tested to BS 476-221

Minimum period of fire resistance in terms of integrity (minutes) when tested to European standards2

Sub-compartment wall FD30S E30 Sa

Fire hazard rooms FD30S E30 Sa

In a compartment wall FD30S – Single-storey healthcare buildings E30 Sa

E30 Sa

FD30S – Storeys above ground in healthcare buildings fitted with sprinklers

FD60S – elsewhere E60 Sa

To a protected shaft containing a stairway or escalator:

a. accessed from a hospital street FD30S E30 Sa

E30 Sa

b. elsewhere FD30S to each of the two sets of doors to the lobby

To a protected shaft containing a lift3:

a. accessed from a hospital street FD30 E30

E30 Sa

b. elsewhere FD30S to the doors from the circulation space to the lobby

FD30 from the lift car to the lobby E30

FD60S E60 Sa

To a protected shaft containing chutes, ducts and pipes

Within a cavity barrier FD30* E30

Continued over page

[HTM 05-02 – PDF page 112]

Notes:

1. To BS 476-22 (or BS 476-8 subject to paragraph 5 in Appendix A of Approved Document B).

2. The national classifications do not automatically equate with the equivalent classifications in the European column; therefore, products cannot typically assume a European class unless they have been tested accordingly.

Unless pressurisation techniques complying with BS EN 12101-6:2005 are used, all these doors (except those marked *) should also either:

(a) have a leakage rate not exceeding 3 m3/m/hour (head and jambs only) when tested at 25 Pa under BS 476-31.1; or

(b) meet the additional classification requirement of Sa when tested to BS EN 1634-3.

3. Lift doors to be tested to BS EN 81-58.

Page 74 – First paragraph up to third bullet has been omitted and replaced with:

“Generally all fire doors should be fitted with an automatic self-closing device complying with BS EN 1154 or BS EN 1634-1, with the following exceptions:

• fire doors to patients’ bedrooms in facilities providing in-patient mental health services;

• fire doors to bedrooms in facilities for people with learning disabilities; and

• fire doors which are kept locked shut.

With the exception of doors to stairways, it may be acceptable for fire doors to be held open on electrically operated door-release mechanisms provided that all of the following criteria can be satisfied:”

List of criteria to remain unaltered.

Final sentence has been added: “Please note: The installation of operation of electro-magnetic hold open/swing free door closers should also satisfy similar criteria.”

Page 92 After the “BS EN 81-2: 1998+A3 2009” reference, the following new reference has been inserted:

“BS EN 81-58 Safety rules for the construction and installation of lifts. Examination and tests. Landing doors fire resistance test. British Standards Institute, 2003”

After the “BS EN 1154: 1997” reference, the following new reference has been inserted:

“BS EN 1155: 1997. Building hardware. Electrically powered hold-open devices for swing doors. Requirements and test methods. British Standards Institute, 1997”.