HTM 05-02: Appendix L: Summary of changes to the April 2014 edition
[HTM 05-02 – PDF page 110]
Appendix L: Summary of changes to the April 2014 edition
Page 10 – paragraph 2.36, last line: “HTM 05-03 series” replaced with “HTM 05-03: Part B”.
Page 12 – first line: “Acute mental patients” replaced with “Patients with an acute mental illness or learning disabilities”.
Page 27 – paragraph 3.43 final sentence amended to read: “Therefore all stairways, other than those contained within and only serving an atrium, should be designed as escape stairways to permit vertical evacuation by the most appropriate method, see paragraphs 3.53 to 3.55.”
Page 28 – paragraph 3.55: “dependent” replaced with “independent”.
Page 31 – paragraph 3.64, fourth line: “a intensive” replaced with “an intensive”.
Page 32 – paragraph 3.69: add after last sentence, “See paragraphs 3.70 to 3.73”.
Page 36 – paragraph 4.6, first line; paragraph 4.8, third line; and paragraph 4.9, third line: “(see Appendix C)” replaced with “(see Appendix D)”
Page 41 – paragraph 5.19: “Appendix B” replaced with “Appendix A”.
Page 44 – Table 6 deleted and replaced with the following Table:
Chemical stores Store rooms
Cleaners’ room Relatives’ overnight stay room
Clothes storage Ward kitchens
Disposal rooms Communal bathrooms in mental health premises (see paragraph 2.52)
Hub rooms Linen stores
Lift motor rooms Staff on-call rooms
Main staff changing and locker rooms
Patient bedrooms provided specifically for:
• people with mental health needs
• people with learning disabilities
Key
Doors to these rooms to be kept locked shut
[HTM 05-02 – PDF page 111]
Appendix L: Summary of changes to the April 2014 edition
Door to be fitted with appropriately designed free-swing self-closing devices
Doors to be fitted with self-closing devices
Self-closing devices not required.
Table 6 Examples of fire hazard rooms
Table 6 Example of fire hazard rooms
Page 48 – paragraph 5.62, third line: “6.48” replaced with “5.66”.
Page 50 – paragraph 5.65(d): after “smoke damper”, “ – see Table 7” has been inserted.
Page 51 – paragraph 5.78: sub-paragraph (c) has been deleted.
Page 60 – paragraph 7.4, line 2: “Table 7” replaced with “Table 10”.
Page 73 – Table C1 deleted and replaced with the following table:
Table C1 Location of fire doors
Location of door Minimum period of fire resistance in terms of integrity (minutes) when tested to BS 476-221
Minimum period of fire resistance in terms of integrity (minutes) when tested to European standards2
Sub-compartment wall FD30S E30 Sa
Fire hazard rooms FD30S E30 Sa
In a compartment wall FD30S – Single-storey healthcare buildings E30 Sa
E30 Sa
FD30S – Storeys above ground in healthcare buildings fitted with sprinklers
FD60S – elsewhere E60 Sa
To a protected shaft containing a stairway or escalator:
a. accessed from a hospital street FD30S E30 Sa
E30 Sa
b. elsewhere FD30S to each of the two sets of doors to the lobby
To a protected shaft containing a lift3:
a. accessed from a hospital street FD30 E30
E30 Sa
b. elsewhere FD30S to the doors from the circulation space to the lobby
FD30 from the lift car to the lobby E30
FD60S E60 Sa
To a protected shaft containing chutes, ducts and pipes
Within a cavity barrier FD30* E30
Continued over page
[HTM 05-02 – PDF page 112]
Notes:
1. To BS 476-22 (or BS 476-8 subject to paragraph 5 in Appendix A of Approved Document B).
2. The national classifications do not automatically equate with the equivalent classifications in the European column; therefore, products cannot typically assume a European class unless they have been tested accordingly.
Unless pressurisation techniques complying with BS EN 12101-6:2005 are used, all these doors (except those marked *) should also either:
(a) have a leakage rate not exceeding 3 m3/m/hour (head and jambs only) when tested at 25 Pa under BS 476-31.1; or
(b) meet the additional classification requirement of Sa when tested to BS EN 1634-3.
3. Lift doors to be tested to BS EN 81-58.
Page 74 – First paragraph up to third bullet has been omitted and replaced with:
“Generally all fire doors should be fitted with an automatic self-closing device complying with BS EN 1154 or BS EN 1634-1, with the following exceptions:
• fire doors to patients’ bedrooms in facilities providing in-patient mental health services;
• fire doors to bedrooms in facilities for people with learning disabilities; and
• fire doors which are kept locked shut.
With the exception of doors to stairways, it may be acceptable for fire doors to be held open on electrically operated door-release mechanisms provided that all of the following criteria can be satisfied:”
List of criteria to remain unaltered.
Final sentence has been added: “Please note: The installation of operation of electro-magnetic hold open/swing free door closers should also satisfy similar criteria.”
Page 92 After the “BS EN 81-2: 1998+A3 2009” reference, the following new reference has been inserted:
“BS EN 81-58 Safety rules for the construction and installation of lifts. Examination and tests. Landing doors fire resistance test. British Standards Institute, 2003”
After the “BS EN 1154: 1997” reference, the following new reference has been inserted:
“BS EN 1155: 1997. Building hardware. Electrically powered hold-open devices for swing doors. Requirements and test methods. British Standards Institute, 1997”.